How to Assess Unbalance in the Phase Currents of an Electric Motor

How to Assess Unbalance in the Phase Currents of an Electric Motor

Unbalance in the phase currents of an electric motor is assessed as a percentage: the difference of the current that deviates most from the three-current average is divided by that average. Current unbalance alone is not a diagnosis; the line-to-line voltages are measured at the same time, because a small voltage unbalance shows up several times larger in the motor current.

How is current unbalance calculated as a percentage?

Take the average of the three phase currents, divide the difference of the current furthest from that average by the average, and multiply by 100. This is the calculation described for voltage in NEMA MG 1, applied to current, and it is the most widely used form on site.

Unbalance (%) = 100 × (maximum deviation) / (average current)

Take a hypothetical reading: L1 = 20.4 A, L2 = 19.1 A, L3 = 21.9 A. The average is 20.47 A. The furthest value is L3, with a difference of 1.43 A; 1.43 / 20.47 gives roughly 7%. If the line-to-line voltages in the same plant read 398, 401 and 404 V, voltage unbalance is only about 0.75%.

No interpretation is made without putting these two numbers side by side.

A small difference in voltage grows in the motor because the motor's impedance to the negative-sequence voltage is close to its locked-rotor impedance and is quite low (general information; confirm with the instructions of the instrument and machine manufacturers).

Why does voltage unbalance appear magnified in the motor current?

An unbalanced three-phase system behaves like the sum of a positive-sequence component rotating forwards and a negative-sequence component trying to rotate backwards. While the motor runs on the positive sequence, the negative sequence induces current in the rotor at roughly twice the frequency.

The rotor reacts to this reverse field almost like a short circuit. The effect is not small. A 1% voltage unbalance can create a current unbalance roughly six to ten times as large, depending on motor type and load. The extra current increases copper losses and temperature rises quickly in the most heavily loaded phase of the winding.

IEC 60034-1 expects motors to deliver rated power under a small voltage unbalance; beyond that, manufacturers recommend derating. For the exact percentage and derating curve, refer to the text of the standard and to the motor manufacturer.

In what order, and with which instrument, should the measurement be made?

A power analyser that logs three currents and three voltages at the same time gives the cleanest result. A single clamp also works but needs care: if a screw conveyor fills and empties or a press arm goes up and down in the few seconds it takes to move the clamp from one phase to the next, the three readings no longer describe the same load and the calculated percentage shows load fluctuation more than real unbalance.

  1. Run the motor under normal process load for at least 15 minutes; values right after starting show the unbalance differently from how it really is.
  2. Read the three line-to-line voltages at the point closest to the motor terminals and note them.
  3. Read the three phase currents with a true-RMS clamp. If you use a single clamp, measure each phase at least twice, in the same order.
  4. Calculate current and voltage unbalance separately and write both on the same form.
  5. For repeatability, repeat the measurement at different times of the shift, especially when welding machines or large single-phase loads are on.

On a motor driven by a frequency converter, the measurement is made at the drive output and the drive's own phase-current display is checked as well. Our three-phase series are suitable for speed control with a frequency converter; for long periods of full torque at low speed an external fan may be needed; if the drive-to-motor cable is long, a dv/dt or sine filter is considered; these conditions are stated with the order.

Cast iron three-phase electric motor and terminal box
Voltage is measured at the point closest to the terminal box; the clamps go on the same phases (representative image).

Is the source of the unbalance the supply or the motor?

The quickest way to separate the source is to roll the supply leads one step at the terminals: move L1 from U1 to V1, L2 from V1 to W1 and L3 from W1 to U1. If the high current stays on the same supply phase, the problem is in the supply; if it follows the same motor winding, the problem is in the motor.

This method does not change the direction of rotation. Phase sequence is kept. Lock-out and tag-out come first, and the terminal nuts are tightened to the same value with a torque wrench; otherwise a loose connection becomes a new source of unbalance.

After rollingInterpretationNext check
High current stayed on the same supply phaseSupply-relatedPanel connections, contactor contacts, cable joints, load distribution on the transformer
High current moved with the motorMotor-relatedWinding resistance, insulation resistance, terminal board
Unbalance disappearedThere was a loose or oxidised terminal connectionThermal camera scan of the connection points under a short load

Prices and technical data are on the product pages; choose a model and order online.

If the motor is the cause, which measurements follow in order?

After power is cut and locked out, winding resistance is measured first, then insulation resistance. A clear difference between winding resistances is the most common sign of an inter-turn short or a loose internal connection.

For small resistances, use a micro-ohmmeter or a four-wire instrument. An ordinary multimeter loses differences below a few ohms in the probe resistance.

Temperature also moves the reading. A winding that has just stopped is hot and shows higher resistance, so the three phases are measured together after the same cooling time and the values are logged with that winding temperature.

Insulation is measured with a megger at a test voltage suited to the motor's rated voltage. Readings are taken winding by winding against the frame and recorded; a trend that falls over time is an early sign of moisture or contamination. A broken rotor bar shows itself less through current unbalance than through current pulsing at slip frequency, and is examined separately by current signature analysis.

What level of current unbalance counts as acceptable?

There is no single universal limit for current; many maintenance programmes use a few per cent as the threshold for monitoring and anything above it as the threshold for investigation. What decides is the change against the same motor's earlier record and the ratio to voltage unbalance.

If current unbalance rises while voltage is balanced, the motor or the connections are examined. The opposite happens too. If voltage is unbalanced and current is distorted by a matching amount, the supply is corrected first; replacing the motor does not solve the problem. For setting phase-loss and unbalance protection on the thermal relay, our motor protection article explains which device acts on which fault.

If the motor is to be replaced, how is the choice made?

If a rewind is not possible or the motor is old, the new one is chosen with the same power, speed and mounting type; compatibility starts with the IEC frame number and is confirmed by comparing shaft, flange and foot dimensions against the technical drawing.

The current of around 20 A in the hypothetical example above corresponds to the 4-pole 11 kW class.

Example models are listed as follows in our electric motor shop:

  • 160M-4 cast iron frame, 11 kW, 1465 rpm, 20.4 A at 400 V; the size matching the currents in the example.
  • 160M-4 aluminium frame, same power and speed; considered for machines with a light base frame in dry surroundings.
  • 160L-4 cast iron, 15 kW, 1465 rpm, 27.3 A; one size up if the existing motor runs permanently at its limit.

All come with IP55, class F insulation and a 400/690 V winding. Every power of the family is on the 3-phase asynchronous electric motors page, and the first energising steps for the new motor are in the commissioning guide.

Send your three current readings, three voltages and winding resistances together with the old motor's nameplate through our equivalent-from-nameplate page, and we will first use the measurements to discuss whether replacement is needed at all. Other speeds and frame options sit in power order on the HEM Motor sales list.

Frequently Asked Questions

Is current unbalance measured at no load as meaningful as under load?

Since most no-load current is magnetising current, the percentage can come out higher. The decision should rest on the loaded measurement and the earlier record.

Does changing the phase sequence fix the unbalance?

No; it only helps find the source. If the unbalance is in the supply, it is cleared on the panel and transformer side; if it is in the motor, in the winding.

Does unbalance only show up as a high current in one phase?

Not always. One phase can be low and the other two normal; since the calculation is based on the largest deviation, both cases are assessed the same way.

Can the motor keep running while the unbalance continues?

It can run under short-term monitoring, but winding temperature rises and insulation life shortens. Keep a close eye on the thermal protection setting and the winding temperature.

HEM Motor Models Related to This Article

The cards show example models related to the topic. A suitable motor is not chosen by power alone: compare speed, voltage, mounting, shaft and connection dimensions on the product page; if unsure, send a photo of the existing motor’s nameplate on WhatsApp.

11 kW 1500 rpm Cast Iron Frame Electric Motor 160M-4

160M-4

11 kW · 1500 rpm

  • Cast iron frame · IEC 160M
  • 1465 rpm · IP55
  • Mounting: B3 foot; flange (B5/B14/B35) depending on frame, confirmed with the order

US$557.82 (€510.52)

View product
11 kW 1500 rpm Aluminium Frame Electric Motor 160M-4

160M-4

11 kW · 1500 rpm

  • Aluminium frame · IEC 160M
  • 1465 rpm · IP55
  • Mounting: B3 foot; flange (B5/B14/B35) depending on frame, confirmed with the order

US$532.46 (€487.32)

View product
15 kW 1500 rpm Cast Iron Frame Electric Motor 160L-4

160L-4

15 kW · 1500 rpm

  • Cast iron frame · IEC 160L
  • 1465 rpm · IP55
  • Mounting: B3 foot; flange (B5/B14/B35) depending on frame, confirmed with the order

US$665.08 (€608.69)

View product

Similar Articles