Surge Protection for an Electric Motor Against Lightning and Supply Transients

Surge Protection for an Electric Motor Against Lightning and Supply Transients

To protect an electric motor against lightning and supply surges, surge protective devices (SPDs) are installed in stages from the main distribution board down to the motor feeder panel, so that the surge is diverted to earth before it reaches the motor. The winding of an induction motor withstands slowly changing voltage well, but a steep-fronted surge lasting microseconds piles up on the first turns and punctures the enamel. A correctly selected SPD with short connections reduces this surge to a level the motor insulation can carry.

How does surge voltage damage the motor winding?

Lightning striking an overhead line or a nearby point, switching of large loads, capacitor bank stages coming in and reclosing after a fuse blows all create short but high-amplitude voltage surges in the supply. The rise time of these surges is very short; in the motor winding the voltage is not shared equally across all turns but concentrates in the first coils and even the first few turns.

As a result, a motor that shows no problem in an insulation resistance measurement can burn out from an inter-turn short circuit.

This fault often appears a few days after a stormy night, under load, so the link between surge and burnout is easily missed. Field irrigation pumps, well and booster stations fed by long overhead lines, and conveyors in open areas are the installations most exposed to this risk.

What SPD types exist and how is staged protection built?

Low-voltage SPDs are divided into test classes in the IEC 61643 family. The classification used on site is as follows:

  • Type 1: where direct lightning current may enter the building, usually in the main board of structures with an external lightning protection system. It has a high impulse current capacity.
  • Type 2: in distribution and sub-distribution boards, against induced and switching surges. It is the type most often seen in motor feeder panels.
  • Type 3: fine protection right next to sensitive equipment; on the motor side it is used for drive control supplies or sensor circuits.

A single SPD does not solve everything. The device in the main board takes most of the surge, and the device in the sub-board brings the remainder down to a level the motor can withstand. For coordination between stages, manufacturers recommend a certain cable distance or a coordination element; these values are taken from the device catalogue.

How are Uc, Up, In and Iimp read when choosing an SPD?

An SPD label carries four basic quantities. Uc (maximum continuous operating voltage) keeps the device from conducting during normal and temporary rises of the supply; it is chosen according to the earthing system (TN, TT, IT) and the phase-to-neutral voltage. Up (voltage protection level) is the voltage remaining across the device during a surge; smaller is better. In (nominal discharge current) and Iimp (impulse current, for Type 1) show how much energy the device can carry repeatedly.

The value that really protects the motor is Up plus the additional voltage developed in the connecting leads. This total must stay below the impulse withstand voltage of the motor and the other devices in the panel. Suitable values are set by the project engineer who knows the earthing system and the lightning risk assessment (general information; confirm with the SPD manufacturer's selection table).

Why should the SPD connection leads be kept short?

Because surge current changes very quickly, the SPD's connecting leads create an inductive voltage drop:

ΔU = L × (di/dt)

In practice an inductance of about 1 µH per metre is assumed for a straight conductor (general information; it varies with cable layout). Hypothetical example: for a 10 kA surge current with an 8/20 µs waveform, the average rate of current change is roughly 1.25 kA/µs. If the connection between the SPD, the busbar and earth is 0.5 m longer in total, the extra voltage is 0.5 µH × 1.25 kA/µs ≈ 0.6 kV.

This 0.6 kV adds to the device's Up, and the surge seen by the motor turns out clearly higher than expected. SPD connections should therefore be as short and straight as possible without forming loops, with the phase and earth conductors run close together.

A V-type (through) connection, where suitable, reduces the effect of lead length.

Electric motor driving an irrigation pump in open country
Field pumps fed by long overhead lines are among the installations most exposed to lightning-induced surges (representative image).

Prices and technical data are on the product pages; choose a model and order online.

Placing SPDs in the motor panel step by step

  1. Start with the risk: determine whether the site is fed by overhead line or underground cable, whether there is external lightning protection, and whether the motor is in an open area.
  2. Identify the earthing system, then choose the SPD connection scheme and Uc value according to a TN-C, TN-S, TT or IT system.
  3. Plan the stages. Install Type 1 or Type 1+2 in the main board and Type 2 in the motor feeder panel; check the distance between panels for coordination.
  4. Install a fuse or circuit breaker ahead of the SPD not exceeding the maximum value stated by the manufacturer; the panel engineer sets the rating from the prospective short-circuit power and the device data.
  5. Keep phase–SPD–earth connections short and straight and bond them to the equipotential busbar.
  6. Make the SPD status indicator or remote signalling contact readable from the panel door or connect it to the automation system; add it to the post-storm checklist.

Attention with long motor cables and frequency converter systems

If the cable between panel and motor is very long (for example a well pump hundreds of metres away), the SPD in the panel may not fully limit the surge at the motor terminals; the cable itself can carry and reflect the surge. In that case additional protection near the terminal box on the motor side is considered, and the motor frame earth is joined to the panel earth with a good equipotential bond.

In systems with a frequency converter, the SPD is placed at the drive's supply input. The fast voltage pulses at the drive output are not an SPD matter; our three-phase series are suitable for speed control with a frequency converter; for long periods of full-torque operation at low speed a separate fan may be needed; if the drive–motor cable is long, a dv/dt or sine filter is considered; these conditions are stated in the order.

When is an SPD replaced and what is checked after a storm?

The varistor inside an SPD ages a little with every surge. If the status window has turned red or the signalling contact has opened, the module must be replaced at once; otherwise the panel is left unprotected. In the post-storm check, the trip records of the motor protection relay, the motor's insulation resistance and, if possible, a surge test are also assessed.

For the selection of protection relays, thermal overloads and motor protection circuit breakers, see our motor protection article. Clarifying at project stage which data the SPD and protective device ratings are based on is cheaper than making changes later.

Choosing an electric motor for surge-exposed sites

At open sites fed by long lines, it also matters that the motor itself has a good insulation margin, a sturdy frame and a well-sealed terminal box. HEM Motor's standard series comes with IP55 and class F insulation, with a PTC winding sensor as an order option; models by power and speed are listed in the electric motor shop. The complete three-phase family is on the asynchronous electric motors page.

Hypothetical pairings: for a small drip irrigation pump, the aluminium-frame 5.5 kW 132S-4 (1460 rpm); for a booster pump fed by an overhead line, the cast iron 18.5 kW 180M-4 (1470 rpm); and for a large irrigation association station, the 75 kW 280S-4 (1486 rpm, 400/690 V). Checking SPD status when a new motor is commissioned can be added to the commissioning checklist.

To determine the model to replace a motor that burned out after a storm, send the nameplate photo, the type of supply line and the panel details via the find an equivalent from the nameplate page; we will assess the motor and the protection conditions together. Other powers are in the HEM Motor product list.

Frequently Asked Questions

Does a factory fed by underground cable need SPDs?

The risk is lower than with an overhead line, but switching surges and voltages induced by nearby lightning still occur. Type 2 protection in the main and sub-boards is usually considered sufficient; the decision is made with a risk assessment.

Why did the motor burn out even though there was an SPD?

The most common causes are higher residual voltage due to long connecting leads, a module at the end of its life, a very long cable from panel to motor, or poor earthing. Lead length and module status are the first points to check.

How often should an SPD be replaced?

There is no fixed period; its life depends on the number and size of surges it has taken. The status indicator is checked regularly, and the module is renewed immediately when the indicator shows a fault.

Can an SPD be fitted in the motor terminal box?

In applications with very long cables, extra protection on the motor side is considered. However, as space, sealing and lead length are limited inside the terminal box, a separate enclosure near the motor is usually preferred.

HEM Motor Models Related to This Article

The cards show example models related to the topic. A suitable motor is not chosen by power alone: compare speed, voltage, mounting, shaft and connection dimensions on the product page; if unsure, send a photo of the existing motor’s nameplate on WhatsApp.

5.5 kW 1500 rpm Aluminium Frame Electric Motor 132S-4

132S-4

5.5 kW · 1500 rpm

  • Aluminium frame · IEC 132S
  • 1460 rpm · IP55
  • Mounting: B3 foot; flange (B5/B14/B35) depending on frame, confirmed with the order

US$320.18 (€293.04)

View product
18.5 kW 1500 rpm Cast Iron Frame Electric Motor 180M-4

180M-4

18.5 kW · 1500 rpm

  • Cast iron frame · IEC 180M
  • 1470 rpm · IP55
  • Mounting: B3 foot; flange (B5/B14/B35) depending on frame, confirmed with the order

US$856.68 (€784.05)

View product
75 kW 1500 rpm Cast Iron Frame Electric Motor 280S-4

280S-4

75 kW · 1500 rpm

  • Cast iron frame · IEC 280S
  • 1486 rpm · IP55
  • Mounting: B3 foot; flange (B5/B14/B35) depending on frame, confirmed with the order

US$2,860.77 (€2,618.24)

View product

Similar Articles