How Much Do Copper, Iron and Friction Losses Account for in an Electric Motor

How Much Do Copper, Iron and Friction Losses Account for in an Electric Motor

In an asynchronous electric motor, the part of the power drawn from the supply that does not reach the shaft falls into five items: the stator winding loss, the rotor bar loss, iron (core) loss, friction and windage loss, and additional load losses. In a medium-power, 4-pole motor at rated load the largest share usually belongs to the copper losses; stator and rotor together make up roughly half or a little more of the total loss, iron loss follows, and friction and additional losses remain in smaller slices.

This distribution is not fixed, however: it shifts markedly with motor power, number of poles and above all the load ratio (general information; confirm with the motor manufacturer's test data).

Where do the five loss items arise?

Stator copper loss is the part of the current flowing through the ohmic resistance of the winding that turns into heat, calculated as PCu1 = 3 × I² × Rphase. Because it grows with the square of current, it rises quickly as load increases. Resistance also rises as the winding heats up, so a hot motor has more loss than a cold one at the same current.

Rotor copper loss is released in the bars and end rings of the aluminium or copper rotor cage. It is hard to measure directly. It can, however, be calculated from slip: PCu2 = s × Pair gap. In other words, the larger the slip, the greater the share of power passing from stator to rotor that turns into heat in the rotor.

Iron loss arises in the stator and rotor laminations through hysteresis and eddy currents. If supply voltage and frequency are constant it changes little whatever the load; the motor carries a similar iron loss whether idle or at rated load. When voltage rises, magnetisation increases and iron loss grows noticeably.

Friction and windage loss is the power spent on bearing friction and on the fan and rotor moving the air. It is strongly linked to speed; since speed stays almost constant as load changes, in practice it behaves like a fixed loss.

Additional load losses stem from leakage flux and harmonics, increase with load and are the hardest item to measure directly.

Loss shares at full load: what does the number of poles change?

Of two motors of equal power, one being 2-pole and the other 6-pole changes the loss distribution. In the 2-pole motor speed is high, so the friction and windage share from fan and bearings grows; in the 6-pole motor more magnetic lamination and winding are needed for equal torque, so the iron and copper shares come to the fore. The table below summarises this tendency qualitatively; numerical shares vary with motor design.

Loss itemChange with loadTendency in a 2-pole motorTendency in a 6-pole motor
Stator copper lossRises with the square of currentMediumHigh
Rotor copper lossRises with slipMediumMedium-high
Iron lossNearly independent of loadMediumHigh
Friction and windageSpeed-dependent, practically constantHighLow
Additional load lossesRise with loadLow-mediumLow-medium

As motor power increases, the total loss ratio falls; as the efficiency class rises, the designer looks for improvement mostly in the copper and iron items.

The improvement between IE3, IE4 and IE5 comes largely from fitting more copper into the slots, from low-loss electrical steel and from designing the fan to create less air friction.

Separating the losses step by step in a hypothetical 15 kW motor

Consider a 4-pole machine with nameplate values of 15 kW and 1465 rpm and a rated-load efficiency assumed, as an example, to be 92%. These values are a calculation example. The efficiency of a real motor should be taken from its nameplate and test report.

  1. Power drawn from the supply: Pin = 15 / 0.92 ≈ 16.3 kW. Total loss ≈ 1.3 kW.
  2. Slip: s = (1500 − 1465) / 1500 ≈ 0.023.
  3. Taking an example value of 0.15 kW for friction and windage, the mechanical power developed by the rotor is ≈ 15.15 kW. Air-gap power ≈ 15.15 / (1 − 0.023) ≈ 15.5 kW.
  4. Rotor copper loss ≈ 0.023 × 15.5 ≈ 0.36 kW.
  5. Remainder ≈ 0.8 kW, shared between stator copper loss, iron loss and additional losses. These items can also be separated with a stator winding resistance measurement and a no-load test.

This simple flow also shows why slip is an important indicator. At the same power, a higher rated speed means a lower rotor loss.

The more precise version of the calculation is done with no-load and load tests, as in the general approach of IEC 60034-2-1.

Fan cover side and cooling fins of a three-phase electric motor
The fan and bearings determine friction and windage loss; this loss is linked to speed and barely changes with load (representative image).

Why does the distribution reverse at partial load?

Because iron and friction losses are nearly independent of load, their share of the total grows when the motor is lightly loaded. Copper losses, on the other hand, fall roughly with the square of load. At half load, stator and rotor copper losses drop to about a quarter of their full-load value. As a result, fixed items dominate the loss budget of a motor at half load.

The peak of the efficiency curve occurs around the load at which variable losses equal fixed losses; in many standard motors this point lies slightly below full load. At a quarter of load, fixed losses remain dominant and efficiency drops markedly. This is why oversized motors run at low efficiency.

Prices and technical data are on the product pages; choose a model and order online.

How is each loss item recognised in the field?

Field conditions that change the loss distribution can usually be caught by measurement. If supply voltage is clearly above rated, no-load current and iron loss increase; if it is below, current and copper loss rise for the same load. Voltage unbalance creates extra current and heating in the windings.

Excess or degraded bearing grease increases friction loss. Dust stuck on the fan cover also weakens cooling; the resistance of the warmer winding, and therefore the Joule loss, rises.

In motors fed by a frequency converter, harmonics in the output voltage increase additional losses. Prolonged full-torque operation at low speed, cable length and the need for a filter are stated with the order. In variable-flow water and air drives, speed adjustment also changes the motor's load and so directly affects the loss balance; power ranges for such drives are gathered under pump electric motors and fan and extractor motors.

Example models: three pole options at the same 15 kW

The calculation and table above showed how a different number of poles changes the loss distribution at the same power. The HEM Motor series includes three cast iron models with which you can make this comparison; all models are IP55 with class F insulation, and IE3, IE4 and IE5 efficiency classes are offered. The family list is on the asynchronous electric motors page, other powers in the electric motor shop.

  • 160M2-2: 15 kW, 2945 rpm, 400/690 V; at high speed the friction and windage share is more pronounced.
  • 160L-4: 15 kW, 1465 rpm, 400/690 V; same speed as in the hypothetical calculation.
  • 180L-6: 15 kW, 978 rpm, 400/690 V; despite equal power the frame grows, and the iron and copper items come to the fore.

Let us clarify your loss calculation with nameplate data

If you want to separate a motor's losses in your own plant, send the nameplate data, the current and voltage you measured and the load ratio through our contact page; we can assess together which item is decisive in choosing the efficiency class. Models in different efficiency classes can be browsed by frame and power in the HEM Motor product list.

Frequently Asked Questions

Why does a motor running at no load still heat up?

Although copper loss becomes small at no load, iron loss and friction and windage loss continue almost unchanged. These fixed losses heat the motor even at no load.

How is rotor copper loss estimated without measuring it?

It is calculated by measuring slip: rotor loss equals air-gap power multiplied by slip. The more accurate the speed measurement, the better the estimate.

Which loss increases if supply voltage is high?

Because magnetisation increases, iron loss and no-load current rise. If voltage is low, current and copper losses increase at the same load.

Which losses does a higher efficiency class reduce?

Mostly stator and rotor copper losses and iron loss are reduced; improvements in fan design also shrink the friction and windage share.

HEM Motor Models Related to This Article

The cards show example models related to the topic. A suitable motor is not chosen by power alone: compare speed, voltage, mounting, shaft and connection dimensions on the product page; if unsure, send a photo of the existing motor’s nameplate on WhatsApp.

15 kW 3000 rpm Cast Iron Frame Electric Motor 160M2-2

160M2-2

15 kW · 3000 rpm

  • Cast iron frame · IEC 160M
  • 2945 rpm · IP55
  • Mounting: B3 foot; flange (B5/B14/B35) depending on frame, confirmed with the order

US$559.25 (€511.84)

View product
15 kW 1500 rpm Cast Iron Frame Electric Motor 160L-4

160L-4

15 kW · 1500 rpm

  • Cast iron frame · IEC 160L
  • 1465 rpm · IP55
  • Mounting: B3 foot; flange (B5/B14/B35) depending on frame, confirmed with the order

US$665.08 (€608.69)

View product
15 kW 1000 rpm Cast Iron Frame Electric Motor 180L-6

180L-6

15 kW · 1000 rpm

  • Cast iron frame · IEC 180L
  • 978 rpm · IP55
  • Mounting: B3 foot; flange (B5/B14/B35) depending on frame, confirmed with the order

US$818.68 (€749.27)

View product

Similar Articles