Loss Difference Between an IE3 Electric Motor and an IE4 Electric Motor

Loss Difference Between an IE3 Electric Motor and an IE4 Electric Motor

The loss difference between an IE3 and an IE4 electric motor is the difference in power the two motors draw from the grid for the same shaft output, and it is calculated separately for each motor with Ploss = Pshaft / η − Pshaft. The difference becomes meaningful in kilowatt hours, once it is multiplied by the motor's real load and annual running hours; it is small on a motor that rarely runs and clear on one that runs continuously.

Why is the loss difference read in kilowatts rather than efficiency percentage?

The percentage-point gap between efficiency classes looks small, but because the power a motor turns into heat depends on the inverse of efficiency, losses change far more visibly. A decision needs kilowatts and kilowatt hours, not percentages.

As an example, take a drive in a pumping station in the 15 kW, 4-pole class running at about 13 kW load. The maintenance manager wants to know what moving to a higher class would change. The answer comes from looking at how much heat the two motors produce at the same shaft power; that heat is energy paid for at the meter that never reaches the shaft. Its sources fall under five headings: resistive heat in the stator winding, heat in the rotor bars, hysteresis and eddy heat in the lamination stack, the mechanical share of bearings and fan, and stray losses not covered by these. Higher efficiency classes shrink some of these items by design: more copper and steel, thin low-loss laminations, an optimised fan and slot geometry (general information; confirm with the motor manufacturer's technical data).

Which formula and which data are used for the loss calculation?

For each motor, loss power is found with Ploss = Pshaft × (1/η − 1); the difference between the two motors' losses gives the extra power drawn from the grid at the same shaft output. For the annual energy difference, this value is multiplied by running hours.

The inputs to the calculation are gathered from the field and from catalogues:

  • real shaft power: not the nameplate rating, but the value derived from measured current and voltage or from process data;
  • efficiency at that load: the part-load efficiency of both motors, from the manufacturer's catalogue;
  • annual running hours: from the shift plan or an hour meter;
  • unit price per kilowatt hour: from the site's own bill.

The last item is the site's own figure; accounting works out the monetary value with its own tariff. All power steps and speed options can be compared on the store page.

Hypothetical example: how much do two motors differ at the same load?

The table below is entirely hypothetical; the efficiency values were chosen to show the method and are not taken from any standard table or specific model.

ItemMotor A (lower efficiency)Motor B (higher efficiency)
Shaft power (measured)13 kW13 kW
Efficiency at this load (hypothetical)0.9200.940
Power drawn from grid13 / 0.920 ≈ 14.13 kW13 / 0.940 ≈ 13.83 kW
Loss power≈ 1.13 kW≈ 0.83 kW
Hourly difference (A − B)≈ 0.30 kW≈ 0.30 kW

Assuming 6000 running hours a year, the hypothetical difference comes to 0.30 × 6000 ≈ 1800 kWh. Its monetary value is calculated as 1800 kWh × the site's own unit price. Had the same motor run 1500 hours a year, the difference would drop to a quarter.

What really decides the value of a class change is how many hours a year the motor turns.

How do part load and a drive change the loss difference?

The loss difference should be calculated at the load point where the motor actually runs. Most pump and fan motors in the field turn at between half and three quarters of nameplate power, and in this region the efficiency curve behaves differently from one motor to another.

At part load, iron and friction losses stay almost constant while copper losses fall with load. On a lightly loaded machine, the design with lower iron loss comes out ahead.

When a frequency inverter enters the picture, things change again. The drive's own loss and the harmonics in its output voltage generate extra heat in the motor; these losses must be included for both motors. Our three-phase series are suitable for speed control with a frequency inverter; for long periods at low speed with full torque an external fan may be needed; if the drive-to-motor cable is long, a dv/dt or sine filter is considered; these conditions are stated with the order.

Rear view of the fan cover of a three-phase electric motor
The fan and cooling path are part of friction and windage loss (representative image).

Prices and technical data are on the product pages; choose a model and order online.

How is the real load measured on site?

Real shaft power is found by measuring the current of all three phases, phase-to-phase voltage and power factor while the motor runs; the most practical way is to connect a three-phase power analyser to the motor supply. Without an analyser, current is read with a clamp meter and a rough estimate is made with the nameplate data.

Measure at a moment when the process runs as it typically does. A reading taken first thing in the morning, while a tank is filling or at a shift change, misleads. With varying load, a recording of several hours is taken and the average power worked out.

A common mistake is dividing current by rated current and calling it the load ratio. At light load, magnetising current makes up most of the total, so this ratio shows load higher than it is and inflates the loss difference too.

What else is checked when deciding on a replacement?

Besides the loss difference, mechanical and electrical fit are checked: frame number, shaft and flange dimensions, starting behaviour and speed. High-efficiency motors sometimes turn slightly faster at the same power; on centrifugal pumps and fans this small speed difference raises the liquid or air delivered, and therefore the load on the shaft, a little.

This last point must not be skipped. If the fan pushes a little more air because of the higher speed, the motor's measured power rises too and part of the loss gain disappears. If needed, the pulley ratio or drive setting is adjusted again.

For frame fit, the technical drawings and the catalogue are read together. For mounting, B3, B5, B14, B34, B35 and vertical V1/V3/V5/V6/V15 are offered depending on frame; flange size is confirmed with the order.

Which efficiency classes and power steps does HEM Motor offer?

HEM Motor offers its three-phase asynchronous series in IE3, IE4 and IE5 efficiency classes; which model is supplied in which class is confirmed with the order. For product groups by class, see the IE3 series, IE4 series and IE5 series pages.

Three steps from the 4-pole cast iron series close to the load level in the hypothetical example: 160M-4 (11 kW, 1465 rpm, 20.4 A at 400 V), 160L-4 (15 kW, 1465 rpm, 27.3 A) and 180L-4 (22 kW, 1470 rpm, 39.7 A). These models are 400/690 V, IP55, with class F insulation; the required efficiency class is stated with the order. The family's other frames and speeds are on the asynchronous electric motors page.

If you send the load value you measured, how many hours it runs and the plate of the old motor through our contact page, we will set the part-load efficiencies of the two classes side by side and work out the loss difference with you. Prices are kept up to date in the HEM Motor product list.

Frequently Asked Questions

Does an IE4 motor always use less energy than an IE3 motor?

At the same shaft power and load point, usually yes. However, efficiency curves may differ at part load and a speed difference can change pump or fan load, so the comparison should be made at the real load.

Which documents are needed to calculate the loss difference?

A catalogue page with part-load efficiency values for both motors, the measured shaft power and the annual running hours are enough. The unit price is taken from the site's own bill.

Does it make sense to switch a rarely used motor to a high-efficiency one?

If annual running hours are low, the energy value of the loss difference stays small as well. In that case replacement is usually considered at the time of a failure or a new investment.

Does reducing motor power also reduce losses?

A motor that is too big for its job always runs at light load, where both efficiency and cosφ fall. Stepping down to the power that matches the real load can be as effective as a class change; starting and peak loads must be checked separately.

HEM Motor Models Related to This Article

The cards show example models related to the topic. A suitable motor is not chosen by power alone: compare speed, voltage, mounting, shaft and connection dimensions on the product page; if unsure, send a photo of the existing motor’s nameplate on WhatsApp.

11 kW 1500 rpm Cast Iron Frame Electric Motor 160M-4

160M-4

11 kW · 1500 rpm

  • Cast iron frame · IEC 160M
  • 1465 rpm · IP55
  • Mounting: B3 foot; flange (B5/B14/B35) depending on frame, confirmed with the order

US$557.82 (€510.52)

View product
15 kW 1500 rpm Cast Iron Frame Electric Motor 160L-4

160L-4

15 kW · 1500 rpm

  • Cast iron frame · IEC 160L
  • 1465 rpm · IP55
  • Mounting: B3 foot; flange (B5/B14/B35) depending on frame, confirmed with the order

US$665.08 (€608.69)

View product
22 kW 1500 rpm Cast Iron Frame Electric Motor 180L-4

180L-4

22 kW · 1500 rpm

  • Cast iron frame · IEC 180L
  • 1470 rpm · IP55
  • Mounting: B3 foot; flange (B5/B14/B35) depending on frame, confirmed with the order

US$901.75 (€825.30)

View product

Similar Articles