When Can a Standard Electric Motor Be Used on a Cold Storage Condenser Fan?

When Can a Standard Electric Motor Be Used on a Cold Storage Condenser Fan?

On a cold storage condenser, a standard three-phase motor can be used if the fan propeller is fitted to the shaft of a separate IEC-frame motor or driven by a belt. In external-rotor fans, where motor and propeller form a single unit, and in electronically controlled EC fans, a standard motor does not directly replace the old motor. In short, what decides is not the power but the design of the fan.

A cold store has two groups of fans: the evaporator fans inside the room and the condenser fans outside. This article deals only with the condenser side; the cold, humid indoor conditions of evaporator fans are a separate subject.

First, identify the fan type

Before starting the replacement, determine the design of the existing fan. Three situations are found on site:

Fan designHow to recognise itCan a standard motor be used?
External-rotor axial fanThe propeller is attached directly to the motor's rotating outer casing; no separate shaft end is visible. The unit hangs on the fan guard as one piece.Not directly; the fan unit is assessed as a whole.
EC fanThere is an electronic board or control box on the motor and a control cable such as 0–10 V.Not directly; the speed control system also changes.
Fan driven by an IEC-frame motorThe motor's nameplate shows a frame code such as 90L or 100L; the propeller is fitted to the shaft with a keyed hub or connected by a belt.Yes, after checking frame, shaft and mounting compatibility.

Most small and medium packaged condenser units have external-rotor fans. On large field-erected condensers, air-cooled chillers and some evaporative condensers, fans with IEC-frame motors are more common.

Why is direct replacement not possible on external-rotor and EC fans?

In an external-rotor motor, the stator is inside and the rotor outside; the propeller blades are bolted directly to the rotating rotor. In a standard induction motor, the rotor turns inside and power is taken from the shaft end. These two designs do not share mounting dimensions. If you want to use a standard motor, the propeller hub, motor support foot or bridge and the fan guard must be redesigned; this is not a motor replacement but a rebuild of the fan unit, and it should be carried out with the fan manufacturer's data.

In EC fans, the motor comes with its own drive and receives a speed command from the refrigeration controller. If a standard motor is fitted instead, a separate frequency inverter is needed for speed control and the control signal must be rewired. External-rotor and EC motors belong to the special motor class and may fall outside the standard range in HEM Motor's 2026 catalogue; you can ask us with a photo of the nameplate.

What should be checked where a standard motor can be used?

If the fan is driven by an IEC-frame motor, the replacement can be made with a few concrete checks:

  • Number of poles and propeller speed: Condenser propellers usually turn slowly for low noise; that is why 6-pole (about 950 rpm) and sometimes 8-pole motors are used. The new motor must have the same number of poles. Fitting a 4-pole model in place of a 6-pole motor raises the propeller speed by about half; according to the fan law, the power demand grows several times over and the motor is overloaded.
  • Shaft direction and mounting arrangement: On horizontal condensers, the motor usually runs vertically with the shaft up or down. In vertical mounting, the side of the motor exposed to rain changes; the terminal box and drainage direction are planned accordingly.
  • Shaft end and propeller hub: The bore diameter and keyway of the hub that seats on the shaft must match the new motor's shaft end. Check the dimensions on the 2D technical drawings.
  • Voltage: Models up to 3 kW are rated 230/400 V and are connected in star on a 400 V supply. Read the nameplate and position the terminal links accordingly.

Mounting options (B3, B5, B14, B34, B35 and vertical V1/V3/V5/V6/V15) are offered according to the frame and the flange size is confirmed with the order; for details on vertical mounting, see our vertical mounting article.

You can find standard models suitable for condenser fans and their current prices on the buy electric motors page.

Outdoors: sun, rain and hot discharge air

The condenser rejects the heat removed from the store. So the motor works both outdoors and in or right next to the condenser's heated air. On the hottest summer days, when the condenser is most heavily loaded, the air around the motor is also at its hottest.

  • IP55 and rain: HEM Motor models have IP55 protection, which protects against water sprayed from any direction. In vertical shaft-up mounting, rainwater falls straight onto the shaft area and fan cover; a rain cover should be used and the motor must not sit in a pocket where water collects.
  • Condensation: A motor that cools down at night can draw in moisture in the morning. The terminal box gasket and cable glands must be sound; this is even more important for standby condenser fans that do not run for long periods.
  • Sun and hot discharge: The highest air temperature at the motor's location is stated in the order. The airflow direction must be kept so that hot air is thrown off by the propeller, not over the motor frame.
  • Dirt and leaves: Like the condenser fins, the motor's fan cover can be blocked by dust and leaves; cleaning should be part of the maintenance plan.

Prices and technical data are on the product pages; choose a model and order online.

Speed control and pressure regulation

In winter, condenser fans are switched off in stages or slowed down to maintain condensing pressure. On fans with IEC-frame motors, this is usually done with a frequency inverter. Our three-phase ranges are suitable for speed control with a frequency inverter; as explained in the inverter question, an external fan may be required for long periods of full-torque operation at low speed, and a dv/dt or sine filter is considered if the drive-motor cable is long. Since fan load falls rapidly at low speed, full torque at low speed is rarely seen on a condenser fan; even so, drive use and cable length should be stated in the order.

Where the condenser is genuinely insufficient in summer, enlarging the motor or changing the number of poles is not the solution; condenser capacity, fin cleanliness and the fan propeller should be assessed together with the refrigeration contractor.

Example models for condenser fans

The actual power is determined from the old motor's nameplate. The following are examples from the range that may be found on small and medium condenser fans:

  • 90S-6 (aluminium frame): 0.75 kW, 6-pole, 935 rpm rated speed, 230/400 V.
  • 90L-6 (aluminium frame): 1.1 kW, 6-pole, 945 rpm, 230/400 V.
  • 100L-6 (aluminium frame): 1.5 kW, 6-pole, 949 rpm, 230/400 V.
  • 90S-4 (aluminium frame): 1.1 kW, 4-pole, 1,445 rpm, 230/400 V; only if the existing fan was designed for a 4-pole motor.

For other motors in HVAC applications, see the HVAC sector motors page.

Hypothetical example: motor replacement on a condenser

The following situation is hypothetical. Suppose that on the field-erected condenser of a fruit store, the motor of one of four fans has burnt out. The nameplate shows 1.1 kW, 6-pole, 90L frame and 230/400 V; the motor is in a vertical shaft-up position and the propeller is fitted to the shaft with a keyed hub.

  • Since the fan is driven by an IEC-frame motor, a standard motor can be used; the 90L-6 with the same power and number of poles is selected.
  • The shaft end and flange size are compared with the technical drawing, and the vertical mounting arrangement is specified in the order.
  • Traces of water are seen in the burnt motor's terminal box; a rain cover is added to the new motor and the cable gland is positioned facing down.
  • The motor is connected in star on the 400 V supply; since no drive is used, there is no additional condition.

Conclusion and information to send for a quote

On a condenser fan, a standard motor is the right choice if the fan is driven by an IEC-frame motor; on external-rotor and EC fans, the fan unit as a whole is assessed first. For a quote, send a photo of the existing motor's nameplate, a general photo of the fan, the number of poles, the mounting orientation (shaft up/down/horizontal), the propeller hub size, the voltage and whether a drive is used. Review suitable models and prices on the buy electric motors page. Share a photo of your current motor's nameplate, its speed and mounting details via the send motor nameplate page and request a quote for the right model; our contact page is open for questions.

Frequently Asked Questions

How can I tell whether the condenser fan has an external rotor?

If the propeller is attached directly to the motor's rotating outer casing and no separate shaft end is visible, the fan has an external rotor. If the nameplate shows an IEC frame code (e.g. 90L), the motor is of standard design.

Can I fit a 4-pole motor instead of a 6-pole condenser motor?

No; the propeller speed rises by about half, the power demand grows several times over and the motor is overloaded. Keep the number of poles.

Is an IP55 motor sufficient on an outdoor condenser?

IP55 is widely used for protection against rain and dust; in vertical shaft-up mounting, a rain cover and the correct cable entry direction are also important. State the ambient conditions in the order.

Can an inverter be used to reduce fan speed in winter?

Yes, our three-phase ranges are suitable for speed control with a frequency inverter. State drive use and cable length in the order.

HEM Motor Models Related to This Article

The cards show example models related to the topic. A suitable motor is not chosen by power alone: compare speed, voltage, mounting, shaft and connection dimensions on the product page; if unsure, send a photo of the existing motor’s nameplate on WhatsApp.

0.75 kW 1000 rpm Aluminium Frame Electric Motor 90S-6

90S-6

0.75 kW · 1000 rpm

  • Aluminium frame · IEC 90S
  • 935 rpm · IP55
  • Mounting: B3 foot; flange (B5/B14/B35) depending on frame — confirmed with the order

US$104.24 (€93.03)

View product
1.1 kW 1000 rpm Aluminium Frame Electric Motor 90L-6

90L-6

1.1 kW · 1000 rpm

  • Aluminium frame · IEC 90L
  • 945 rpm · IP55
  • Mounting: B3 foot; flange (B5/B14/B35) depending on frame — confirmed with the order

US$130.59 (€116.54)

View product
1.5 kW 1000 rpm Aluminium Frame Electric Motor 100L-6

100L-6

1.5 kW · 1000 rpm

  • Aluminium frame · IEC 100L
  • 949 rpm · IP55
  • Mounting: B3 foot; flange (B5/B14/B35) depending on frame — confirmed with the order

US$160.93 (€143.62)

View product