If one connection point in the terminal box of an electric motor looks clearly hotter than the other phases on a thermal image, the most likely cause is increased contact resistance at that point: a loosened nut, a poorly crimped cable lug or an oxidised surface. In the terminal box, absolute temperature on its own says little; the real information is the temperature difference between the three phase connections under the same load. If this difference is measured under the right conditions and interpreted with a load correction, the fault is caught before the connection burns and the motor drops into single phasing.
Why does a terminal connection heat up?
The heat released at a connection point is the square of the current multiplied by the contact resistance:
P = I² × Rcontact
Hypothetical example: if a sound connection carrying 40 A has a contact resistance of 0.5 mΩ, about 0.8 W of heat is produced at the point and easily dissipated through the copper stud and the cable. If the nut loosens and the resistance rises to 5 mΩ, the loss at the same current becomes 8 W. Because this power is concentrated on a surface of a few square centimetres, the lug, terminal stud and the end of the cable insulation heat up quickly.
A heated connection accelerates oxidation, and the oxide raises the resistance further; the process feeds itself. In the end the terminal board chars, the lug melts or the connection opens completely and the motor is left on two phases. Thermal imaging lets you see the early link in this chain.
What should be prepared before a thermography measurement?
Load, safety and emissivity setting should be prepared in advance. Terminal box thermography is meaningful with the motor under load; at no load or very light load even a loose connection can look sound. Read the current in each phase with a clamp meter at the time of measurement and note it. The motor should have run for at least half an hour, preferably long enough for temperatures to stabilise.
An open terminal box contains live parts. Opening the cover while energised must be done only by authorised personnel with suitable personal protective equipment, in line with the plant's electrical safety instructions. If this is not possible, an image taken from outside the cover and at the cable gland is assessed together with a quick measurement made just after the cover is opened, once the motor has been stopped and isolated.
Bright copper and brass surfaces have low emissivity; the camera shows them colder than they really are and may pick up reflections from hot objects nearby. Make the comparison on high-emissivity surfaces such as the lug barrel, the cable insulation or the terminal board. The camera's emissivity and reflected temperature settings must be entered according to the manufacturer's instructions.
What should you look for in the thermal image?
Look at the temperature difference between the phases. Because the terminal box sits on top of the motor frame, it is already warm; winding heat rises through the frame and the base of the box. So the question "the terminal is at 60 °C, is that high?" has no answer on its own. The right question is: if the U, V and W connections carry the same current, why is one hotter than the others?
Three patterns can be distinguished in the image. If a single connection point is hot while its cable and the other points are normal, the problem is the contact at that point. If one phase's cable is hot along its whole length, that phase may be drawing more current; confirm this with a clamp meter, the cause may be supply voltage imbalance or a winding problem. If the whole terminal box and all cables are equally warm, it is not a local connection fault; load, ambient temperature or cable sizing should be reviewed.
The studs under the star or delta links are also checked. If a link nut is loose, two studs heat up together and the image can be misread as two separate faults.

How is a difference measured at low load corrected?
The difference is scaled up by the square of the current ratio. Measurement cannot always be made at full load. Since heating changes roughly with the square of the current, a temperature rise measured at low load can be carried over to full load as follows:
ΔTfull ≈ ΔTmeasured × (Irated / Imeasured)²
Hypothetical example: a motor with a rated current of 39.7 A is drawing 20 A at the time of measurement, and the V phase connection is 6 °C hotter than the others. At full load this difference could rise to about 6 × (39.7 / 20)² ≈ 24 °C. This is an estimate; in real behaviour the exponent may be slightly below 2, and convection and ambient temperature also affect the result (general information; confirm with the instrument manufacturer's instructions). Correcting a measurement taken at very low load also magnifies the error; if possible, repeat the measurement at higher load.