To verify the values on an asynchronous electric motor nameplate in the field, you turn the nameplate into a measurement plan: voltage and connection type are checked in the terminal box, current with a clamp meter on all three phases, speed with a tachometer, and power and torque by simple calculations from those readings. Nameplate values describe the rated point; if the field reading departs from it, the cause is sought on the motor, supply or load side.
Which nameplate value can be measured directly in the field, and which is tested by calculation?
Voltage, current and speed are measured directly; power, torque and power factor are tested by calculation from the measured values. Design values such as insulation class and degree of protection are not measured in the field; only their symptoms are checked.
Nameplate line
Field method
Tool used
Voltage and connection (Δ/Y)
Look at the terminal links, measure line-to-line voltage
True-RMS multimeter
Rated current
Read the current on each of the three phases separately
Clamp meter
Rated speed
Measure speed at the shaft end, calculate slip
Optical or contact tachometer
Rated power and torque
Calculate from measured current, voltage and speed
Power analyser or calculation sheet
Frequency
Read the supply frequency (output frequency on converter-fed motors)
Multimeter or converter display
Insulation class, degree of protection
Indirect signs only: temperature, condition of seals and cable entry
Thermometer, visual check
How is the voltage and connection line confirmed in the terminal box?
A dual voltage on the nameplate (for example 230/400 V or 400/690 V) describes two connection types: the lower value belongs to delta, the higher value to star. Whichever value matches the line-to-line voltage of the supply, the winding must run in the connection next to that value.
On a 400 V supply, a motor rated 230/400 V is connected in star, and a motor rated 400/690 V in delta. The supply voltage decides the connection. When you open the terminal box, check whether the links sit side by side across the three terminals (delta) or are joined in a single row (star), and compare this with the diagram on the nameplate. Then read the three line-to-line voltages with the motor running; the difference between them should be small.
On a panel with star-delta starting, the motor must be rated 400/690 V, because in the run position the winding is connected in delta and sees 400 V directly. If a motor rated 230/400 V is connected to such a panel, excess voltage is applied to the winding in the delta position. The winding will not stand this voltage for long.
Under what condition should nameplate current be compared with measured current?
Nameplate current applies at rated voltage and rated shaft power, so the comparison is made once the motor has reached thermal equilibrium and the machine is at its normal production load. A reading taken right after starting or with the machine unloaded is not compared with the nameplate. A cold motor misleads.
Read the three phases separately, take the average and write the voltage at the time of reading on the same line. A single-phase reading misleads. If voltage is below the rated value, current rises slightly for the same shaft power; if it is above, magnetising current increases. A reading above the nameplate calls for checking connection and voltage first, then the mechanical load. A reading far below the nameplate means the motor is running at part load; on its own that is not a problem.
How does a speed measurement confirm the rated speed on the nameplate?
If the measured speed lies between the rated speed on the nameplate and the synchronous speed, the motor is running below rated load; if it falls below the rated speed, it is above rated load. Synchronous speed is found from frequency and pole count:
ns = 120 × f / p
On a 50 Hz supply this gives 3000 rpm for a 2-pole motor, 1500 for a 4-pole and 1000 for a 6-pole. Slip is calculated with s = (ns − n) / ns. For an optical tachometer reading, a small piece of reflective tape is stuck on the shaft end or the coupling hub; the tape is not stuck inside the fan cover.
A 4-pole motor with 1450 rpm on its nameplate has a rated slip of 50 rpm. If 1462 rpm is measured in the field, slip is 38 rpm and load is roughly 38 / 50 ≈ 76%. The motor is running at three-quarter load. This ratio is approximate; the speed on the nameplate is also written with a tolerance and winding temperature affects slip (general information; confirm with the machine manufacturer).
The nameplate, terminal box and shaft end are the three main check points in the field (representative image).
Prices and technical data are on the product pages; choose a model and order online.
Are the power, torque and horsepower values consistent with each other?
There is a fixed relationship between power, speed and torque on the nameplate, and the nameplate is tested against itself with it:
T [Nm] = 9550 × P [kW] / n [rpm]
As a hypothetical example, take a 4 kW, 1450 rpm motor: 9550 × 4 / 1450 ≈ 26.3 Nm. That is also the rated torque on the product page of HEM Motor's 112M-4 model. Calculation and catalogue agree. When the torque on a nameplate or in a catalogue differs clearly from this calculation, one of the lines has been misread or the nameplate belongs to another motor.
For horsepower, 1 HP = 0.746 kW is used. 4 kW is about 5.36 HP; nameplates and catalogues, however, show rounded series values such as 5.5 HP. The small difference is not an error, but if a nameplate saying 4 kW shows 7.5 HP, the case should be investigated.
What should be done with a motor whose nameplate is unreadable or doubtful?
The nameplate may have been worn off, painted over or replaced after a rewind; in that case the values are rebuilt backwards from measurements. Measurement takes the place of the nameplate. The IEC frame number on the housing (for example 112M) is usually found separately on the casting or a label and is the first clue.
To find synchronous speed, run the motor at no load and measure speed; a value close to 1500 rpm means 4 poles.
Measure the resistance of the three windings with the same instrument; they should be close to one another, and a large difference points to a winding problem.
Measure winding-to-frame insulation resistance with a megger and assess the value using the interpretation recommended by the instrument manufacturer.
Record no-load and loaded current and compare them, together with frame number and speed, with catalogue values at the same power step.
Match dimensions such as shaft diameter, foot hole spacing and flange against the frame table in the technical drawings.
The IEC frame number is the first piece of information for compatibility; the exact fit is confirmed by comparing mounting type, shaft diameter and length, foot hole spacing, flange and electrical values. If you still cannot be sure after these steps, photos of the nameplate and connection should be assessed together with the measured values.
Example electric motors matching the nameplate values
Why the connection line matters can be seen at two neighbouring power steps of the 4-pole cast iron series: the 3 kW model's nameplate says 230/400 V, the 4 kW model's says 400/690 V. The motor going onto the same panel should not be chosen without comparing this line with that of the old motor. A wrong line means a wrong connection. The models are listed with their nameplate data in the electric motor shop:
100L2-4: cast iron, 3 kW, 1450 rpm, 230/400 V (Δ/Y), 6.02 A at 400 V, 19.8 Nm.
112M-4: cast iron, 4 kW, 1450 rpm, 400/690 V (Δ/Y), 7.95 A at 400 V, 26.3 Nm. The model in the torque calculation.
132S-4: cast iron, 5.5 kW, 1460 rpm, 400/690 V (Δ/Y), 10.7 A at 400 V, 36 Nm.
The standard series comes with IP55 protection, class F insulation and 50 Hz; it is offered in IE3, IE4 and IE5 efficiency classes, and the class for each model is confirmed with the order. B3, B5, B14, B34, B35 and vertical V1/V3/V5/V6/V15 are offered depending on frame; flange size is confirmed with the order. The full power and speed table of the family is on the 3-phase asynchronous electric motors page.
If the nameplate values you read in the field and the voltage, current and speed you measured do not agree, send a clear photo of the nameplate and your measurement table through the find-an-equivalent-from-the-nameplate page; we will sort out together which line is doubtful. Other steps you may want to compare are open in the HEM Motor model list.
Frequently Asked Questions
The nameplate shows two current values; which one should I use?
The two currents belong to two voltages: the higher current is for the lower voltage (delta), the lower current for the higher voltage (star). Use the value that corresponds to your supply voltage.
If the speed I measure is higher than on the nameplate, is the motor faulty?
Usually not; when the motor runs below rated load, its speed approaches synchronous speed. The case to watch is speed falling clearly below the rated value on the nameplate.
How do I check the cosφ value on the nameplate in the field?
It is measured with a three-phase power analyser while the motor is running close to rated load. At part load the power factor falls below the nameplate value, which is normal.
Can I trust the nameplate of a rewound motor?
If the winding data changed during repair, the nameplate may no longer describe the motor. The nameplate needs to be tested again with no-load current, winding resistance and speed measurements.
HEM Motor Models Related to This Article
The cards show example models related to the topic. A suitable motor is not chosen by power alone: compare speed, voltage, mounting, shaft and connection dimensions on the product page; if unsure, send a photo of the existing motor’s nameplate on WhatsApp.
In an asynchronous electric motor, slip grows roughly in proportion to load across the normal operating range: the rotor, which turns just below synchronous speed at no load, falls... More Details
An asynchronous electric motor is an AC machine whose rotor turns because the rotating field set up by the stator windings induces current in the rotor bars, so the shaft always ru... More Details
When selecting an asynchronous electric motor for a heavy inertia load, the deciding factor is not continuous running power but whether the motor can bring the load up to rated spe... More Details
Shaft end load on an asynchronous electric motor is the radial force that the belt pull on the pulley places on the shaft and, through it, on the drive-end bearing; the closer the ... More Details
The five operating mistakes that age an asynchronous electric motor early are: forcing a motor chosen for continuous duty into frequent starts, running it on unbalanced or low volt... More Details
In an asynchronous electric motor, most of the no-load current is magnetising current and is almost independent of load; the part that grows as load is applied is the active compon... More Details