For a filter press feed pump, the electric motor is selected for the heaviest moment of the cycle; on a press with a centrifugal pump this moment is usually the start of filling, because with the chambers empty flow is highest and back pressure lowest. As the cycle progresses the cake forms, pressure rises, flow falls and power demand decreases; motor power is therefore checked against both peak power and the equivalent power that represents heating over the whole cycle.
How does the pump load change during a filter press cycle?
A filter press cycle roughly consists of three phases. In the filling phase the chambers between the plates fill with slurry; resistance is low and the pump moves to the right end of its curve, to high flow. In the compaction phase the cake thickens on the cloth, back pressure rises and flow decreases steadily. In the final phase the pump runs at high pressure with very little flow, almost as if working against a closed valve.
In a centrifugal pump, power rises together with flow. That is why the highest power is seen at the start of the cycle, when pressure is lowest. This is the counter-intuitive point: operators usually think the pump struggles when pressure is high, whereas motor current peaks at the start of filling.
With piston or membrane pumps the picture is different. In these pumps flow is fixed by speed, torque demand rises with pressure and motor load climbs towards the end of the cycle. Knowing the pump type and the manufacturer's power–pressure curve before selecting the motor is therefore essential.
How is the cycle load recorded on site?
An energy analyser connected to the motor input records active power and current at one-second intervals over at least two full cycles. At the same time the gauge reading on the pump discharge line and, if possible, the filtrate flow are noted. In the recording, the start of filling, the pressure rise and the end of the cycle must be clearly distinguishable.
As slurry density changes, the curve changes too. If the plant works with different solids contents, separate recordings are taken for the densest and the thinnest slurry. With thin slurry filling lasts longer and peak power stays longer; this directly affects the heating calculation. Pay attention to one detail when recording. If the air vent valve at the pump outlet or a bypass line has been left open, the measured power does not represent the real cycle. Before measuring, the line layout is set as in normal operation.
How are equivalent power and peak power calculated?
Under variable load, the motor's heating is approximately determined by the root mean square power: Peq = √(Σ Pi² × ti / Σ ti). This method is meaningful when the motor's thermal time constant is longer than the cycle phases (general information; confirm with the machine manufacturer).
Hypothetical example: the recording shows a filling phase of 5 minutes at an average of 9 kW, a compaction phase of 20 minutes at an average of 6 kW and a final phase of 15 minutes at an average of 3.5 kW. Calculation: 9² × 5 = 405; 6² × 20 = 720; 3.5² × 15 = 183.75. Total 1,308.75; divided by 40 minutes gives 32.72; its square root is about 5.7 kW.
Equivalent power came out at 5.7 kW.
At first glance a 7.5 kW motor seems sufficient. But the 9 kW at the start of filling clearly exceeds the rated power of a 7.5 kW motor for five minutes. Whether the motor can cope with this short overload depends on the manufacturer's data, and the thermal relay may trip during this time as well.
Two routes then remain: choosing an 11 kW motor that covers peak power, or reducing peak power by limiting the filling flow.
The load of the feed pump motor is recorded with an analyser over the cycle (representative image).
Prices and technical data are on the product pages; choose a model and order online.
How does a frequency converter regulate this load?
On a feed pump the frequency converter does two jobs. At the start of filling it lowers speed and thereby limits flow and hence peak power; as the cycle progresses it increases speed according to the signal from the pressure sensor to reach the target pressure. The power curve flattens and the motor works in a narrower range.
Slowing down the filling is also beneficial for the cloth and the cake. With very fast filling, fine particles can embed themselves in the pores of the cloth and filtration resistance rises early. Target pressure and ramp times are set according to the press manufacturer's recommendation.
When a drive is used there are also a few conditions on the motor side. Because the shaft-mounted fan slows down with speed, long running at low speed with high torque may require a separate cooling fan; if the distance between panel and motor is large, fitting a dv/dt or sine filter at the cable end is discussed.
Option
Peak power
Motor power
Point to watch
Direct-on-line, no valve adjustment
High at the start of filling
Selected for peak power
Thermal setting checked against peak current
Direct-on-line, filling valve throttled
Medium
Approaches equivalent power
Valve loss consumes energy, depends on the operator
Frequency converter, pressure control
Can be limited
Can be selected for equivalent power
Cooling at low speed and cable filter
Which problems are seen on site in this application?
The most common complaint is the thermal relay tripping at the start of every cycle. Usually the motor has been undersized or the filling valve has been opened fully by the operator. The analyser recording shows which it is within a few cycles. The second problem concerns the pump gland and bearings. If at the end of the cycle the pump turns for a long time at very low flow, the fluid heats up, cavitation noise is heard and the gland wears quickly. This is a problem of the pump duty point, not of the motor; the minimum flow limit is obtained from the pump manufacturer.
The third is the muddy and humid environment. In the filter press area wash water splashes and the floor is constantly wet. The terminal box cover gasket and the sealing of cable entries should be checked at every maintenance.
Which example motors fit this calculation?
Three 2-pole cast iron models that can be considered according to the equivalent and peak power values of the hypothetical example are listed below. IP55 protection and class F insulation are common to all three; in the wet filter press area a cast iron frame is preferred. For other power steps, see the list in the HEM Motor shop.
132S1-2: 5.5 kW, 2930 rpm, 10.1 A at 400 V, rated torque 17.9 Nm. Close to equivalent power; worth considering only if peak power is tightly limited by a drive.
132S2-2: 7.5 kW, 2930 rpm, 13.7 A at 400 V, rated torque 24.4 Nm. The step that fits the example cycle when filling flow is limited with a frequency converter.
160M1-2: 11 kW, 2945 rpm, 19.6 A at 400 V, rated torque 35.7 Nm. For direct-on-line systems drawing 9 kW at the start of filling.
Other options for pump applications are gathered on the pump electric motors page.
If you share the pump type, a two-cycle power recording and the press manufacturer's target pressure via our contact page, we can calculate equivalent and peak power together and determine the right motor power. The current status of the models is on our sales page.
Frequently Asked Questions
Should I select the feed pump motor for the pressure at the end of the cycle?
With a centrifugal pump, no; the highest power is usually seen at the start of filling, at low pressure and high flow. With piston and membrane pumps, however, load rises with pressure, so the pump type must be clarified first.
Why does the thermal relay trip only at the start of filling?
At this moment the motor draws its highest current. If the motor is small or the filling valve is fully open, current exceeds the thermal setting; the analyser recording shows the cause.
Can peak power be reduced without a frequency converter?
It can be reduced by throttling the valve on the filling line, but this method creates energy loss and depends on the operator setting the valve correctly.
Does slurry density affect motor selection?
Yes. As density changes, cycle time and the power curve change; the decision should be made with a separate recording for the most demanding slurry.
HEM Motor Models Related to This Article
The cards show example models related to the topic. A suitable motor is not chosen by power alone: compare speed, voltage, mounting, shaft and connection dimensions on the product page; if unsure, send a photo of the existing motor’s nameplate on WhatsApp.
When choosing an electric motor for a dosing pump, the adjustment range is the flow band produced jointly by the stroke length setting and the motor speed. Mounting dimensions are ... More Details
When choosing an electric motor for a mono pump (progressive cavity pump with a helical rotor), the decisive factor is often not running power but the breakaway torque at the first... More Details
When choosing a motor for a peristaltic pump, the deciding value is not flow or pressure but the torque the rotor needs to squeeze the hose. The rotor turns slowly, so a gearbox al... More Details
When choosing an electric motor for a vegetable washing drum, two things are considered together: how well the motor will withstand splashing and wash water, and at what speed and ... More Details
The gap between an electric motor's fan cover and the wall behind it is the only inlet section through which cooling air reaches the fan; if this gap is smaller than the open area ... More Details
As the holes in an electric motor's fan cover clog, the cooling airflow drops and the winding temperature climbs not in proportion to the blocked area but along an increasingly ste... More Details
We use necessary and optional cookies to improve your experience, enhance content and analyse traffic. Under the GDPR, optional (analytics/marketing) cookies are only used with your explicit consent. Please choose your preference below.
Cookie Policy