Unbalance in the phase currents of an electric motor is assessed as a percentage: the difference of the current that deviates most from the three-current average is divided by that average. Current unbalance alone is not a diagnosis; the line-to-line voltages are measured at the same time, because a small voltage unbalance shows up several times larger in the motor current.
How is current unbalance calculated as a percentage?
Take the average of the three phase currents, divide the difference of the current furthest from that average by the average, and multiply by 100. This is the calculation described for voltage in NEMA MG 1, applied to current, and it is the most widely used form on site.
Unbalance (%) = 100 × (maximum deviation) / (average current)
Take a hypothetical reading: L1 = 20.4 A, L2 = 19.1 A, L3 = 21.9 A. The average is 20.47 A. The furthest value is L3, with a difference of 1.43 A; 1.43 / 20.47 gives roughly 7%. If the line-to-line voltages in the same plant read 398, 401 and 404 V, voltage unbalance is only about 0.75%.
No interpretation is made without putting these two numbers side by side.
A small difference in voltage grows in the motor because the motor's impedance to the negative-sequence voltage is close to its locked-rotor impedance and is quite low (general information; confirm with the instructions of the instrument and machine manufacturers).
Why does voltage unbalance appear magnified in the motor current?
An unbalanced three-phase system behaves like the sum of a positive-sequence component rotating forwards and a negative-sequence component trying to rotate backwards. While the motor runs on the positive sequence, the negative sequence induces current in the rotor at roughly twice the frequency.
The rotor reacts to this reverse field almost like a short circuit. The effect is not small. A 1% voltage unbalance can create a current unbalance roughly six to ten times as large, depending on motor type and load. The extra current increases copper losses and temperature rises quickly in the most heavily loaded phase of the winding.
IEC 60034-1 expects motors to deliver rated power under a small voltage unbalance; beyond that, manufacturers recommend derating. For the exact percentage and derating curve, refer to the text of the standard and to the motor manufacturer.
In what order, and with which instrument, should the measurement be made?
A power analyser that logs three currents and three voltages at the same time gives the cleanest result. A single clamp also works but needs care: if a screw conveyor fills and empties or a press arm goes up and down in the few seconds it takes to move the clamp from one phase to the next, the three readings no longer describe the same load and the calculated percentage shows load fluctuation more than real unbalance.
- Run the motor under normal process load for at least 15 minutes; values right after starting show the unbalance differently from how it really is.
- Read the three line-to-line voltages at the point closest to the motor terminals and note them.
- Read the three phase currents with a true-RMS clamp. If you use a single clamp, measure each phase at least twice, in the same order.
- Calculate current and voltage unbalance separately and write both on the same form.
- For repeatability, repeat the measurement at different times of the shift, especially when welding machines or large single-phase loads are on.
On a motor driven by a frequency converter, the measurement is made at the drive output and the drive's own phase-current display is checked as well. Our three-phase series are suitable for speed control with a frequency converter; for long periods of full torque at low speed an external fan may be needed; if the drive-to-motor cable is long, a dv/dt or sine filter is considered; these conditions are stated with the order.

Is the source of the unbalance the supply or the motor?
The quickest way to separate the source is to roll the supply leads one step at the terminals: move L1 from U1 to V1, L2 from V1 to W1 and L3 from W1 to U1. If the high current stays on the same supply phase, the problem is in the supply; if it follows the same motor winding, the problem is in the motor.
This method does not change the direction of rotation. Phase sequence is kept. Lock-out and tag-out come first, and the terminal nuts are tightened to the same value with a torque wrench; otherwise a loose connection becomes a new source of unbalance.
| After rolling | Interpretation | Next check |
|---|---|---|
| High current stayed on the same supply phase | Supply-related | Panel connections, contactor contacts, cable joints, load distribution on the transformer |
| High current moved with the motor | Motor-related | Winding resistance, insulation resistance, terminal board |
| Unbalance disappeared | There was a loose or oxidised terminal connection | Thermal camera scan of the connection points under a short load |