The loss difference between an IE3 and an IE4 electric motor is the difference in power the two motors draw from the grid for the same shaft output, and it is calculated separately for each motor with Ploss = Pshaft / η − Pshaft. The difference becomes meaningful in kilowatt hours, once it is multiplied by the motor's real load and annual running hours; it is small on a motor that rarely runs and clear on one that runs continuously.
Why is the loss difference read in kilowatts rather than efficiency percentage?
The percentage-point gap between efficiency classes looks small, but because the power a motor turns into heat depends on the inverse of efficiency, losses change far more visibly. A decision needs kilowatts and kilowatt hours, not percentages.
As an example, take a drive in a pumping station in the 15 kW, 4-pole class running at about 13 kW load. The maintenance manager wants to know what moving to a higher class would change. The answer comes from looking at how much heat the two motors produce at the same shaft power; that heat is energy paid for at the meter that never reaches the shaft. Its sources fall under five headings: resistive heat in the stator winding, heat in the rotor bars, hysteresis and eddy heat in the lamination stack, the mechanical share of bearings and fan, and stray losses not covered by these. Higher efficiency classes shrink some of these items by design: more copper and steel, thin low-loss laminations, an optimised fan and slot geometry (general information; confirm with the motor manufacturer's technical data).
Which formula and which data are used for the loss calculation?
For each motor, loss power is found with Ploss = Pshaft × (1/η − 1); the difference between the two motors' losses gives the extra power drawn from the grid at the same shaft output. For the annual energy difference, this value is multiplied by running hours.
The inputs to the calculation are gathered from the field and from catalogues:
- real shaft power: not the nameplate rating, but the value derived from measured current and voltage or from process data;
- efficiency at that load: the part-load efficiency of both motors, from the manufacturer's catalogue;
- annual running hours: from the shift plan or an hour meter;
- unit price per kilowatt hour: from the site's own bill.
The last item is the site's own figure; accounting works out the monetary value with its own tariff. All power steps and speed options can be compared on the store page.
Hypothetical example: how much do two motors differ at the same load?
The table below is entirely hypothetical; the efficiency values were chosen to show the method and are not taken from any standard table or specific model.
| Item | Motor A (lower efficiency) | Motor B (higher efficiency) |
|---|---|---|
| Shaft power (measured) | 13 kW | 13 kW |
| Efficiency at this load (hypothetical) | 0.920 | 0.940 |
| Power drawn from grid | 13 / 0.920 ≈ 14.13 kW | 13 / 0.940 ≈ 13.83 kW |
| Loss power | ≈ 1.13 kW | ≈ 0.83 kW |
| Hourly difference (A − B) | ≈ 0.30 kW | ≈ 0.30 kW |
Assuming 6000 running hours a year, the hypothetical difference comes to 0.30 × 6000 ≈ 1800 kWh. Its monetary value is calculated as 1800 kWh × the site's own unit price. Had the same motor run 1500 hours a year, the difference would drop to a quarter.
What really decides the value of a class change is how many hours a year the motor turns.
How do part load and a drive change the loss difference?
The loss difference should be calculated at the load point where the motor actually runs. Most pump and fan motors in the field turn at between half and three quarters of nameplate power, and in this region the efficiency curve behaves differently from one motor to another.
At part load, iron and friction losses stay almost constant while copper losses fall with load. On a lightly loaded machine, the design with lower iron loss comes out ahead.
When a frequency inverter enters the picture, things change again. The drive's own loss and the harmonics in its output voltage generate extra heat in the motor; these losses must be included for both motors. Our three-phase series are suitable for speed control with a frequency inverter; for long periods at low speed with full torque an external fan may be needed; if the drive-to-motor cable is long, a dv/dt or sine filter is considered; these conditions are stated with the order.