In an asynchronous electric motor, the part of the power drawn from the supply that does not reach the shaft falls into five items: the stator winding loss, the rotor bar loss, iron (core) loss, friction and windage loss, and additional load losses. In a medium-power, 4-pole motor at rated load the largest share usually belongs to the copper losses; stator and rotor together make up roughly half or a little more of the total loss, iron loss follows, and friction and additional losses remain in smaller slices.
This distribution is not fixed, however: it shifts markedly with motor power, number of poles and above all the load ratio (general information; confirm with the motor manufacturer's test data).
Where do the five loss items arise?
Stator copper loss is the part of the current flowing through the ohmic resistance of the winding that turns into heat, calculated as PCu1 = 3 × I² × Rphase. Because it grows with the square of current, it rises quickly as load increases. Resistance also rises as the winding heats up, so a hot motor has more loss than a cold one at the same current.
Rotor copper loss is released in the bars and end rings of the aluminium or copper rotor cage. It is hard to measure directly. It can, however, be calculated from slip: PCu2 = s × Pair gap. In other words, the larger the slip, the greater the share of power passing from stator to rotor that turns into heat in the rotor.
Iron loss arises in the stator and rotor laminations through hysteresis and eddy currents. If supply voltage and frequency are constant it changes little whatever the load; the motor carries a similar iron loss whether idle or at rated load. When voltage rises, magnetisation increases and iron loss grows noticeably.
Friction and windage loss is the power spent on bearing friction and on the fan and rotor moving the air. It is strongly linked to speed; since speed stays almost constant as load changes, in practice it behaves like a fixed loss.
Additional load losses stem from leakage flux and harmonics, increase with load and are the hardest item to measure directly.
Loss shares at full load: what does the number of poles change?
Of two motors of equal power, one being 2-pole and the other 6-pole changes the loss distribution. In the 2-pole motor speed is high, so the friction and windage share from fan and bearings grows; in the 6-pole motor more magnetic lamination and winding are needed for equal torque, so the iron and copper shares come to the fore. The table below summarises this tendency qualitatively; numerical shares vary with motor design.
| Loss item | Change with load | Tendency in a 2-pole motor | Tendency in a 6-pole motor |
|---|---|---|---|
| Stator copper loss | Rises with the square of current | Medium | High |
| Rotor copper loss | Rises with slip | Medium | Medium-high |
| Iron loss | Nearly independent of load | Medium | High |
| Friction and windage | Speed-dependent, practically constant | High | Low |
| Additional load losses | Rise with load | Low-medium | Low-medium |
As motor power increases, the total loss ratio falls; as the efficiency class rises, the designer looks for improvement mostly in the copper and iron items.
The improvement between IE3, IE4 and IE5 comes largely from fitting more copper into the slots, from low-loss electrical steel and from designing the fan to create less air friction.
Separating the losses step by step in a hypothetical 15 kW motor
Consider a 4-pole machine with nameplate values of 15 kW and 1465 rpm and a rated-load efficiency assumed, as an example, to be 92%. These values are a calculation example. The efficiency of a real motor should be taken from its nameplate and test report.
- Power drawn from the supply: Pin = 15 / 0.92 ≈ 16.3 kW. Total loss ≈ 1.3 kW.
- Slip: s = (1500 − 1465) / 1500 ≈ 0.023.
- Taking an example value of 0.15 kW for friction and windage, the mechanical power developed by the rotor is ≈ 15.15 kW. Air-gap power ≈ 15.15 / (1 − 0.023) ≈ 15.5 kW.
- Rotor copper loss ≈ 0.023 × 15.5 ≈ 0.36 kW.
- Remainder ≈ 0.8 kW, shared between stator copper loss, iron loss and additional losses. These items can also be separated with a stator winding resistance measurement and a no-load test.
This simple flow also shows why slip is an important indicator. At the same power, a higher rated speed means a lower rotor loss.
The more precise version of the calculation is done with no-load and load tests, as in the general approach of IEC 60034-2-1.

Why does the distribution reverse at partial load?
Because iron and friction losses are nearly independent of load, their share of the total grows when the motor is lightly loaded. Copper losses, on the other hand, fall roughly with the square of load. At half load, stator and rotor copper losses drop to about a quarter of their full-load value. As a result, fixed items dominate the loss budget of a motor at half load.
The peak of the efficiency curve occurs around the load at which variable losses equal fixed losses; in many standard motors this point lies slightly below full load. At a quarter of load, fixed losses remain dominant and efficiency drops markedly. This is why oversized motors run at low efficiency.