What Should Be Examined If an Electric Motor Trips the Fuse Only Under Load?

What Should Be Examined If an Electric Motor Trips the Fuse Only Under Load?

If an electric motor runs normally on no load and trips its fuse only when load is applied, the fault is most likely not in the winding; either the motor really is going above rated current, or the protective device is wrongly selected or wrongly set for that current. The investigation starts by measuring the three phase currents and voltages at the same time under load.

Why does a motor that runs fine on no load trip its protection under load?

On no load the motor draws a small part of its rated current; as load is applied, current rises and approaches the protective device's threshold at that moment. A motor that looks healthy on no load therefore reveals the fault only under load.

Three different root causes can produce the same picture. The first is genuine overload: the driven machine demands more torque than the motor can carry. The second is a supply problem: voltage is low or unbalanced, so the motor delivers the same power with more current. The third lies on the protection side: thermal relay setting, fuse characteristic or contactor contact shows current as higher than it is, or heats up.

A winding fault can also become evident under load, but it usually leaves a trace on no load too, such as current imbalance or a smell.

Which device is tripping: fuse, thermal relay or residual current device?

Knowing which device trips is half the way to the cause. Look at the panel before reaching for a meter.

Tripping deviceHow it tripsFirst cause to consider
Thermal relayAfter minutes, once the motor warms upContinuous overload, low voltage, wrong setting, phase loss
Magnetic part of the motor protection breakerInstantly, mostly at start or on a sudden load shockJammed mechanism, inter-turn short, characteristic mismatch
Blade or miniature fuseOne phase opens, the motor is left on two phasesPeak current under load, heating at a loose connection
Residual current deviceWhen load is applied or in damp weatherWeakened insulation, cable damage, drive filter leakage

The "trip" indicator on the thermal relay, the lever position on the breaker and a blown element in the fuse are the first places to look. If one phase fuse has blown and the motor keeps running, it turns on two phases, its sound deepens and the thermal relay opens within a few minutes.

Which measurements should be taken under load, and in what order?

Current and voltage first, then speed and temperature. All are taken with the machine at its real load, as close as possible to the moment of tripping.

  1. At the contactor output, read the three phase currents one by one with a True-RMS clamp meter; compare them with the rated current on the nameplate.
  2. At the same time, measure the three line voltages at the motor terminals. A clear difference between the panel input and the terminals means the cable or a connection is heating up.
  3. If a thermal camera is available, look at the fuse holders, contactor contacts and terminal screws. One connection point looking hotter than the others means a loose or oxidised contact.
  4. Read shaft speed with an optical tachometer. If speed is below the rated nameplate value, the motor is straining under load.
  5. Note the setting and class of the thermal relay and write them next to the rated current from the nameplate.

If one person takes the readings alone, a clamp meter with current logging makes the job easier. The current curve of the few minutes before the trip shows whether load grows steadily or in sudden shocks.

Prices and technical data are on the product pages; choose a model and order online.

What cause do the measurement results point to?

If the three phase currents are balanced and above rated, the problem is the mechanical load; if they are unbalanced, the supply or the winding is examined; if the protection trips while current is below rated, the protective device itself is questioned.

Common findings on the mechanical side: a conveyor drum with a seized bearing, a fan with an over-tensioned belt, a centrifugal pump whose flow has risen above design, oversized material fed to a crusher. Removing the coupling and turning the driven machine by hand is the quickest way to feel a bind.

On the voltage side, even a small imbalance between line voltages creates a much larger imbalance in currents (general information; confirm with the machine manufacturer). If voltage drops when a large load on the same line switches on during the day, the trips coincide with those hours.

If tripping happens while current is below rated, check whether the thermal relay is set to the nameplate rated current, the relay class and the ambient temperature inside the panel. In a panel exposed to sunlight, a thermal relay can open early even when the motor is cool.

If the residual current device trips, winding-to-frame insulation resistance is measured with a megger. The test should be done separately on the motor side and the cable side; otherwise a crushed cable looks like the motor's fault.

Side view of a foot-mounted three-phase electric motor and terminal box
Voltage under load is measured at the motor terminals, not at the panel input (representative image).

Why is increasing the fuse or thermal setting not a solution?

Enlarging the protective device does not remove the cause; it only weakens protection of the motor and cable. If the real reason for tripping is the load or the supply, the motor pays with its winding this time instead of the fuse.

Protection is chosen by calculation. Cable cross-section, fuse type and rating are determined by the project or panel engineer from the motor's rated current, starting method and duration, cable length, installation method and ambient temperature, and approved according to the electrical regulations in force. The thermal relay is set to the rated current on the nameplate. A decision to "fit the next size up" should not replace a calculation made with this information.

To see in detail which protective device acts on which fault, the article on thermal relay, fuse and motor protection breaker explains the distinction step by step.

How do you decide whether the motor is too small for its job?

If current is still above rated after maintenance has been corrected and voltage and connections have been verified, the motor is too small for its job. In that case one power step up is assessed together with the torque and speed required by the machine manufacturer.

Information needed for the decision: current and voltage measured under load, power, speed and frame on the nameplate, whether starting is direct, star-delta or by drive, and daily running hours. Because the frame may also grow at the next step, mounting fit is checked separately: the IEC frame number is the first piece of compatibility information; exact fit is confirmed by comparing mounting type, shaft diameter and length, foot hole spacing, flange and electrical ratings. Frame dimensions and power steps can be seen product by product in the electric motor shop.

As an example, three consecutive steps in the 4-pole cast iron series:

  • 132S-4: 5.5 kW, 1460 rpm, 10.7 A at 400 V, rated torque 36 Nm.
  • 132M-4: 7.5 kW, 1460 rpm, 14.3 A at 400 V, rated torque 49.1 Nm. The next step up, staying in the same 132 frame.
  • 160M-4: 11 kW, 1465 rpm, 20.4 A at 400 V, rated torque 71.7 Nm. The frame rises to 160; foot and shaft dimensions change.

These steps belong to the three-phase asynchronous electric motors family and come with IP55 and Class F insulation. To find the equivalent of the existing motor from its nameplate, the equivalent motor table can be used.

If you share the current and voltage values taken under load, the type of device that trips and a photo of the motor nameplate through our contact page, we can work out together whether the problem lies in the load or the motor and, if needed, select a suitable step from the product list.

Frequently Asked Questions

What should be checked if the motor runs normally in the morning but trips in the afternoon?

Voltage drop during the day and temperature inside the panel are checked. Large loads switching on the same line in the afternoon can lower voltage and raise current; in a sunlit panel the thermal relay also opens early.

Current is at rated value but the thermal relay still trips; is the relay faulty?

It may be, but first the setting, relay class and balance of the three phases are checked. If one phase is higher than the others, the relay is opening because of that phase.

What could cause tripping at the changeover moment of a star-delta start?

If changeover time is too short, the motor switches to delta before accelerating and draws high current. The timer setting and the starting time under load are checked.

If the residual current device trips only under load, is the motor faulty?

Not necessarily. Winding and cable insulation resistance are measured separately; if a frequency inverter is used, the leakage current of the drive filter is also taken into account.

HEM Motor Models Related to This Article

The cards show example models related to the topic. A suitable motor is not chosen by power alone: compare speed, voltage, mounting, shaft and connection dimensions on the product page; if unsure, send a photo of the existing motor’s nameplate on WhatsApp.

5.5 kW 1500 rpm Cast Iron Frame Electric Motor 132S-4

132S-4

5.5 kW · 1500 rpm

  • Cast iron frame · IEC 132S
  • 1460 rpm · IP55
  • Mounting: B3 foot; flange (B5/B14/B35) depending on frame, confirmed with the order

US$335.43 (€306.99)

View product
7.5 kW 1500 rpm Cast Iron Frame Electric Motor 132M-4

132M-4

7.5 kW · 1500 rpm

  • Cast iron frame · IEC 132M
  • 1460 rpm · IP55
  • Mounting: B3 foot; flange (B5/B14/B35) depending on frame, confirmed with the order

US$387.29 (€354.46)

View product
11 kW 1500 rpm Cast Iron Frame Electric Motor 160M-4

160M-4

11 kW · 1500 rpm

  • Cast iron frame · IEC 160M
  • 1465 rpm · IP55
  • Mounting: B3 foot; flange (B5/B14/B35) depending on frame, confirmed with the order

US$557.82 (€510.52)

View product

Similar Articles