When choosing an IE4 electric motor, a constant load is judged at a single operating point, while a variable load is judged across the whole load profile. For a constant load the catalogue efficiency at that point is enough; for a variable load the efficiency at each load step is weighted by the hours spent at that step and annual energy is calculated from this weighted sum. Even if two drives have the same plate power, the right comparison method differs when one always runs at full load and the other spends half the day at half load.
What is the difference between constant and variable load?
Under constant load the motor delivers almost the same torque and speed all day. A cooling tower fan, a constant-flow process pump or a continuously loaded belt conveyor are examples. The current log looks like a flat line.
Under variable load, torque, speed or both change hour by hour. An air compressor runs in loaded-unloaded cycles, an air handling unit fan adjusts flow with the season, a crusher strains according to feed. The current log looks jagged, stepped or wavy.
The reason for the distinction is simple: motor efficiency changes with load. On most induction motors the efficiency curve is flat roughly between 75% and 100% load and drops noticeably below 50%.
How is the comparison made under constant load?
Actual shaft power is measured once and the efficiencies of the two motors at this point are read from the catalogue. If load is around 75% of plate power the 75% column is used, if close to full load the 100% column. The annual energy difference is found as follows:
ΔE = Pshaft × t × (1/η1 − 1/η2)
Here t is the annual running hours (general information; confirm efficiencies from the catalogue page of the model you choose). Constant load is the easy case. One measurement, one multiplication.
How is weighted efficiency calculated under variable load?
First the load profile is drawn up. An energy analyser or panel current log gives at least a week of data; this data is split into a few steps. For a fan, for example, a table like this might result:
| Load step | Share of annual hours | Catalogue efficiency to use |
|---|---|---|
| Close to full load (90–100%) | 20% | 100% load column |
| Medium load (65–85%) | 50% | 75% load column |
| Light load (40–60%) | 30% | 50% load column |
The numbers are hypothetical and only show the method. In each row shaft power is divided by that row's efficiency to get the supply side; these are multiplied by the hour shares and added up. The same calculation is done separately for the two motors and the annual kWh difference emerges.
The row that moves the result most is the light load step. The part-load efficiency of higher efficiency class motors also usually follows a flatter curve; the difference most often opens up here. Exact values are read from the model catalogue.

How does variable speed operation change the calculation?
On fans and pumps whose flow is set with a frequency converter, load falls with speed as well as with torque. On a centrifugal machine shaft power drops roughly with the cube of speed; at 80% speed power falls to about half. The motor now runs both slower and lighter.
With converter operation, drive losses enter the calculation too and motor efficiency differs at every speed-torque point. If the manufacturer can give separate data for these points, those are used. Without data the calculation remains a rough estimate and the result should be read as a range.