When selecting an asynchronous electric motor for a heavy inertia load, the deciding factor is not continuous running power but whether the motor can bring the load up to rated speed within an acceptable time. To check this, the load inertia referred to the motor shaft, the average torque the motor delivers during start-up and the load's counter-torque are calculated together; the acceleration time must stay below the motor's permissible starting time.
Large fan impellers, flywheel presses, crusher rotors, centrifuges and mill drums fall into this class. On these machines a motor that seems powerful enough can overheat the rotor during start-up and trip the protection relay.
Why is an inertia load calculated separately from continuous power?
Because the energy needed to spin a heavy mass is spent only during start-up, until the machine reaches rated speed, and a large share of that energy turns into heat in the rotor. This load never shows in the continuous power figure. For example, a fan that needs only 22 kW in continuous operation can hold the motor at high current for more than 20 seconds while starting.
During start-up the current drawn from the supply is several times the rated value on the nameplate; in those seconds the rotor bars and stator winding heat up with no chance to cool. On a pump with a short start this lasts a few seconds and causes no trouble; on a load with high inertia the time stretches and heat builds up. Here fan and pump part ways. Two questions are asked in selection: does the motor produce enough torque to accelerate the load, and does this acceleration finish within the motor's thermal limits?
How is load inertia referred to the motor shaft?
The inertia of a load connected through a belt or gearbox is referred to the motor shaft by multiplying it by the square of the speed ratio: Jreferred = Jload × (nload / nmotor)². If the machine runs slower than the motor, the inertia felt at the shaft decreases; if it runs faster, it increases.
Total inertia is found by adding the inertias of the motor rotor, the pulleys and the coupling to this value. Fan and flywheel inertia is taken from the machine manufacturer's data; if it is missing, a rough estimate can be made from the impeller's mass and radius, but the margin of error is large. The inertia values in this article are given in SI units.
Hypothetical example: a fan impeller with an inertia of 60 is belt-driven at 1000 rpm, the motor runs at 1475 rpm. The referred inertia is 60 × (1000 / 1475)² ≈ 27.6. Adding a hypothetical 0.3 for the rotor and pulleys gives a total of about 27.9.
Which formula gives the acceleration time?
The acceleration time is found by dividing the product of total inertia and angular speed by the average accelerating torque:
ta = Jtotal × ω / (Tmotor,avg − Tload,avg) ω = 2π × n / 60
Tmotor,avg is the average of the torque the motor delivers from standstill to rated speed and is estimated from the torque curve read at the locked-rotor, breakdown and pull-up points. Tload,avg is the load's counter-torque over the same range. On a fan the counter-torque rises with the square of speed, so its average is taken as roughly one third of the full-speed value (general information; confirm with the machine manufacturer).
Let us continue the example. Take a 30 kW motor at 1475 rpm with a rated torque of 194.2 Nm. With direct-on-line starting, assume a hypothetical average motor torque of 350 Nm and a fan counter-torque of 160 Nm at full speed referred to the motor shaft; the average counter-torque is then about 55 Nm. ω = 2π × 1475 / 60 ≈ 154.5 rad/s. The acceleration time comes out at 27.9 × 154.5 / (350 − 55) ≈ 14.6 seconds.
Why is star-delta starting inadequate for heavy inertia?
In star the voltage per winding drops, so torque stays at roughly one third of the delta value; with high inertia the net accelerating margin melts away, and the start either drags on or the motor stalls at an intermediate speed. While trying to lower the current, you raise the rotor's thermal load.
In the same example the average motor torque in star falls to about 117 Nm. With a counter-torque of 55 Nm the net accelerating torque is 62 Nm and the time rises to 27.9 × 154.5 / 62 ≈ 70 seconds. Moreover, because the fan's counter-torque grows with speed, the motor may never reach rated speed in star; at the changeover to delta the current jumps to a level close to a direct start. An electronic soft starter also cuts the voltage and therefore reduces torque in proportion to the square of the voltage; it runs into the same bottleneck.
Two routes suit heavy inertia better: a ramped start with a frequency converter (it gives torque close to rated torque while the current is limited) and mechanical solutions such as a fluid coupling that bring the load in after the motor. Our three-phase series are suitable for speed control with a frequency converter; long periods at low speed with full torque may require an external fan; if the drive–motor cable is long, a dv/dt or sine filter is considered; these conditions are stated with the order.











