Why Does the Capacitor Connection Point Matter in Electric Motor Power Factor Correction?

Why Does the Capacitor Connection Point Matter in Electric Motor Power Factor Correction?

In electric motor power factor correction, where the capacitor is connected decides the current the overload relay sees, the voltage left on the winding when the motor stops and the section of cable in which losses fall. A capacitor of the same kVAr rating gives quite different results when placed before or after the contactor, or on either side of the overload relay. Put it in the wrong place and protection drifts.

At which points can a capacitor be connected for individual compensation?

There are three basic points: the supply side of the contactor, between contactor and overload relay, and between overload relay and motor terminals. As a fourth option the capacitor is fed from a separate branch through its own contactor, interlocked with the motor contactor.

A capacitor connected on the supply side of the contactor stays in circuit even while the motor is stopped. The line then turns capacitive when it runs without load; reactive energy may build up in the reverse direction on the panel meter.

A capacitor connected after the contactor leaves the line at the very moment the motor is de-energised. This is the arrangement seen most on site. It needs no extra contactor, and the capacitor supplies reactive power only while the motor is turning.

Does connecting before or after the overload relay change its setting?

Yes, it does. If the capacitor is connected between overload relay and motor, the current passing through the relay is smaller than the motor's real current, because part of the reactive current is now supplied by the capacitor.

So if the relay is set to the plate current, it trips late when the motor is overloaded.

The right approach is to measure the current at the relay input with a clamp meter after compensation, with the motor at full load, and correct the setting to that reading. The measurement is taken on the three phases separately. If one phase clearly stands apart from the others, the first suspect is a capacitor cell that has lost capacitance. Capacitance loss over the years is normal in dry-type capacitors, and each phase lead is checked separately with a multimeter that measures capacitance (general information; confirm with the capacitor manufacturer's data).

If the capacitor is connected on the supply side of the overload relay, the relay sees the motor's real current and a setting based on plate current stays valid. Some panel builders prefer this arrangement for that reason.

Why can the capacitor be dangerous when the motor stops?

If motor and capacitor sit behind the same contactor, opening the contactor disconnects both from the supply but leaves them connected to each other. As long as the shaft keeps turning, the capacitor excites the winding and the motor generates voltage like a generator for a while; this is called self-excitation.

If the capacitor rating is chosen too large this voltage can rise above supply voltage. With high-inertia loads such as fans or flywheels the run-down lasts longer, so the risk increases.

The second hazard is restarting. If the contactor closes again while the motor is still turning and carrying residual voltage, the two voltages meet out of phase; welded contactor contacts and an impact torque on the shaft may follow. The split-second gap when jumping from star to delta repeats this picture.

In general practice the individual capacitor rating is kept below the reactive power the winding demands while the motor runs unloaded (general information; for the exact value consult the panel engineer and the capacitor manufacturer). No-load reactive power is found from the current and voltage measured with the motor turning without load.

What information is used to calculate the capacitor rating?

The basic formula is Qc = P × (tanφ1 − tanφ2). Here P is the measured active power. φ1 is the present power factor angle and φ2 the angle to be reached.

Take a hypothetical example: the analyser shows 12 kW active power and a cosφ of 0.80, with a target of 0.95. Since tanφ1 ≈ 0.75 and tanφ2 ≈ 0.33, Qc ≈ 12 × 0.42 ≈ 5.0 kVAr. This result is compared with the no-load reactive power; if it is larger, the step is reduced.

The data needed for the calculation fit in a short list:

  • Active power and cosφ measured under load (with a power analyser, over at least one full work cycle).
  • Current and voltage measured at no load.
  • How starting is done (direct from the supply, stepped, or through a drive).
  • The step structure and harmonic situation of the central compensation in the panel.

Capacitor cable and fuse are outside the scope of this article; the project or panel engineer selects them according to the capacitor's rated current and the cable's installation conditions.

Prices and technical data are on the product pages; choose a model and order online.

In which section does cable loss fall?

Reactive current falls only in the section between the capacitor and the supply. The closer the capacitor is to the motor terminals, the longer the length of cable that is relieved.

With central compensation the capacitor stays in the main panel. The feeder running from the panel out to the site goes on carrying reactive current. On a long borehole line or in a treatment plant spread across a site this difference is felt; on a motor next to the same panel it is insignificant.

This is easy to see on site. The clamp meter goes first on the panel outgoing feeder, then on the motor side of the point where the capacitor is connected; the difference is the reactive current the capacitor takes over on that line. The reading takes two minutes.

Cast iron three-phase electric motor
An individual capacitor is added to the motor supply once its position relative to contactor and overload relay has been chosen (representative image).

How is the connection point chosen for soft-started and drive-fed motors?

No capacitor is connected at the output of a frequency converter, that is between drive and motor. The drive's switching pulses load the capacitor with excess current, the drive trips and the capacitor heats up quickly. On drive-fed motors power factor is handled on the supply side of the drive.

With a soft starter the capacitor is switched in by a separate contactor after starting is complete and the bypass contactor has closed. A capacitor at the thyristor output can damage the starter.

With star-delta starting the capacitor is connected behind the line contactor, preferably with discharge resistors. To prevent an out-of-phase voltage reaching the winding at changeover, some panels switch the capacitor in only after the delta contactor has closed.

HEM Motor's three-phase series are suitable for speed control with a drive. If full torque is needed at low speed for long periods, a separately powered fan comes into question, and if the drive cable is long, a dv/dt or sine filter; these are written into the order.

Series information is on the asynchronous electric motors page and high-efficiency options on the IE4 class page. The current list of motors for which compensation is being newly installed is in the HEM Motor store.

Which motor steps are common in individual compensation?

An individual capacitor generally makes sense on motors that run for long periods at steady load and have a noticeable no-load reactive power. The plate values of the 4-pole models below give a starting point for the calculation:

ModelPowerRated speedPlate current (400 V)
160M-411 kW1465 rpm20.4 A
180M-418.5 kW1470 rpm33.5 A
225S-437 kW1485 rpm66.1 A

All three have cast iron frames and 400/690 V windings.

Plate current is not no-load current; to set the capacitor rating, a no-load measurement must be made after the motor is installed. If you send your panel diagram, starting method and motor plate through the contact page, we will settle together the capacitor connection point and the motor step and choose the right model from the sales list.

Frequently Asked Questions

How is the relay set if the capacitor is connected after the overload relay?

With compensation in circuit the motor is run at full load and the current through the relay is measured with a clamp meter. The setting is made to this measured value, not to plate current.

What happens if the capacitor rating is too large?

When the motor is stopped together with the contactor, self-excitation may occur and a voltage higher than the supply may appear on the winding. The line also turns capacitive when unloaded.

Can an individual capacitor be added to a drive-fed motor?

Not between drive and motor. The power factor requirement is assessed at the drive's supply input, with the solution recommended by the drive manufacturer.

Is an individual capacitor still needed if there is central compensation?

On motors with short lines it is usually not needed. On large, continuously running motors with long feeders an individual capacitor can be considered separately to reduce reactive current in the line.

HEM Motor Models Related to This Article

The cards show example models related to the topic. A suitable motor is not chosen by power alone: compare speed, voltage, mounting, shaft and connection dimensions on the product page; if unsure, send a photo of the existing motor’s nameplate on WhatsApp.

11 kW 1500 rpm Cast Iron Frame Electric Motor 160M-4

160M-4

11 kW · 1500 rpm

  • Cast iron frame · IEC 160M
  • 1465 rpm · IP55
  • Mounting: B3 foot; flange (B5/B14/B35) depending on frame, confirmed with the order

US$557.82 (€510.52)

View product
18.5 kW 1500 rpm Cast Iron Frame Electric Motor 180M-4

180M-4

18.5 kW · 1500 rpm

  • Cast iron frame · IEC 180M
  • 1470 rpm · IP55
  • Mounting: B3 foot; flange (B5/B14/B35) depending on frame, confirmed with the order