The most reliable way to monitor winding temperature in an IE4 efficiency-class electric motor is to connect the PTC thermistor embedded in the winding to a thermistor relay or to the thermistor input of the drive. A thermal overload relay estimates temperature from current, while a thermistor senses heat directly in the winding, so it catches overheating earlier when cooling fails or the motor turns at low speed.
Why is winding temperature a more accurate protection criterion than current measurement?
What ages insulation is not the current itself but the temperature the winding reaches, and the same current can produce very different winding temperatures depending on cooling. A thermal overload relay or motor protection circuit breaker (MPCB) calculates the heating effect of current over time using a model. If the fan cowl is clogged with dust, the air in a compressor room has warmed up, or the motor runs slowly on a frequency converter, that model no longer reflects reality. A thermistor measures the winding itself.
As the efficiency class rises, losses fall and at the same load the winding usually runs cooler.
That extra margin is reassuring but it does not make monitoring unnecessary: because losses are low, current reacts less to temperature changes, and a cooling fault may hardly show in the current reading at all. The rule of thumb that every lasting 10 °C rise roughly halves insulation life is a useful guide here (general information; confirm with the motor manufacturer's data). We explain which protective device responds to which fault in our electric motor protection guide.
What is the difference between a PTC thermistor, a PT100 and a bimetal contact?
A PTC thermistor is a trip element whose resistance rises sharply at a set threshold, a PT100 is a resistor that measures temperature continuously, and a bimetal contact is a switch that opens mechanically at its threshold. The choice depends on whether you only want a trip or also want to follow the trend.
| Sensor | Information it gives | Device it connects to | Where it fits |
|---|---|---|---|
| PTC thermistor | Threshold exceeded or not | Thermistor relay or the drive's PTC input | Trip protection on fan, pump and conveyor drives |
| PT100 | Continuous temperature value | Temperature transmitter, PLC analogue input or monitoring relay | Large motors where separate warning and trip thresholds and data logging are wanted |
| Bimetal contact | Contact open or closed | Wired in series with the control circuit | Simple control panels where no separate relay can be fitted |
The response temperature of a PTC is chosen according to the motor's insulation class and is stated in the motor documents; do not interpret trip records without knowing this value. In the HEM Motor range, PTC and PT100 winding sensors are order options. Please confirm at the time of ordering which one your motor has and how its leads are marked in the terminal box.
We have collected the general features of motors in this class on our IE4 Super Premium Efficiency Electric Motors page; the efficiency class in which a listed model is supplied is confirmed with the order.
How is winding temperature calculated with the resistance method?
On a motor without a thermistor, the average winding temperature is found by comparing cold and hot winding resistance. The general formula used for copper windings is:
θ2 = (R2 / R1) × (235 + θ1) − 235
R1 is the cold winding resistance, θ1 the winding temperature at that moment (equal to ambient if the motor has stood for a long time), R2 the resistance measured right after the motor has warmed up under load, and θ2 the average winding temperature. The constant 235 applies to copper; a different constant is used for aluminium windings (general information; confirm with the instructions of the instrument and motor manufacturer).
Hypothetical example: the motor has stood overnight, the winding is at 20 °C and the resistance between two leads reads 0.80 Ω. After running under load for a few hours and being stopped, the same leads read 1.06 Ω. 1.06 / 0.80 = 1.325; 1.325 × 255 ≈ 337.9 and 337.9 − 235 ≈ 102.9 °C.
With an ambient of 25 °C, the winding rise above ambient is about 78 K.
Take the reading as quickly as possible after stopping the motor and use a four-wire micro-ohmmeter that can read low resistances accurately; as the winding cools during measurement, the result comes out low. Compare the value you find with the insulation class and the manufacturer's temperature rise information. This method gives the average and does not show the hottest spot in the winding.
How is the thermistor circuit checked before commissioning?
The thermistor circuit is checked before power is applied by measuring its resistance with a low-voltage multimeter and by testing the relay trip. The sequence used on site is:
- In the terminal box, separate the thermistor leads from the power leads; if the marking is unclear, check the motor documents and never connect by guesswork.
- Read the resistance between the leads with a multimeter that uses a low measuring voltage. On a cold motor the value is low, usually in the order of a few hundred ohms; an open circuit or a near-zero reading points to a cable or sensor fault.
- When running an insulation test with a megger, short the thermistor leads together and earth them; applying a high test voltage to the thermistor can damage the sensor.
- Route the thermistor cable separately from the power cable, using a screened cable with the screen earthed at one point.
- After connecting the relay, disconnect the thermistor line once; check that the relay stops the motor and does not allow a restart until it is reset by hand.