How Is Power Assessed When an Electric Motor Is Used at High Altitude?

How Is Power Assessed When an Electric Motor Is Used at High Altitude?

Under IEC 60034-1, the power on the nameplate is defined, unless stated otherwise, for an installation altitude of up to 1000 metres and air not exceeding 40 °C. Higher up the air thins, the fan moves less mass at the same speed, and the winding heats more at the same shaft power. Above 1000 metres the motor is either used at reduced power or the next step up is chosen; the manufacturer's altitude-temperature table gives the ratio.

Why does altitude heat the motor?

The heat of a totally enclosed, externally fan-cooled motor is carried away by the air the fan blows along the frame fins. Air's capacity to carry heat is proportional to its density. As altitude increases, air pressure and density fall; even if the fan moves the same volume, the mass of air carried decreases.

Losses, however, do not change.

At the same shaft power the same heat is produced in the winding, the laminations and the bearings, but less of it is carried away; winding temperature rises as a result.

At high locations the ambient air is usually cooler, and this partly offsets the effect of thinner air. The standard offers an approach that takes this offset into account: at a given altitude, if ambient temperature is low enough, derating may not be needed (general information; confirm with the machine manufacturer).

What changes on the electrical side?

Thin air also has lower dielectric strength. In low-voltage motors this usually concerns not the winding but the clearances in the terminal box and the cable ends. On standard motors running at normal network voltage the practical effect is limited; even so, at very high altitudes the connections in the terminal box must be kept clean and tight, because flashover risk rises when moisture and dust combine.

On motors with a frequency converter, the converter itself is also affected by altitude and has its own derating table. Motor and drive must be checked separately. The two do not use the same table.

How is the derating calculation set up?

The calculation uses two inputs: installation altitude and the highest ambient temperature at that point. The manufacturer's table gives a factor where these two values intersect.

Ppermitted = Pnameplate × kaltitude/temperature

Thinking the other way round is more useful for selection: the shaft power the machine needs is divided by this factor, and the first nameplate power equal to or greater than the result is chosen.

Prequired nameplate ≥ Pshaft / kaltitude/temperature

Because the value of the factor varies with motor design, insulation class and cooling method, giving a general figure would be misleading. Values valid for HEM motors are confirmed with the order once installation altitude and ambient temperature are stated.

Hypothetical example: a mine conveyor at 2500 metres

Suppose a conveyor needs 17 kW shaft power by measurement, and the site is at 2500 metres with a summer shade temperature around 30 °C. Assume a factor of 0.88 is read from the manufacturer's table for this condition, as an example.

Required nameplate power comes out at 17 / 0.88 ≈ 19.3 kW. The 18.5 kW step is not enough; 22 kW is chosen. The same conveyor could run comfortably on an 18.5 kW motor at sea level; you can see the two steps side by side in the electric motor shop. Do not finalise this calculation without taking the factor from your own supplier's table. The difference looks small; its effect is not.

What is the point of class F insulation with class B temperature rise?

The insulation material tells you how much heat the winding will tolerate. The upper limit of class F insulation is above that of class B. Many standard motors are made with class F insulation and designed to stay within class B temperature rise at rated load.

The difference is a thermal margin. In situations such as a short overload, a hot afternoon or high altitude, this margin protects the winding.

Whether this margin can be used in the altitude calculation depends on the design and requires the manufacturer's approval. Pushing a motor at nameplate power at high altitude because "it is class F anyway" quietly shortens winding life. Insulation in the HEM series is class F; if a higher insulation level is needed, it should be discussed before ordering.

Large frame three-phase electric motor
At high altitude the frame fins see less air at the same fan speed; clean fins become even more important (representative image).

Prices and technical data are on the product pages; choose a model and order online.

How is the effect of high altitude monitored on site?

Monitoring a motor at high altitude during its first weeks shows at the lowest cost whether the calculation holds. A clamp meter, a non-contact thermometer and a notebook are enough.

  1. After the motor has run at full load for at least an hour, measure frame temperature each time at the same spot, usually under the terminal box.
  2. Note ambient temperature and the three phase currents at the same time. If the frame heats noticeably as current approaches the nameplate value, derating may have been insufficient.
  3. Repeat the measurement at midday and in a position facing the sun directly; at high locations solar radiation heats the frame additionally.
  4. Make sure the fan cover grille and fins are clean; on dusty mining and quarry sites this matters as much as altitude.

If the overload relay trips often, changing the setting should not be the first idea. The relay may be telling you the motor really is hot; raising the setting above nameplate current hands the problem to the winding. Writing the trip times next to ambient temperature often clears up the picture: if trips cluster in the afternoon, the cause is most likely heat.

Another long-term sign to watch is the yearly trend of winding insulation resistance. A steady fall in the megger reading taken each year under the same conditions shows the winding is ageing thermally.

Which HEM models can be considered for high altitude?

Around the hypothetical 2500-metre conveyor example, three 4-pole cast iron frame steps:

  • 160L-4: 15 kW, 1465 rpm, 27.3 A at 400 V, 97.8 Nm; for jobs needing 15 kW at sea level, and for smaller loads at high altitude.
  • 180L-4: 22 kW, 1470 rpm, 39.7 A at 400 V, 142.9 Nm; the step chosen after derating in the example calculation.
  • 200L-4: 30 kW, 1475 rpm, 53.8 A at 400 V, 194.2 Nm; for the same load at higher altitude or in a hotter environment.

A cast iron frame helps heat spread along the fins; the whole family is on the cast iron electric motors page. The series is IP55 protected, insulation class F and carries CE marking. It is offered in IE3, IE4 and IE5 efficiency classes; which class your chosen model comes in is settled with the order. When ordering a new motor, remember to add installation altitude and highest ambient temperature to the information to give when requesting a quote; for first start-up steps see the commissioning checklist.

Send the installation altitude, ambient temperature and the machine's shaft power together with a nameplate photo of the existing motor through our contact page; we will determine the right step for the altitude together. All options are in the HEM Motor product list.

Frequently Asked Questions

Is an altitude calculation needed below 1000 metres?

Usually not, as long as ambient temperature does not exceed 40 °C. Below 1000 metres, if temperature is high, temperature derating is assessed separately.

Does driving the motor with a frequency converter solve the problem at high altitude?

It does not; the converter is also affected by altitude and has its own derating table. Because the fan's airflow falls further at low speed, a separate fan is considered if necessary.

How should I give altitude information on the order?

Write the height of the installation site above sea level in metres, the ambient temperature of the hottest period and whether the motor will run outdoors or indoors.

At high altitude, is it possible to improve cooling instead of increasing motor power?

Solutions such as a separate fan can be considered in some applications. Whether this is suitable should be assessed with the manufacturer; in most cases the next step up is the simpler solution.

HEM Motor Models Related to This Article

The cards show example models related to the topic. A suitable motor is not chosen by power alone: compare speed, voltage, mounting, shaft and connection dimensions on the product page; if unsure, send a photo of the existing motor’s nameplate on WhatsApp.

15 kW 1500 rpm Cast Iron Frame Electric Motor 160L-4

160L-4

15 kW · 1500 rpm

  • Cast iron frame · IEC 160L
  • 1465 rpm · IP55
  • Mounting: B3 foot; flange (B5/B14/B35) depending on frame, confirmed with the order

US$665.08 (€608.69)

View product
22 kW 1500 rpm Cast Iron Frame Electric Motor 180L-4

180L-4

22 kW · 1500 rpm

  • Cast iron frame · IEC 180L
  • 1470 rpm · IP55
  • Mounting: B3 foot; flange (B5/B14/B35) depending on frame, confirmed with the order

US$901.75 (€825.30)

View product
30 kW 1500 rpm Cast Iron Frame Electric Motor 200L-4

200L-4

30 kW · 1500 rpm

  • Cast iron frame · IEC 200L
  • 1475 rpm · IP55
  • Mounting: B3 foot; flange (B5/B14/B35) depending on frame, confirmed with the order

US$1,211.23 (€1,108.54)

View product

Similar Articles