Voltage and Starting Method Compatibility for an 18.5 kW Electric Motor

Voltage and Starting Method Compatibility for an 18.5 kW Electric Motor

18.5 kW (25 HP) is the transition zone between small motors, which many plants start direct-on-line without any trouble, and large motors, whose starting method requires serious planning. Connecting a motor of this rating directly to the supply may or may not cause problems, depending on the plant's transformer capacity and the condition of the line. A wrong connection, on the other hand, can burn the motor at its first start. This article explains how to match an 18.5 kW motor's nameplate voltage to the supply and which questions to ask when choosing between star-delta, direct-on-line, a soft starter or a frequency inverter.

Three-phase electric motor with its terminal box visible
The connection type is set by the links in the terminal box (representative image).

Electrical values of the 18.5 kW models

At HEM Motor, 18.5 kW is offered with a cast iron frame at three speeds. All three models have a nameplate voltage of 400/690 V (Δ/Y), 50 Hz; the protection class is IP55 and the insulation class is F.

Model codeSynchronous / rated speedIEC frameRated current (400 V)Rated torqueProduct page
200L1-61,000 / 980 rpm200L35.9 A180.3 Nm200L1-6 cast iron
180M-41,500 / 1,470 rpm180M33.5 A120.2 Nm180M-4 cast iron
160L-23,000 / 2,940 rpm160L32.5 A60.1 Nm160L-2 cast iron

The current in the table is the rated current drawn at 400 V and full load. The current drawn at the moment of starting is several times higher, and that is the value that really determines the starting method.

What does a 400/690 V nameplate tell you?

The two voltages on the nameplate show that the motor windings can be connected to suit two different supplies. Each winding phase is designed for 400 V:

  • Delta (Δ) on a 400 V supply: each phase winding is connected directly between two lines and sees 400 V. On the standard industrial supply in Türkiye and Europe, an 18.5 kW motor runs with this connection.
  • Star (Y) on a 690 V supply: each phase winding sees the line voltage divided by √3, which is again about 400 V. This connection is for plants with 690 V distribution.

A common mistake is to leave the motor connected in star on a 400 V supply. In that case each winding sees about 230 V and the motor torque drops noticeably; under load the motor loses speed, its current rises and it overheats. Conversely, connecting a motor with a 230/400 V nameplate in delta on a 400 V supply applies overvoltage to the windings and burns the motor in a short time. So when replacing a motor, always look at the old motor's nameplate voltage and how the terminal links were fitted.

Older nameplates may show values such as 380/660 V. These come from earlier nominal supply values and follow the same connection logic as today's 400/690 V motors; even so, note the voltage actually measured on the supply when replacing.

Starting methods and decision questions at 18.5 kW

Direct-on-line starting

The motor is connected straight to the supply by a contactor. It is the simplest and cheapest arrangement; the motor delivers its full torque at start. The drawback is the high current drawn at start. If the transformer capacity is sufficient, the line is short and there are no sensitive loads fed from the same panel, direct-on-line starting at 18.5 kW is applied without problems in many plants. Whether it is possible is decided by the person who designed the plant's electrical installation and by the rules of the distribution company.

Star-delta starting

The motor first starts in star and switches to delta once it reaches a certain speed. Because each winding sees a lower voltage in star, the starting current and starting torque drop to about one third. This method requires two conditions:

  • The motor's running connection at the supply voltage must be delta. The 18.5 kW models with a 400/690 V nameplate are suitable because they run in delta on a 400 V supply. On a 690 V supply they already run in star, so they are not suitable for star-delta starting.
  • The links in the terminal box must be removed and all six ends run separately to the panel. That means a six-core cable or two separate cables.

The weak point of star-delta is torque. Because the starting torque drops to one third, it works well only on machines that start with a light load (a fan or pump starting unloaded, a compressor, a crusher starting empty). On machines that start under load, such as a loaded belt, a full screw conveyor or a full mixer, the motor may not reach enough speed in star; a large current surge occurs at the changeover to delta and the purpose of the method is lost.

Soft starter

It limits current by raising the voltage steplessly during start. It reduces mechanical shock and protects transmission elements such as belts and couplings. However, when the voltage is reduced the torque also falls; on its own it is not a solution for heavy-load starting. The motor's terminal connection stays as its normal running connection (delta at 400 V).

Frequency inverter (drive)

This method can both limit current and provide high torque at low speed; it also allows speed adjustment. Our three-phase series are suitable for speed control with a frequency inverter; for long periods of full-torque operation at low speed, an external fan may be needed, and if the cable between the drive and the motor is long, a dv/dt or sine filter is considered; these conditions are stated with the order. For details, see the question on use with a frequency inverter.

Prices and technical data are on the product pages; choose a model and order online.

Decision table: which method and when?

SituationMethod to considerNote
Strong transformer, short line, light startDirect-on-lineStarting current and cable cross-section must be confirmed by the installation designer
400 V supply, fan or pump starting unloadedStar-deltaSix ends run to the panel; changeover time must be set correctly
No shock wanted on belt, coupling or pipelineSoft starterStarting torque may not be enough under heavy load
Start under load or speed adjustment neededFrequency inverterLow speed, cable length and filter are stated with the order
Plant with 690 V distributionDirect-on-line, soft starter or driveA 400/690 V motor does not start in star-delta on this supply

This table is a starting framework. The starting method is determined by the machine's starting load, starting frequency, supply condition and protection arrangement together; the final decision belongs to the plant's electrical engineer. For choosing protective devices, you can read our article on thermal relay and fuse selection.

Example: deciding to move from star-delta to a drive

The following sequence is a hypothetical example. Suppose a screw conveyor at a plant is driven by a 1,500 rpm, 18.5 kW motor through a star-delta panel and struggles at the morning start when it was left full at the end of the shift.

  • Read the symptom: the motor turns slowly in star and the thermal relay trips at the changeover to delta. This is a sign that the starting torque does not meet the load; the motor's power may not be insufficient.
  • Check the motor: the existing motor has a 400/690 V nameplate and runs in delta at 400 V. The model to consider as a replacement is the 180M-4 (18.5 kW, 4 poles, 1,470 rpm, IEC 180M, 400/690 V).
  • Rethink the method: if emptying the screw conveyor every shift is not possible, a frequency inverter is considered instead of star-delta. In that case, how long it will run at low speed and the cable length are stated with the order.
  • Do not oversize the power: trying to solve a star-delta problem with a bigger motor also increases the starting current. Fix the starting method first.

At the same plant, the 160L-2 (18.5 kW, 2 poles, 2,940 rpm, IEC 160L) could be considered for a centrifugal fan that starts unloaded, or the 200L1-6 (18.5 kW, 6 poles, 980 rpm, IEC 200L) for a slow-running drive; the method is chosen separately for each machine.

Voltage and starting information for your order

  • Supply voltage and frequency (e.g. 400 V, 50 Hz) and whether the plant has 690 V distribution
  • Planned starting method: direct-on-line, star-delta, soft starter or frequency inverter
  • Whether the machine is empty or loaded at start, and how many times a day it starts
  • If a drive is used, the speed range and the drive-to-motor cable length
  • For a replacement, a photo of the old motor's nameplate and of the terminal connection

You can review the 18.5 kW models and current prices on the buy electric motors page. If you are unsure about your current motor's nameplate voltage or connection, send us a photo of the nameplate; for other questions, reach us through our contact page.

HEM Motor Models Related to This Article

The cards show example models related to the topic. A suitable motor is not chosen by power alone: compare speed, voltage, mounting, shaft and connection dimensions on the product page; if unsure, send a photo of the existing motor’s nameplate on WhatsApp.

18.5 kW 1500 rpm Cast Iron Frame Electric Motor 180M-4

180M-4

18.5 kW · 1500 rpm

  • Cast iron frame · IEC 180M
  • 1470 rpm · IP55
  • Mounting: B3 foot; flange (B5/B14/B35) depending on frame — confirmed with the order

US$867.92 (€774.56)

View product
18.5 kW 3000 rpm Cast Iron Frame Electric Motor 160L-2

160L-2

18.5 kW · 3000 rpm

  • Cast iron frame · IEC 160L
  • 2940 rpm · IP55
  • Mounting: B3 foot; flange (B5/B14/B35) depending on frame — confirmed with the order

US$709.45 (€633.13)

View product
18.5 kW 1000 rpm Cast Iron Frame Electric Motor 200L1-6

200L1-6

18.5 kW · 1000 rpm

  • Cast iron frame · IEC 200L
  • 980 rpm · IP55
  • Mounting: B3 foot; flange (B5/B14/B35) depending on frame — confirmed with the order

US$1,126.64 (€1,005.45)

View product

Similar Articles