Is the Insulation Class of an Electric Motor the Same as the Permitted Ambient Temperature?

Is the Insulation Class of an Electric Motor the Same as the Permitted Ambient Temperature?

No, they are not the same thing. The insulation class defines the thermal ceiling of the insulating material around the winding; the permitted ambient temperature shows how warm the surrounding air may be while the motor delivers its nameplate power. An F class motor does not mean it can run in a 155 °C environment; that temperature is the ceiling for the hottest spot inside the winding.

Which temperature does the letter of the insulation class describe?

The letter shows the temperature the insulation system (enamelled wire, slot paper, varnish and binding materials together) can withstand over a long period. In the thermal classification of IEC 60085 the 130 °C ceiling is marked with the letter B and the 155 °C ceiling with the letter F (general information; confirm with the machine manufacturer). That is a 25 degree step.

This value is not an ambient temperature. It is a ceiling set for the hottest spot of the winding, usually the area in the middle of the slot and on the inner side of the end windings. The value you read on the frame with a thermometer never reaches that spot; there is always a temperature difference between frame and winding.

Where does the ambient temperature limit come from?

The nameplate values of standard motors are given for the default condition in IEC 60034-1, that is, surrounding air not above 40 °C and an installation altitude not above 1000 m. The kW, current and speed on the plate apply under that condition.

The hottest spot of the winding is found by adding three parts:

Thottest spot = Tambient + ΔTaverage winding + hot spot allowance

For class F, the standard limits the average winding temperature rise, measured by the resistance method, to 105 K. A 40 °C ambient plus a 105 K rise totals 145 °C; the roughly 10 K left to 155 °C covers the gap between the average and the hottest spot. When ambient rises to 50 °C at the same load, that margin melts away and the insulation ceiling comes closer.

If the plate carries no marking such as "Ta 40 °C", the motor is assumed to be calculated for 40 °C.

Why are the insulation letter and the temperature rise letter written separately in a specification?

Because keeping a winding with F insulation within the B limit for heating leaves the material a reserve of about 25 K. That reserve is what gets used on a hot afternoon or during a few minutes of overload. The shorthand "insulation F, rise B" in specifications describes exactly this.

On site this reserve may seem to make no difference in a stuffy switchroom in summer or on a conveyor beside a furnace, but it builds up on insulation life. As a general approach, when the hottest spot runs 10 K higher continuously, the expected insulation life is roughly halved (general information; confirm with the machine manufacturer). The reverse is also true: a winding running 10 K cooler lasts longer.

When ordering, asking in which temperature rise class the motor was tested is a good habit for plants with harsh ambient conditions.

Prices and technical data are on the product pages; choose a model and order online.

How is winding temperature rise measured on site?

The most reliable method is to measure winding resistance cold and again right after the motor has warmed up under load, then calculate the difference. A thermometer stuck to the frame or an infrared gun cannot see inside. It only tracks the surface trend.

  1. With the motor stopped for at least several hours, record the ambient temperature (T1) and the winding resistance between two terminals (R1) with a micro-ohmmeter or a four-wire measuring instrument.
  2. Run the motor at its normal load until the frame temperature no longer changes noticeably over half an hour.
  3. After stopping and isolating, measure the resistance (R2) on the same terminals without delay, within seconds; also note the ambient temperature at that moment (Ta).
  4. For a copper winding, calculate the average temperature rise: ΔT = (R2 − R1) / R1 × (235 + T1) + T1 − Ta.

Hypothetical example: cold at 20 °C R1 = 1.00 Ω, hot R2 = 1.38 Ω, and ambient 30 °C at the moment of stopping. ΔT = 0.38 × 255 + 20 − 30 ≈ 87 K. The result is below the F limit. It slightly exceeds the B limit, though. If the same motor is moved into a 45 °C room, the average winding temperature rises to about 132 °C and the margin left for the hottest spot narrows.

The most common mistake in this measurement is letting five or ten minutes pass between stopping and reading the resistance. The winding cools in that time and the calculated rise looks lower than it really is. Every minute counts here.

Three-phase electric motor seen from the fan cover side
The fan cover and frame fins are the only path by which ambient air can carry away winding heat (representative image).

What must be taken into account for a motor working in a hot environment?

If the surrounding air exceeds 40 °C or the plant sits higher than 1000 m, the power the motor can deliver continuously is derated. The derating factor is taken from the table in the manufacturer's catalogue; for HEM Motor models this value should be confirmed with the order. The power steps are sorted by frame on the electric motor sales page.

Do not guess. First, measure which air the motor really breathes: on the intake side of the fan, about half a metre from the motor, at midday. Beside a furnace, dryer or compressor outlet this value can be very different from the hall temperature, and only once you have that figure should you compare the actual shaft power of the machine with the motor plate and check whether the gap covers the derating factor. If it does not, the next power step, moving the motor away from the hot zone or bringing a fresh-air duct are put on the table as options.

A fan cover clogged with dust has the same result as warming the ambient by several degrees.

A PTC sensor embedded in the winding and an anti-condensation heater are order options; in environments where temperature changes often, the PTC monitors heating directly in the winding that the thermal relay cannot see.

Which HEM Motor models can serve as examples for this calculation?

In the standard HEM Motor series the protection degree is IP55, insulation is class F and frequency is 50 Hz; IE3, IE4 and IE5 efficiency classes are offered, and which class is available for a given model is confirmed with the order. The 4-pole cast iron steps below can be used in a derating calculation for a hot foundry conveyor or a drying line fan:

  • 112M-4: 4 kW, 1450 rpm, 7.95 A at 400 V, 400/690 V (Δ/Y).
  • 132S-4: 5.5 kW, 1460 rpm, 10.7 A at 400 V. The step to check when a machine with about 4 kW shaft power needs a margin for a hot environment.
  • 160M-4: 11 kW, 1465 rpm, 20.4 A at 400 V.

All steps are listed in the electric motor store; the other frames of the same family are shown on the general purpose industrial motors page.

Write the ambient temperature you measured where the motor will run, the altitude and the real load of the machine through the contact page; with these three pieces of information we will pin down which step the derating leads to. Prices and frame options are in the HEM Motor product list.

Frequently Asked Questions

Does a motor with F insulation deliver full power in a 60 °C environment?

Nameplate power is usually written assuming 40 °C surrounding air. In a hotter environment derating applies; the factor is taken from the catalogue and confirmed with the order.

If the frame is at 80 °C, is the winding also at 80 °C?

No, the winding is always hotter than the frame. Frame readings are used for trend monitoring; the real heating of the winding is found with the resistance method.

Does high altitude have the same effect as ambient temperature?

It acts in a similar direction; thin air carries less heat. Above 1000 m cooling weakens and the motor heats up more for the same power.

When is a PTC sensor needed?

If ambient temperature fluctuates, the motor starts and stops often or cooling air can be interrupted, a PTC monitors the winding directly. It is specified as an option with the order.

HEM Motor Models Related to This Article

The cards show example models related to the topic. A suitable motor is not chosen by power alone: compare speed, voltage, mounting, shaft and connection dimensions on the product page; if unsure, send a photo of the existing motor’s nameplate on WhatsApp.

4 kW 1500 rpm Cast Iron Frame Electric Motor 112M-4

112M-4

4 kW · 1500 rpm

  • Cast iron frame · IEC 112M
  • 1450 rpm · IP55
  • Mounting: B3 foot; flange (B5/B14/B35) depending on frame, confirmed with the order

US$249.49 (€228.34)

View product
5.5 kW 1500 rpm Cast Iron Frame Electric Motor 132S-4

132S-4

5.5 kW · 1500 rpm

  • Cast iron frame · IEC 132S
  • 1460 rpm · IP55
  • Mounting: B3 foot; flange (B5/B14/B35) depending on frame, confirmed with the order

US$335.43 (€306.99)

View product
11 kW 1500 rpm Cast Iron Frame Electric Motor 160M-4

160M-4

11 kW · 1500 rpm

  • Cast iron frame · IEC 160M
  • 1465 rpm · IP55
  • Mounting: B3 foot; flange (B5/B14/B35) depending on frame, confirmed with the order

US$557.82 (€510.52)

View product

Similar Articles