The cosφ on the nameplate is the cosine of the phase shift between current and voltage when the electric motor runs at rated voltage and full load. It tells you how much of the apparent power drawn from the supply becomes active power at the shaft, but only at that rated point; at half load or idling, the value read in the field comes out clearly lower than the plate.
Which operating point does the nameplate cosφ describe?
It describes a single point: rated voltage, rated frequency and continuous operation at the shaft power printed on the plate. Manufacturers determine this figure in the type test, with the machine carrying full load. Expecting the same number at no load, at part load or at low voltage is a flawed comparison from the start.
On some plates the value appears as "cos φ", on others as "PF". Dual-voltage plates such as 230/400 V carry only one cosφ, because the winding sees the same voltage whether it is connected in star or delta.
Small, multi-pole machines show a lower figure. The reason is the air gap: in a small 6-pole motor, the share of current needed just to build the field is larger than in a big 2-pole unit (general information; confirm with the machine manufacturer).
How do cosφ, current and efficiency cross-check each other on the plate?
In a three-phase motor, shaft power, line current, line voltage, cosφ and efficiency are tied together by one equation; if one of them does not fit, the plate has been misread or the winding was altered during a rewind.
Pshaft = √3 × U × I × cosφ × η
Take a hypothetical check. In the HEM Motor catalogue, the 7.5 kW model with code 132M-4 has a rated current of 14.3 A at 400 V. √3 × 400 × 14.3 comes to roughly 9,907 VA, and since shaft power is 7,500 W, the product of cosφ and efficiency works out at about 0.76. If we imagine a plate reading cosφ 0.82, efficiency would have to sit somewhere near 0.92. Both numbers are only an example; the real cosφ and efficiency of the model are taken from the catalogue or confirmed with the order.
On an old motor with a half-erased plate, the same equation works backwards. You read full-load current with a clamp meter and line-to-line voltage with a multimeter; split that against the active power shown on a power analyser and it becomes obvious on its own whether cosφ or efficiency looks odd.
Why does cosφ drop as load decreases?
Because the reactive current that builds the magnetic field is almost independent of load and keeps flowing at about the same level while voltage stays constant; when load falls, only the active current shrinks.
A motor turning at half load still shows a noticeable current on the ammeter. An ever larger part of that current does no work and simply keeps the field alive. With the coupling removed and the shaft spinning freely, cosφ falls far below the plate value, and on an analyser screen this drop can look like a fault at first glance.
The real consequence shows up at plant scale. Motors chosen one or two sizes too large for a fan, pump or conveyor "just in case" run permanently at part load, drag the average power factor of the site down and add work for the compensation panel. In a facility that exceeds its reactive energy limit, this picture also lands on the electricity bill.
Which instrument measures cosφ on site, and in what order?
The most reliable result comes from a power analyser that sees all three voltages and all three currents at the same time. A single-clamp wattmeter gives only a rough idea, and only when the voltages are balanced.
Run the machine under normal process load for at least 15–20 minutes; a reading taken on a cold winding drifts somewhat as it warms up.
Attach the voltage probes at the nearest accessible point to the motor terminals and the current clamps to the same phases; the arrow on each clamp should point towards the load.
Check the phase sequence on the analyser screen and confirm that the active power of every phase is positive.
Log active power, apparent power and cosφ for a few minutes; do not rely on one instantaneous reading.
Read the speed with an optical tachometer at the same time; slip is a second clue to how close the motor runs to its rated load.
Analysers often display two different numbers. PF is the total power factor including harmonics; cosφ (DPF) gives only the phase shift of the fundamental, and that is what you compare with the plate. On a motor fed by a frequency converter, the value read on the drive input is the power factor seen by the grid and cannot be compared directly with the motor nameplate. Our three-phase series are suitable for speed control with a frequency converter; for long periods of full torque at low speed an external fan may be needed; if the drive-to-motor cable is long, a dv/dt or sine filter is considered; these conditions are stated with the order.
When measuring cosφ, the voltage probes are connected at the point closest to the terminal box (representative image).
Prices and technical data are on the product pages; choose a model and order online.
If the measured value deviates from the plate, where do you look first?
Read the direction of the deviation together with the current level and the cause usually narrows down to a few checks. The mapping below sets the order of checks on site; it is not a limit taken from a standard.
Seen on the analyser
Likely reason
Look here first
cosφ far below the plate, current also well below rated current
Motor running at light load
Speed and slip, real demand of the process
cosφ low, current close to rated value
Over-magnetising from high supply voltage, or turns removed during a rewind
Terminal voltage, earlier no-load current record
cosφ above the plate, current above rated value
Overload or low voltage
Voltage log, resistance of the driven machine
Different cosφ in each of the three phases
Voltage unbalance or a clamp fitted the wrong way
Clamp direction, the three line-to-line voltages
cosφ almost 1 at the measuring point
Measurement taken on the supply side of a capacitor at the motor terminals
Move probe and clamp to the motor side of the capacitor
The last row is often missed. In older plants with a fixed capacitor at the motor, a clamp placed on the cable before the capacitor connection measures the compensated line and makes the motor look better than it is.
How is the nameplate cosφ used in a compensation calculation?
The plate cosφ is the starting figure for the reactive power the motor draws at full load: Q = P1 × tanφ. Here P1 is the active power taken from the supply, found by dividing shaft power by efficiency.
In a hypothetical case, a motor drawing 8 kW from the grid with cosφ 0.82 on its plate has a tanφ of about 0.70; at full load it draws roughly 5.6 kVAr of reactive power. At part load this value is found by measurement, not by calculation.
The plant's electrical engineer decides the capacitor steps and whether a capacitor will be connected straight to the motor terminals. If a capacitor at the motor exceeds the machine's no-load magnetising demand, the motor can self-excite when power is cut and hold voltage at the terminals for a while; no capacitor is ever connected to a frequency converter output (general information; confirm with the project engineer). If the stepped relay in the panel cannot reach its target value, the first thing to check is whether the phase carrying the current transformer matches the phases from which the relay takes its voltage.
Where do people go wrong when choosing an electric motor by its cosφ?
The most common mistake is oversizing for a safety margin and assuming the high cosφ on the plate will hold in the field. A machine chosen too large runs at a lower cosφ under its real load.
Measure the active power of the existing motor under load first, then pick the size. If the analyser points to a shaft demand of around 6 kW and the start is light, 7.5 kW can be considered instead of 11 kW; with a heavy start or peak loads, that decision is made together with the machine builder. For anyone making this comparison, three cast iron models at 1500 rpm are listed with their catalogue current in the electric motor shop:
112M-4: 4 kW; rated speed 1450 rpm, catalogue current 7.95 A (400 V), winding 400/690 V.
132M-4: 7.5 kW; rated speed 1460 rpm, catalogue current 14.3 A (400 V). This is the example used in the cross-check above.
160M-4: 11 kW; rated speed 1465 rpm, catalogue current 20.4 A (400 V).
All of them have IP55 frame protection and class F winding insulation. HEM Motor offers IE3, IE4 and IE5 options in this family; which efficiency class applies to which code, and the cosφ printed on the plate, are confirmed with the order. Other powers and speeds of the same family are on the 3-phase asynchronous electric motors page.
Send the analyser log and a readable photo of the old plate through the channels on our contact page, and we will work out the load ratio together and talk through whether one size down makes sense. Aluminium-frame equivalents and 2- to 6-pole options sit in power order on the HEM Motor sales list.
Frequently Asked Questions
How do you find cosφ if it is not printed on the plate?
If current, voltage, shaft power and efficiency can be read, it is calculated from the equation above. If efficiency is missing as well, it is measured with a power analyser while the motor runs at full load.
Is cosφ interpreted the same way on a single-phase motor?
The logic is the same, but √3 drops out of the equation: P = U × I × cosφ × η. In permanent-capacitor single-phase motors, cosφ is also affected by the capacitor value.
Does a high cosφ mean high efficiency?
No. cosφ shows how much of the current is active, while efficiency shows how much of the active power taken from the supply reaches the shaft; they are separate quantities.
Does correcting cosφ with a capacitor reduce the motor winding current?
It does not. Line current on the supply side of the capacitor falls, while the current through the motor winding stays the same.
HEM Motor Models Related to This Article
The cards show example models related to the topic. A suitable motor is not chosen by power alone: compare speed, voltage, mounting, shaft and connection dimensions on the product page; if unsure, send a photo of the existing motor’s nameplate on WhatsApp.
In compact electric motor selection, power density shows how small a frame the same kilowatts are taken from; cooling area is the outer surface through which that frame can shed he... More Details
An aluminium frame is a sound choice for drives with low vibration, coupling alignment or moderate pulley load, no shocks and a flat base. Where small pulleys put a large radial lo... More Details
IEC and NEMA nameplates are not compared directly but field by field after translation: power from HP to kW, protection from enclosure type to IP code, while efficiency class and s... More Details
IP55 protection is enough in most cases for an electric motor working outdoors, provided the motor does not take rain directly, condensation water can drain from the frame, and the... More Details
Class F insulation means the winding materials are chosen to withstand up to 155 °C; Class B temperature rise means that at rated load the motor's winding rises no more than 80 K a... More Details
No, they are not the same thing. The insulation class defines the thermal ceiling of the insulating material around the winding; the permitted ambient temperature shows how warm th... More Details