When choosing an electric motor for a feed dosing screw, the real goal is for every turn of the screw to carry the same amount at low flow; to achieve this, before moving on to motor power, the gearbox ratio, the lowest frequency the motor may run at and the torque required at start are decided together. Because flow is proportional to screw speed, the motor's ability to turn at low speed without slipping or overheating is the basis of feeding stability.
What does flow depend on in a dosing screw?
The volume a screw carries is the amount the space between the flights advances in one turn multiplied by the number of turns per minute. That is why the most direct way to adjust flow is to change screw speed.
Volumetric flow is calculated approximately as Q = (π/4) × (D² − d²) × s × φ × n. Here D is the screw outer diameter, d the shaft diameter, s the pitch, φ the fill factor and n the speed per minute. The fill factor depends on the product's flowability, the screw's inclination and the feed hopper design; the correct value comes from the machine manufacturer or a calibration weighing (general information; confirm with the machine manufacturer).
On site the formula means something simple: if speed halves, flow roughly halves too. If speed is unstable, so is flow.
Hypothetical example: how does the speed range determine flow?
The values below are hypothetical and were chosen to show the method. A screw outer diameter of 100 mm, shaft diameter of 30 mm, pitch of 100 mm, fill factor of 0.4 and feed bulk density of 0.6 t/m³ are assumed.
| Screw speed | Volumetric flow | Mass flow |
|---|---|---|
| 10 rpm | ≈ 0.17 m³/h | ≈ 0.10 t/h |
| 20 rpm | ≈ 0.34 m³/h | ≈ 0.21 t/h |
| 40 rpm | ≈ 0.69 m³/h | ≈ 0.41 t/h |
The volume carried per turn is about 0.000286 m³. A range between 10 and 40 rpm changes flow by up to four times. If the recipe contains small additives, the lower end becomes even more important.
The real question is which frequencies this range corresponds to on the motor side. If a six-pole motor running at 935 rpm at mains frequency is connected to a 40 rpm screw speed through a gearbox of about 23.4 ratio, the motor runs at around 12.5 Hz for 10 rpm. The shop page can be used to view power and speed steps side by side.
Why does the motor struggle at low frequency?
A screw is a constant-torque load: even when speed drops, the torque needed to push the feed hardly decreases. The motor, however, is cooled by a fan fitted to its own shaft; as the shaft slows, the cooling air weakens too. The result is that a motor running at full torque at low frequency for long periods heats up. Even if winding temperature does not exceed its limit, insulation life is shortened. This is solved in one of two ways: either the gearbox ratio is increased to raise the motor's lowest operating frequency, or a separate fan running independently of the motor's speed is added. Our three-phase series are suitable for speed control with a frequency inverter; long operation at low speed with full torque may require a separate fan; if the drive-to-motor cable is long, a dv/dt or sine filter is considered; these conditions are stated with the order.
Choosing the ratio is a balance. As the ratio grows, the motor turns faster and cooler, but reaching the upper flow may require going above 50 Hz; in this region the torque the motor can deliver decreases.
Why does feeding fluctuate if speed does not stay constant?
When load rises, the speed of an asynchronous machine drops slightly; this difference is called slip. As the level in the feed hopper changes, the load seen by the screw changes too, motor speed varies by a few percent and flow shifts by the same proportion.
Slip compensation or vector control mode in frequency inverters largely corrects this deviation. If tighter accuracy is required, an encoder is fitted to the motor shaft and closed-loop speed control is set up; encoder mounting is specified at the start of motor selection.
There is also mechanical pulsation.
A single-flight screw drops a heap at the outlet once every turn. At low speed this pulse becomes noticeable. A double-flight screw or a smaller pitch smooths the output. This is a screw design issue, not a motor one, but on site it is often blamed on the motor.