A burnt winding often carries the cause of the failure on itself: with phase loss one or two phase groups darken while the others stay intact, with overload all three phases darken evenly, and with a voltage surge the damage is concentrated in a small area, usually in the first turns near the supply end. Once these three patterns can be told apart, it also becomes clear what must be corrected on the panel side before fitting a new electric motor. Below we explain how to read each pattern, which measurement confirms it and the interpretation mistakes commonly made on site.
Where should you look first on a dismantled stator?
When the motor arrives at the workshop, the terminal box should be photographed before the end shields are opened and the rotor is pulled: the position of the links shows whether it was connected in star or delta, and discoloration of the cables shows whether the problem started at the connection. The end windings are then examined by the three phase groups. What matters is not so much the colour itself as its distribution: is a single area affected, certain phase groups, or the whole circumference?
The rotor also holds clues. Bluish discoloration of the rotor bars or melting marks on the cage ring show that the motor turned for a long time locked or with very high slip. If there are rubbing marks in the bearing housings, the possibility that the rotor touched the stator and the winding damage began for a mechanical reason also comes onto the table.
What trace does phase loss leave on the winding?
With phase loss, one or two phase groups darken depending on the connection. The others stay intact. If one phase is lost while the motor is running, the remaining two phases continue to carry the load and the current rises noticeably. In a star-connected winding two phase groups overheat; the typical picture is two of the three phase groups darkened and one almost clean. In a delta-connected winding the phase winding connected between the two healthy lines carries the highest current, so usually a single phase group appears clearly burnt (general knowledge; confirm with the rewinding workshop's assessment).
The source of phase loss is mostly outside the motor: a single blown fuse, a burnt contact in the contactor, a loose terminal or a broken cable. So before fitting the new motor, check the fuses, contactor contacts and all terminals. A motor protection relay or thermal relay that is sensitive to phase loss prevents this fault from recurring; the logic of sizing the protective device is explained step by step in our motor protection guide.
Why do all three phases darken under overload?
When the motor runs continuously above its nameplate current, heat is distributed equally across the three phases. The result is that all end windings darken to the same shade, the enamel becomes brittle and the varnish turns brown; there is no distinct hot spot. This pattern shows that the problem lies in the load or cooling, not in the supply.
A rule often used on site describes the effect of heat on insulation life: for every 10 °C the winding temperature rises above the class limit, insulation life is roughly halved (general knowledge; confirm with the insulation manufacturer's data). That is why not only short events but small overloads lasting weeks quietly consume the winding. A clogged fan cowl, a hot machine room or repeated frequent starts produce the same pattern.
Telling a locked rotor from overload
If power is applied while the rotor is fully locked, the current stays at starting current level and the winding burns within seconds to a few minutes. The pattern is again equal across all three phases, but the colour is much darker, even charred, and discoloration is seen on the rotor bars. Overload leaves a lighter and more uniform darkening; the rotor usually looks normal.
What damage does a voltage surge leave on the winding?
A voltage surge leaves small, local damage. Lightning, switching of power factor correction steps or switching events in the network produce short, steep-fronted voltage surges. Such a surge is not distributed evenly over the whole winding; the largest voltage difference appears between the first few turns closest to the supply end. The result is a small puncture or turn-to-turn short at a slot exit or in the first coil, while the rest of the winding is clean.
A similar trace can appear on motors driven by a frequency converter. Our three-phase series are suitable for speed control with a frequency converter; for long periods at low speed with full torque, a separate fan may be required; if the drive-to-motor cable is long, a dv/dt or sine filter is considered; these conditions are stated in the order. On a motor showing local damage, cable length and filter status must always be questioned.
| Burn pattern | Probable cause | Check on the panel side |
|---|---|---|
| Two phase groups dark in star connection | Phase loss | Fuses, contactor contacts, terminals |
| One phase group dark in delta connection | Phase loss | Same checks, phase loss protection |
| All three phases evenly and lightly darkened | Continuous overload or poor cooling | Load current, fan cowl, ambient temperature |
| All three phases very dark, rotor discoloured | Locked rotor | Mechanical jamming, protection setting |
| One phase slightly darker than the others | Voltage unbalance | Phase-to-phase voltages |
| Small local puncture in the first turns | Voltage surge | Surge arrester, cable length, filter |