When building a sound enclosure around an electric motor, cooling is preserved by giving the enclosure a labyrinth or silenced inlet large enough for the air the motor fan draws, plus a separate hot-air outlet. If the inside is a few degrees warmer than the outside, the motor is effectively running in a hotter environment; ventilation is designed to limit that difference.
Why does a closed enclosure spoil motor cooling?
Standard industrial motors cool with a fan outside the frame: the fan draws ambient air through the fan cover grille and blows it over the finned frame. The design assumes the air drawn in is at ambient temperature.
In a closed enclosure the motor draws its own hot air back in. The inside air warms up, the temperature difference between frame and air shrinks, and the same loss heat has to be rejected at a higher winding temperature. Current does not change. The winding heats up.
For the motor, a sound enclosure is above all an ambient temperature issue. The kW value on the nameplate depends on a defined cooling air temperature (general information; IEC 60034-1 mostly uses 40 °C, confirm with the maker's documents). Once the inside air passes that limit, the power available from the motor effectively drops.
How much air must pass through the enclosure?
The airflow needed is calculated from the heat released inside the enclosure and the permitted temperature rise. Most of the heat is motor losses; loss is roughly the difference between input power and shaft power.
The calculation goes like this: first find the loss heat, then the airflow that carries it away at a given temperature rise. For the heat-carrying capacity of air, the relation Q ≈ 3.0 × Ploss / ΔT is used in practice, with Q in m³/h, Ploss in watts and ΔT in kelvin (general information; an approximate value for air density near sea level, confirm with the ventilation designer).
Hypothetical example: if the efficiency of a 15 kW motor is taken as 0.92, the loss is about 15 / 0.92 − 15 ≈ 1.3 kW. If the inside air may be at most 5 K warmer than outside, the airflow needed comes out at 3.0 × 1300 / 5 ≈ 780 m³/h. If a gearbox, pump or compressor sits in the same enclosure, its heat is added.
The motor's own fan moves this airflow over the frame, but it does not exchange the enclosure air with the outside. Whether an auxiliary extract fan is needed is decided by this calculation. The power and current values for the calculation are on the product pages in the HEM Motor shop.
Where should the air inlet and outlet go?
In the right layout, cool air enters on the fan cover side and hot air leaves at the opposite upper corner. Hot air rises; putting the outlet near the ceiling uses that natural flow.
Place the inlet behind the fan cover, leaving at least a few fingers of space in front of the grille. If the fan cover rests against the enclosure wall, the motor starves of air.
Put the outlet on the shaft side of the motor and in the upper part of the enclosure; if inlet and outlet sit side by side on the same wall, hot air goes straight back into the inlet.
Fit labyrinths or acoustically lined bends in the inlet and outlet ducts. A plain hole largely cancels the enclosure's sound insulation.
If an auxiliary fan is used, put it on the outlet; the enclosure stays at slight negative pressure and dust enters through the filtered inlet rather than the door gap.
If the duct cross-section is kept too small, air velocity rises, a whistle-like noise comes from the labyrinth bends, which means a new noise replaces the one the enclosure was meant to silence, and on top of that the pressure drop exceeds what the motor fan can deliver. The cross-section is chosen wide enough to pass the calculated airflow at low velocity.
The enclosure inlet goes on the fan cover side, with space left in front of the grille (representative image).
Prices and technical data are on the product pages; choose a model and order online.
How is the enclosure temperature verified on site?
Verification is done with the enclosure closed and after the motor has reached thermal equilibrium at full load. Two thermometers, a clamp meter and, if possible, an infrared thermometer are enough.
One thermometer stays outside the enclosure, the second inside, just in front of the fan cover inlet. After the motor has run under load for at least an hour, the difference between the two readings is noted; if it exceeds the value allowed in the calculation, ventilation is insufficient. At the same time motor current is logged and frame temperature is measured at the same point with the infrared thermometer.
A measurement taken with the door open misleads. The picture most often met on site: the door is left open during commissioning, everything looks normal, and a few weeks after the door is closed the thermal relay starts tripping.
The result is judged against the hottest hour of summer. An enclosure running with a 5 K difference in winter can push the motor close to its limit when outdoor temperature rises in summer. A July afternoon is what decides.
What are the common mistakes in enclosure design?
The most common mistake is designing the enclosure for sound insulation alone and thinking about ventilation later. The mistakes that follow mostly grow from the same root.
Leaving the fan cover a few centimetres from the enclosure wall; the fan finds no room to draw air.
Gluing acoustic foam close to the fan cover grille; over time the foam comes loose and blocks the grille.
Leaving the inlet filter out of the maintenance plan; a dust-filled filter effectively seals the enclosure.
Running the motor at low speed on a frequency converter without allowing for its own fan's airflow falling as well.
The last point deserves attention. When the motor slows, the air its own fan blows also falls; because airflow drops in proportion to speed, at 25 Hz it is roughly halved (general information). Our three-phase series are suitable for speed control with a drive; if full load is drawn at low speed for hours, a separately powered fan may be needed, and an output filter if the drive is far away. State these conditions with the order. A comparison of cooling methods is in the IC411 and IC416 cooling methods article.
What information should you give HEM when choosing a motor for an enclosed application?
In an enclosed application, the motor is chosen using the highest enclosure temperature. If the inside temperature will exceed 40 °C, a larger frame, a separate fan or derated operation is considered.
Information to send: machine power and speed, inside dimensions of the enclosure, the highest outdoor temperature, other heat sources sharing the enclosure with the motor, whether there is speed control, and the existing motor's nameplate. How to read the nameplate is explained on the find an equivalent motor from the nameplate page; for the first start of the new motor see the commissioning guide.
132S-4: 5.5 kW for small screw compressors; light aluminium frame, rated current 10.7 A, 36 Nm at 1460 rpm.
160M-4: the 11 kW aluminium frame step; draws 20.4 A, delivers 71.7 Nm at 1465 rpm.
160L-4: the 15 kW from the hypothetical calculation; cast iron frame, 27.3 A, 97.8 Nm at 1465 rpm.
Share your enclosure dimensions and temperature readings through our contact page; we will pick the right step from the product list together.
Frequently Asked Questions
Is a separate extract fan required for the motor in a sound enclosure?
Not always. If the airflow calculated from loss heat cannot be achieved by natural flow, an auxiliary fan is fitted on the outlet.
How warm may the inside of the enclosure get?
Most makers rate nameplate power for 40 °C cooling air. If the inside temperature will go above that, the frame is upsized or the motor is derated; the value is confirmed with the maker's documents.
How much space should be left between the fan cover and the enclosure wall?
The exact distance varies with frame size; dimensions are taken from the technical drawings. The general rule is to leave a free area from which the fan cover can draw air easily.
Can acoustic foam be wrapped over the motor?
No. Frame and fan cover must stay free; absorbing material goes on the enclosure walls and ducts.
HEM Motor Models Related to This Article
The cards show example models related to the topic. A suitable motor is not chosen by power alone: compare speed, voltage, mounting, shaft and connection dimensions on the product page; if unsure, send a photo of the existing motor’s nameplate on WhatsApp.
Checking that electric motor pulleys lie in the same plane means seeing whether the side faces of both pulleys meet on one straight line. In practice a taut string, a steel straigh... More Details
If an electric motor's coupling element fails often, the first thing to investigate is shaft misalignment, followed by coupling selection, starting and shock loads, environmental e... More Details
The quickest way to tell foundation looseness from unbalance in electric motor vibration is to loosen the foot bolts one at a time while measuring and watch the change, and to comp... More Details
In an electric motor running in a hot environment, winding and bearing temperatures are monitored separately because they heat up from different sources, have different limits and ... More Details
When an electric motor is started for the first time at sub-zero temperatures, three things need checking: winding insulation resistance and any moisture or ice inside, bearing gre... More Details
Under IEC 60034-1, the power on the nameplate is defined, unless stated otherwise, for an installation altitude of up to 1000 metres and air not exceeding 40 °C. Higher up the air ... More Details