Panel planning for an IE5 electric motor starts once it is clear whether the motor will run on a drive or directly from the grid: magnet-based synchronous designs usually depend on a frequency drive, and the panel is built around that drive's input protection, harmonic measures, cooling and motor cable. If a drive-free design has been chosen, the classic starting arrangement applies. Making this decision before ordering the motor saves drawing the panel twice.
Can an IE5 electric motor run without a drive?
Most IE5-level electric motors with a permanent magnet or reluctance rotor cannot run without a drive; a frequency drive is needed to reach synchronous speed and keep control. Designs that reach the IE5 level with a lower-loss induction build, however, can be connected directly to the grid.
This distinction changes the entire panel project. In a drive-fed arrangement, the contactor, thermal relay and star-delta group give way to the drive, its input protection and filters. In a drive-free arrangement, starting current, starting method and the motor protection relay are the main topics.
HEM Motor offers motors in the IE3, IE4 and IE5 efficiency classes.
For a given power and frame, which rotor design delivers the IE5 level and whether a drive is mandatory must be confirmed when ordering; start the panel drawing after that confirmation.
Which nameplate data are used when selecting a drive?
The drive is selected by the motor's rated current, rated voltage, motor type (induction or synchronous) and load character; looking only at the kW value is not enough. Two motors with the same kW can draw different currents, and a drive is limited by current.
- Rated current and connection (400 V delta or 690 V star): the drive's continuous output current must be above this.
- Motor type: for a permanent magnet synchronous motor, the drive must support that motor type and the motor parameters (such as inductance and back-EMF constant) must be entered.
- Load character: variable torque is selected for fans and pumps, constant torque for conveyors and mixers; for heavy starts, the drive's short-time overload capacity is checked.
- Speed range: if the motor will run for long periods at low speed with full torque, motor cooling is assessed separately.
With magnet motors, the drive runs a motor identification step at first commissioning. Because some drives can only partly perform this step with the load coupled, adding a time window in the commissioning plan when the motor can be turned unloaded makes the job easier (general knowledge; confirm with the drive manufacturer's instructions).
We have collected the general features of motors in this class on our IE5 Ultra Premium Efficiency Electric Motors page; the efficiency class in which a listed model is supplied is confirmed with the order.
Which protection and filter elements are planned on the panel's input side?
On the input side, a main switch or load-break switch, short-circuit protection and, where needed, an input reactor and EMC filter are planned to protect the drive and the grid. The ratings of these elements are set from the table in the drive manufacturer's manual. Figures for fuse or breaker ratings, cable cross-section and residual current device type are not given here; the project engineer calculates them from the drive input current, short-circuit power, cable length, installation method and ambient temperature. Knowing which information the calculation needs helps you collect the right data on site:
- Transformer rating and short-circuit current at the supply point (from the utility or the existing project).
- The drive's input current and the protection type recommended by the manufacturer.
- Cable route and length from the panel to the motor.
- Other drives fed from the same busbar and the state of the compensation panel.
Harmonics are a separate topic. In plants where several drives are fed from the same transformer, current harmonics can stress compensation capacitors; that is why an input reactor, a DC link choke or an active filter is assessed at the project stage. Check whether the compensation panel has harmonic-filtered (detuned) steps.
How should the motor cable and earthing be planned?
The cable from drive to motor is chosen as a shielded, symmetrical type, the shield is earthed at both ends with a 360-degree clamp, and the cable route is kept apart from control cables. These three measures reduce both bearing currents and the noise that spreads to nearby measurement lines. As the cable gets longer, voltage peaks at the motor terminals grow. Our three-phase series are suitable for speed control with a frequency converter; for long periods at low speed with full torque an external fan may be needed; if the drive–motor cable is long, a dv/dt or sine filter is considered; these conditions are stated when ordering.
An equipotential bond between the motor frame and the driven machine lowers the chance that drive-induced shaft voltages discharge through the bearing. If an insulated bearing or shaft grounding brush is required, state it in the order and get confirmation.