The voltage drop percentage in an electric motor supply is calculated for a three-phase line with ΔU% = √3 × I × L × (R × cosφ + X × sinφ) / U × 100. The calculation is done twice: once with the running current, once with the current and power factor at the moment of starting; the second is often the real source of the problem.
Where does each term in the formula come from?
Current I comes from the motor nameplate, length L from the actual route of the cable from the panel to the terminal box, and R and X from the resistance and reactance per km given in the cable manufacturer's catalogue. U is the line-to-line supply voltage, 400 V for industrial supplies in Turkey.
The most common mistake with length is using the straight-line distance on the layout sketch. Cable trays turn at corners, drop down columns and run behind the machine; the route measured with a tape or from the tray plan comes out clearly above the distance on paper. In addition, the cable's resistance at operating temperature is higher than the 20 °C value printed in the catalogue; on a loaded, warm line this difference must be taken into account (general information; confirm with the cable manufacturer's data).
The cosφ value comes from the motor nameplate or catalogue. It applies at full load. At part load the power factor falls but so does current, so the drop calculation is made for the full-load scenario.
How is the drop calculated in continuous running?
The rated current on the nameplate, the actual cable length and the catalogue R and X values are put into the formula; the resulting volts are divided by the supply voltage and multiplied by 100.
Hypothetical example: a 37 kW, 4-pole motor draws 66.1 A at 400 V. The cable route from panel to motor is 120 m. The cable catalogue gives a conductor resistance of 0.32 Ω/km and a reactance of 0.08 Ω/km; take cosφ as 0.86, which makes sinφ ≈ 0.51.
The figures are hypothetical and only show the method. In your own plant, take R and X from the catalogue of the cable you use and cosφ from the motor nameplate.
Why must the drop at starting be calculated separately?
In direct-on-line starting the current the motor draws from the supply exceeds the nameplate value many times over; in those seconds the power factor is also very low. Because current multiplies, the drop multiplies too; voltage at the motor's own terminals falls exactly when it needs torque most.
Back to the same example. Assume a locked-rotor current ratio of 6 and a cosφ of 0.3 at start (both values must be taken from the catalogue). Current is about 397 A; the bracket term is 0.32 × 0.3 + 0.08 × 0.95 ≈ 0.172 Ω/km. ΔU ≈ 1.73 × 397 × 0.12 × 0.172 ≈ 14.2 V, roughly 3.6%.
On paper that may look small. But this is the motor cable alone; the drop in the transformer and the main feeder happens at the same moment. Because the torque of an asynchronous motor varies with the square of voltage, each percent lost at the terminals takes away roughly twice as much from starting torque (general information; confirm with the machine manufacturer). That is why a belt full of material or a hammer mill cannot start on a weak line, or takes a very long time to start.
On motors with long supply lines, voltage drop is measured at the terminal box under load (representative image).
Prices and technical data are on the product pages; choose a model and order online.
How do you verify the calculation by measurement on site?
A sound check is made by measuring two points at the same time: the output terminal in the panel and the motor's terminal box. The difference between them gives the cable's real drop.
This needs two people and two multimeters. With the motor under load, one reads line-to-line voltage in the panel and the other at the motor; the readings are matched by saying “now” over a radio or phone. For the starting moment an instrument with peak hold or an energy analyser is used; an ordinary multimeter cannot catch the brief collapse at start. If the measured difference is clearly larger than calculated, the first place to look is the intermediate connections and cable lugs: a loose lug both increases the drop and shows up as a hot spot on a thermal camera.
Which options are considered if the drop turns out high?
A lasting solution always goes through the plant's electrical design. The permitted drop limit is defined in the regulations and the project specification, and the cable cross-section and protective devices are set by the electrical engineer who signs the design. This article does not recommend a cross-section or fuse rating; it shows what information the decision is based on.
Situation
Route to consider
Whose decision
Drop high in continuous running
Recalculating the cable cross-section or a parallel run
Design electrical engineer
Drop high only at starting
A method that reduces starting current: star-delta, soft start, drive
Panel designer and machine manufacturer
Long line, motor far from the panel
Moving the panel or a distribution box closer to the motor
Plant management and design lead
Drop dominated by the transformer side
Transformer tap setting or capacity review
Plant electrical supervisor, distribution company
If starting with a drive is chosen: our three-phase series are suitable for speed control with a frequency converter; long running at low speed with full torque may need a separate fan; with a long drive–motor cable a dv/dt or sine filter is considered; these conditions are stated with the order.
What information enters the calculation when ordering a new motor?
The voltage drop calculation relies on the motor's rated current, locked-rotor current ratio and power factor. So when a motor is selected, these three values must be taken from the catalogue and passed to the design team. Moving from IE3 to IE4 can lower running current somewhat, but the starting current ratio varies by model; the two must be checked separately.
Three models close to the power family of the example calculation are listed below; rated currents are from the product pages, while starting current and cosφ values are confirmed with the order. Current data for all models are listed in the electric motor shop.
160M-4: aluminium frame, 11 kW, 1465 rpm, 20.4 A at 400 V, 400/690 V.
180M-4: cast iron, 18.5 kW, 1470 rpm, 33.5 A at 400 V, 400/690 V.
225S-4: cast iron, 37 kW, 1485 rpm, 66.1 A at 400 V, 400/690 V. The current used in the hypothetical calculation.
Family features are on the asynchronous electric motors page. Stating the cable length and starting method when requesting a quote speeds up finding the right model; the information needed is listed in the quote preparation guide.
If your existing motor struggles to start on a long line, send the nameplate photo, the cable route length and the starting method via our contact page; we will go through the calculation together with the catalogue values. You can find all power steps in the HEM Motor sales list.
Frequently Asked Questions
Is the same formula used for a single-phase motor?
On a single-phase line a factor of 2 is used instead of √3, because current flows through both the phase and the neutral conductor. U is then taken as the phase-to-neutral voltage.
Does voltage drop increase the motor's current?
If the load is constant and terminal voltage falls, the motor raises its current to keep the power at the shaft. That makes the drop a little larger again and heats the winding.
Does voltage drop come only from the cable?
No; the transformer, the main distribution line and the breaker and contactor contacts also add to it. That is why total drop is assessed from the transformer output, not from the panel.
Should R be taken at 20 °C or at operating temperature in the calculation?
For a line under continuous load, resistance at operating temperature gives a more realistic result. Cable catalogues often give this value separately.
HEM Motor Models Related to This Article
The cards show example models related to the topic. A suitable motor is not chosen by power alone: compare speed, voltage, mounting, shaft and connection dimensions on the product page; if unsure, send a photo of the existing motor’s nameplate on WhatsApp.
Checking that electric motor pulleys lie in the same plane means seeing whether the side faces of both pulleys meet on one straight line. In practice a taut string, a steel straigh... More Details
If an electric motor's coupling element fails often, the first thing to investigate is shaft misalignment, followed by coupling selection, starting and shock loads, environmental e... More Details
The quickest way to tell foundation looseness from unbalance in electric motor vibration is to loosen the foot bolts one at a time while measuring and watch the change, and to comp... More Details
When building a sound enclosure around an electric motor, cooling is preserved by giving the enclosure a labyrinth or silenced inlet large enough for the air the motor fan draws, p... More Details
In an electric motor running in a hot environment, winding and bearing temperatures are monitored separately because they heat up from different sources, have different limits and ... More Details
When an electric motor is started for the first time at sub-zero temperatures, three things need checking: winding insulation resistance and any moisture or ice inside, bearing gre... More Details