Terminal Box Temperature of an Electric Motor in Thermal Imaging

Terminal Box Temperature of an Electric Motor in Thermal Imaging

If one connection point in the terminal box of an electric motor looks clearly hotter than the other phases on a thermal image, the most likely cause is increased contact resistance at that point: a loosened nut, a poorly crimped cable lug or an oxidised surface. In the terminal box, absolute temperature on its own says little; the real information is the temperature difference between the three phase connections under the same load. If this difference is measured under the right conditions and interpreted with a load correction, the fault is caught before the connection burns and the motor drops into single phasing.

Why does a terminal connection heat up?

The heat released at a connection point is the square of the current multiplied by the contact resistance:

P = I² × Rcontact

Hypothetical example: if a sound connection carrying 40 A has a contact resistance of 0.5 mΩ, about 0.8 W of heat is produced at the point and easily dissipated through the copper stud and the cable. If the nut loosens and the resistance rises to 5 mΩ, the loss at the same current becomes 8 W. Because this power is concentrated on a surface of a few square centimetres, the lug, terminal stud and the end of the cable insulation heat up quickly.

A heated connection accelerates oxidation, and the oxide raises the resistance further; the process feeds itself. In the end the terminal board chars, the lug melts or the connection opens completely and the motor is left on two phases. Thermal imaging lets you see the early link in this chain.

What should be prepared before a thermography measurement?

Load, safety and emissivity setting should be prepared in advance. Terminal box thermography is meaningful with the motor under load; at no load or very light load even a loose connection can look sound. Read the current in each phase with a clamp meter at the time of measurement and note it. The motor should have run for at least half an hour, preferably long enough for temperatures to stabilise.

An open terminal box contains live parts. Opening the cover while energised must be done only by authorised personnel with suitable personal protective equipment, in line with the plant's electrical safety instructions. If this is not possible, an image taken from outside the cover and at the cable gland is assessed together with a quick measurement made just after the cover is opened, once the motor has been stopped and isolated.

Bright copper and brass surfaces have low emissivity; the camera shows them colder than they really are and may pick up reflections from hot objects nearby. Make the comparison on high-emissivity surfaces such as the lug barrel, the cable insulation or the terminal board. The camera's emissivity and reflected temperature settings must be entered according to the manufacturer's instructions.

What should you look for in the thermal image?

Look at the temperature difference between the phases. Because the terminal box sits on top of the motor frame, it is already warm; winding heat rises through the frame and the base of the box. So the question "the terminal is at 60 °C, is that high?" has no answer on its own. The right question is: if the U, V and W connections carry the same current, why is one hotter than the others?

Three patterns can be distinguished in the image. If a single connection point is hot while its cable and the other points are normal, the problem is the contact at that point. If one phase's cable is hot along its whole length, that phase may be drawing more current; confirm this with a clamp meter, the cause may be supply voltage imbalance or a winding problem. If the whole terminal box and all cables are equally warm, it is not a local connection fault; load, ambient temperature or cable sizing should be reviewed.

The studs under the star or delta links are also checked. If a link nut is loose, two studs heat up together and the image can be misread as two separate faults.

Close-up of a foot-mounted three-phase electric motor showing the terminal box
Because the terminal box sits on the frame it also carries winding heat; interpretation is based on the phase-to-phase difference (representative image).

How is a difference measured at low load corrected?

The difference is scaled up by the square of the current ratio. Measurement cannot always be made at full load. Since heating changes roughly with the square of the current, a temperature rise measured at low load can be carried over to full load as follows:

ΔTfull ≈ ΔTmeasured × (Irated / Imeasured)²

Hypothetical example: a motor with a rated current of 39.7 A is drawing 20 A at the time of measurement, and the V phase connection is 6 °C hotter than the others. At full load this difference could rise to about 6 × (39.7 / 20)² ≈ 24 °C. This is an estimate; in real behaviour the exponent may be slightly below 2, and convection and ambient temperature also affect the result (general information; confirm with the instrument manufacturer's instructions). Correcting a measurement taken at very low load also magnifies the error; if possible, repeat the measurement at higher load.

Prices and technical data are on the product pages; choose a model and order online.

What should be done about a hot terminal point?

The step is chosen by the size of the phase-to-phase difference. Exact thresholds should be taken from the thermography guideline your organisation has adopted. The table below is a qualitative ranking used on site, based on the phase-to-phase difference.

Condition in the imageLikely causeRecommended step
Small difference at one pointBeginning of loosening, surface dirtTighten and clean at the next planned stop, measure again
Clear difference at one pointLoose nut, poorly crimped lugPlan a stop soon, inspect lug and stud
Large difference at one point, discolorationAdvanced contact fault, board damageStop as soon as possible, replace parts
One phase's cable hot along its lengthHigh phase current, voltage imbalanceMeasure current and phase-to-phase voltages, check winding
Whole box and cables equally warmHigh load, hot ambient, cable sizeReview load and cable calculation

How is a hot spot on the terminal cleared?

Simply tightening a connection found loose is often not enough. In a heated lug the copper may have softened and the surface oxidised; even if the nut is tightened, the contact area is not what it was. Cut off a discoloured lug and crimp a new one, clean or replace the stud and washers, and renew the terminal board if it shows cracks or carbon tracks.

The lug must match the cable cross-section and be crimped with the correct die; the cable cross-section and protective device rating are calculated by the panel engineer from the motor current, cable length, installation method and ambient temperature. If aluminium cable is used, a suitable bimetallic lug must be used for the transition to the copper stud. The nut is tightened to the terminal manufacturer's torque value; too much torque can snap the stud or crack the board.

On vibrating machines loosening recurs. Here, spring washers or locking nuts, and cable that enters the terminal box without tension and is secured at the gland, are important. If cable weight or vibration bears directly on the lug, a tightened connection will loosen again within a few weeks.

If the terminal fault recurs, should the electric motor be replaced?

If a hot spot keeps recurring on the same phase of the same motor, the problem may not be the connection alone. If the terminal board has deformed from heat, the winding lead has been damaged inside the box, or the motor draws more current through one of the phases, the motor should be inspected in the workshop or replaced. For comparison, options by power and speed are listed in the electric motor shop; alternatives for the same supply are gathered on the asynchronous electric motors page.

Hypothetical pairings: for 4 kW on a conveyor or mixer, the aluminium-frame 112M-4 (1450 rpm, 7.95 A); matching the load correction example above, the 22 kW cast iron 180L-4 (1470 rpm, 39.7 A); and for a larger pump or fan, the 55 kW 250M-4 (1485 rpm, 97.6 A, 400/690 V). Rated currents can be used as the reference in thermography load correction; for other powers see the current table.

When a new motor is fitted, checking the terminal connection once with thermography under first load is a good habit; this step can be added to the commissioning checklist. If you share your thermography report and a photo of the motor nameplate via the find an equivalent from the nameplate page, we will determine the counterpart in the same frame together if a change is needed; all models are also in the HEM Motor product list.

Frequently Asked Questions

Is thermography useful with the terminal box cover closed?

An image from outside the cover can only show very advanced heating or a hot cable at the gland. Early diagnosis requires a direct view of the connection points; the safe way to do this must be set by the plant's electrical safety instructions.

If all three phases are equally warm, are the connections sound?

Equality shows there is no local contact fault, but if all are high it may point to overload, hot ambient or cable sizing. Measure the current and compare it with the nameplate value.

A bright copper stud looks cold in the image; why?

Bright metals have low emissivity and the camera shows them colder than they are. Make the comparison on matt surfaces such as the lug barrel or cable insulation.

Is the terminal hotter on a motor driven by a frequency converter?

Harmonics at the drive output can cause extra heating in cables and connections. Interpretation still rests on the phase-to-phase difference; if there is a clear difference between the three phases, the cause is still sought in the connection.

HEM Motor Models Related to This Article

The cards show example models related to the topic. A suitable motor is not chosen by power alone: compare speed, voltage, mounting, shaft and connection dimensions on the product page; if unsure, send a photo of the existing motor’s nameplate on WhatsApp.

4 kW 1500 rpm Aluminium Frame Electric Motor 112M-4

112M-4

4 kW · 1500 rpm

  • Aluminium frame · IEC 112M
  • 1450 rpm · IP55
  • Mounting: B3 foot; flange (B5/B14/B35) depending on frame, confirmed with the order

US$238.15 (€217.96)

View product
22 kW 1500 rpm Cast Iron Frame Electric Motor 180L-4

180L-4

22 kW · 1500 rpm

  • Cast iron frame · IEC 180L
  • 1470 rpm · IP55
  • Mounting: B3 foot; flange (B5/B14/B35) depending on frame, confirmed with the order

US$901.75 (€825.30)

View product
55 kW 1500 rpm Cast Iron Frame Electric Motor 250M-4

250M-4

55 kW · 1500 rpm

  • Cast iron frame · IEC 250M
  • 1485 rpm · IP55
  • Mounting: B3 foot; flange (B5/B14/B35) depending on frame, confirmed with the order

US$2,025.96 (€1,854.20)

View product

Similar Articles