Spare electric motor planning for power plant auxiliary systems means ranking every auxiliary motor (feed and condensate pumps, boiler fans, cooling tower fans, fuel and ash handling drives) by whether the unit sheds load when it stops, and setting aside ready motors in the store wherever the installed standby pump is not enough.
An installed standby (a second pump, a second fan) covers the failure, but the unit runs without backup until the failed motor comes back; a motor in the store closes exactly that open window. Taking the auxiliary systems one by one makes it clear which motor should have a shelf spare and where the installed standby can be relied on.
Why keep a motor in the store when there is already an installed standby pump?
In power plants, feed water, condensate and cooling water pumps are usually installed in twos or threes; one runs while the other waits ready to start automatically. This arrangement prevents the unit from tripping at the first failure. But when the motor of the running pump burns out, the second pump that takes over is now on its own. If rewinding or delivery of a new motor takes weeks, the unit runs without any safeguard for that whole period.
During this period without backup, a second failure means direct load shedding or a unit stop. When a motor with the same power, speed and connection is in the store, the failed motor is removed, the spare is fitted and the installed redundancy is restored within a few shifts. The unit is protected again. The aim of planning is not to keep a shelf counterpart for every motor, but to pick out the drives whose time without backup is costly for the plant.
Sorting auxiliary drives into three classes by their effect on the unit
Start by drawing up a list of all auxiliary motors with their nameplate data: power, speed, voltage, frame number, mounting type, whether they run direct-on-line or on a drive, and how many are installed. Then ask one question for each drive: what does the unit do if this motor stops?
Class A covers drives whose stop makes the unit shed load or trip on protection; boiler fans installed without standby, single-line fuel feeders and pumps with no installed standby fall into this group.
Class B covers drives that reduce capacity but do not stop the unit; losing a single fan in a multi-cell cooling tower spoils condenser vacuum in summer and reduces load.
Class C covers ventilation, drainage and workshop drives that have no effect on plant operation for some time.
| Auxiliary drive | Typical installed redundancy | Effect if it stops | Store spare approach |
|---|---|---|---|
| Boiler feed pump | 2×100% or 3×50% | Standby starts, then the unit runs without backup | One motor of the same type on the shelf |
| Condensate pump | 2×100% | Period of operation without backup | One on the shelf, common frame with the cooling water pump if possible |
| Induced and forced draft fans | Often 2×50% | Load drops when one fan is lost | Shelf motor or rewinding plan for large ratings |
| Cooling tower fans | Many cells, no separate standby | Capacity loss in summer | One or two motors depending on the number of cells |
| Fuel feeder, ash and slag conveyor | Often a single line | Fuel or ash flow stops | Shelf motor is a must |
| Compressed air compressor | Usually with standby | Instrument and valve air at risk | Covered from a common power group |
Why are fuel and ash line motors overlooked in most plants?
In plants firing coal, lignite or biomass, fuel feeder screws, apron feeders, bucket elevators and ash conveyors get less attention than pumps because their power is small. Yet these lines often turn on a single motor and have no standby. When the ash conveyor under the boiler stops, slag builds up and unit load may have to be reduced within a few hours. If the biomass screw stops, the fuel supply is cut.
These drives have one advantage. Their power ranges from a few kilowatts to a few tens of kilowatts, and most are four-pole motors flanged to a gearbox input. If frames and flanges can be standardised, two or three different screws can be covered by a single shelf motor. Remember that coal and ash dust settle on the cooling fins of these drives and that the spare motor will enter the same environment. The IP55 frame protection and class F winding in the standard equipment provide a sufficient starting point for this dusty environment.
Why is a spare for boiler fan and cooling tower motors slow to find?
The induced draft fan (ID) and forced draft fan (FD) carry the largest motors of the auxiliary systems. When one of these motors burns out, rewinding takes a long time, and finding a motor of the same size is not easy either. If the fans are arranged 2×50%, the unit stays up at half load, but if this lasts for months the plant pays with the energy it cannot sell. That is why boiler fans are the item where a shelf spare deserves the most discussion.
The picture is different for cooling tower fans: ratings are smaller, numbers are larger and the motors are often identical. Stocking spares gets easier. In a six- or eight-cell tower, a single motor on the shelf prevents a cell from staying out of service for months in summer. Because the tower environment is constantly humid, the insulation resistance of a motor taken from the store must be measured before it is fitted. You can find ratings suitable for boiler and tower fans on the fan and extractor motors page.

Shrinking the shelf by reducing nameplate variety
Over the years plants fill up with motors brought in by different contractors; the motors of two pumps doing the same job may have different frames and different connections. Keeping a separate spare for each makes the store grow. The shelf keeps getting longer. Gathering motors into the same power and frame during renewal or outages markedly reduces the number of spares.
When standardising, the IEC frame number is checked first; then shaft dimensions, the fixing holes in the feet, the flange and the electrical values on the nameplate are placed side by side to confirm the fit.
Depending on the frame, the motor can be supplied foot-mounted (B3), flange-mounted (B5, B14), carrying both foot and flange (B34, B35) or for vertical operation (V1, V3, V5, V6, V15); the flange size is settled when the order is placed. Dimensions by frame are on the technical drawings page.
Pay attention to voltage as well: in our catalogue, models up to 3 kW are wound for 230/400 V and those from 4 kW upwards for 400/690 V. In a plant whose auxiliary busbar is 690 V, the delta-star connection of the spare motor must be chosen for that voltage. You can sort suitable candidates among the cast iron models in our shop by kilowatts and number of poles.