Before switching to an electric motor in the IE4 efficiency class, you need to measure, for every motor you plan to replace, at what power, for how many hours and how often it runs over at least one full production week, and turn the result into a load-duration table. The return on higher efficiency comes from the loss difference multiplied by operating hours; without a load profile, any switch-over calculation stays a guess.
Why does the load profile come before motor selection?
Because the loss difference between two motors is not a fixed number. It grows or shrinks with the load point at which the motor runs. The efficiency on the nameplate belongs to rated load. An extract fan turning at half load all day and a compressor delivering at full load over three shifts may carry the same nameplate values, yet they get very different results from moving to a higher-efficiency motor.
The profile also answers a second question: is the motor the right size? If the measurement shows that the existing motor does not use even half of its power, the power step is reconsidered first. Replacing an oversized motor with a more efficient motor of the same power leaves the real problem (excess power) where it was.
Which measurements should be recorded, and for how long?
The most reliable data is the active power (kW) recorded by a three-phase power analyser connected to the motor supply over at least one full production week. A single spot reading with a clamp meter is not a profile. Morning start-up, the lunch break and weekend standby only show up in a long recording.
- Connect the analyser as close to the motor terminals as possible, and on motors driven by a frequency converter, on the converter's output side. Values on the converter input describe the converter, not the motor.
- Record the three phase voltages, the three phase currents, active power and cosφ. A logging interval of one to five minutes is enough for most processes; shorten it on machines with frequent start-stop cycles.
- Note the production records for the same period (shift plan, product changes, maintenance stops). These notes tell you whether a dip in the power curve is a stoppage or a light product.
- Count the number of starts separately. On a motor that starts several times an hour, the starting current affects both heating and the energy table.
- Add photos of the existing motor's nameplate, shaft end and feet to the file; the mounting compatibility of the new motor will be checked from them.
In plants that run seasonally (cold stores, irrigation, drying), one week is not enough. Taking one week from the busy period and one from the quiet period makes the annual table far more realistic.
We have collected the general features of motors in this class on our IE4 Super Premium Efficiency Electric Motors page; the efficiency class in which a listed model is supplied is confirmed with the order.
How is a load-duration table built from the records?
You divide each recorded power value by the motor's rated power to convert it to a load ratio, split these ratios into ten-point bands and add up the time spent in each band. The resulting table shows how many hours a year the motor spends at which load.
Two formulas are enough for the calculation. Load ratio: β = Pmeasured,shaft / Prated. Shaft power is the electrical power read by the analyser multiplied by the efficiency at that load. If part-load efficiency is unknown, the nameplate value is used as a rough estimate. Energy for the period is found with E = Σ Pi × ti, that is, the average power of each band is multiplied by the hours in that band and summed.
When scaling the weekly table up to a year, use the actual number of operating weeks as the multiplier. An annual table that does not deduct holidays, maintenance and order gaps inflates the result.
How is the annual energy difference calculated from the loss difference?
In each load band, the difference between the losses of the existing motor and those of the candidate motor is multiplied by the hours in that band, and the bands are summed: ΔE = Σ (Ploss,old,i − Ploss,new,i) × ti. Loss power is found for each motor with Pshaft × (1/η − 1), using that motor's own part-load efficiency.
Hypothetical example: a 15 kW cooling water pump runs 4,200 hours a year at roughly three-quarter load and 1,800 hours at half load. Suppose the loss difference calculated from catalogue data comes out at 0.35 kW at three-quarter load and 0.25 kW at half load. The annual difference is 0.35 × 4,200 + 0.25 × 1,800 = 1,470 + 450 = 1,920 kWh. You work out the payback period yourself by multiplying this figure by the plant's own unit energy cost and dividing the motor price difference by the result.
The loss values in the example only illustrate the method; a real calculation must use the manufacturer's data for both motors (general information; confirm with the machine manufacturer).