In the auxiliary systems of a power plant, the switch to IE3 and IE4 electric motors is made by starting with the drives that run the longest and at the highest load, and by tying each replacement to a planned overhaul outage. On motors that run all year, such as cooling water pumps, boiler fans and cooling tower fans, the efficiency class difference feeds directly into auxiliary consumption; on auxiliary drives that start a few times a year, the same investment pays back far more slowly. Below we cover how to order the switch list in thermal, cogeneration and biomass plants, which technical points to check at replacement, and example models.
What does the efficiency gap between IE3 and IE4 turn into on an auxiliary drive?
IE classes are minimum efficiency steps defined in the IEC 60034-30-1 standard for the same power and number of poles. An IE4 motor produces the same shaft power with somewhat lower losses than IE3; the difference looks small in percentage terms, but in a power plant this loss is part of the auxiliary consumption deducted from every hour and every megawatt-hour sold. Waste heat is also lower. The winding runs cooler.
Three variables decide the size of the return: motor power, annual running hours and average load ratio. With a hypothetical example, if a 110 kW cooling water pump runs 8000 hours a year, even a single point of efficiency difference corresponds to several thousand kilowatt-hours a year. On a fire standby pump of the same power running 300 hours a year, the gain almost disappears. Do the calculation with the plant's own auxiliary energy price. What is given here is a general information framework, and exact figures must be verified with nameplate values and measurement.
How is the switch order for auxiliary drives set by annual hours and load ratio?
The order runs from the drive with the highest annual running hours and load ratio down to the lowest; fire and standby pumps stay at the end of the list.
| Auxiliary system | Typical operation | Switch priority | Note |
|---|---|---|---|
| Main cooling water and condenser pumps | Continuous while the unit runs | High | Large power, long hours; address at the first overhaul |
| Forced and induced draught fans (FD/ID) | Continuous, load follows boiler load | High | Damper and speed control are reviewed first |
| Cooling tower fans | Depends on season and outdoor air | Medium-high | Many fans; group switch with a single motor type possible |
| Condensate and intermediate circuit pumps | Continuous | Medium | Alternating replacement on parallel units |
| Coal, biomass and ash conveyors | Shift-based, intermittent | Medium-low | Idle running times are reduced first |
| Fire, emergency lubrication and standby pumps | Testing and emergencies | Low | Replacement at failure or end of life is enough |
Why are cooling water pumps at the top of the list?
The pumps carrying the flow through the condenser are the largest and most continuous load among the auxiliary drives of a water-cooled plant. They do not stop while the unit is online. They usually run at a load close to the design point; this is where an efficiency class upgrade pays back fastest.
For medium-power cooling water and auxiliary cooling pumps fed at low voltage, the 4-pole 110 kW cast iron frame 315S-4 can be shown as an example; its rated speed is 1488 rpm and its voltage 400/690 V. On smaller closed-circuit cooling pumps the 55 kW 250M-4 (1485 rpm) can be considered; you can compare the different pole options of these two powers in the electric motor store. For options on the pump side, see the pump electric motors page.
Large medium-voltage drives such as the main feedwater pumps fall outside HEM Motor's series for sale; the series consists of low-voltage models in the 0.25–355 kW range.
Why is the control method addressed before the efficiency class on boiler fans?
If fan flow is throttled by a damper when the plant runs at part load, the return from upgrading the motor's efficiency class is small next to the energy wasted in the damper. Forced and induced draught fans follow the boiler load. The order on the fan side is therefore: first the control method (damper, inlet vanes or speed control) is addressed, then motor power is verified against the measured load, and the efficiency class is chosen last.
HEM Motor's three-phase series are suitable for being driven by a frequency converter. If the induced draught fan is to turn slowly but with high torque for long periods at low load at night, an independent cooling fan may be needed; if the cable distance between the drive panel and the fan motor is long, a dv/dt or sine filter is considered. You need to pass these conditions on with your order.
The hot flue gas carried by the induced draught fan reaches the fan, not the motor; however, the ambient temperature around the fan is taken into account separately in motor selection. For other models for fan drives, see the fan and extractor motors page.