How Is Axial Load Assessed When an Electric Motor Is Mounted Shaft Up?

How Is Axial Load Assessed When an Electric Motor Is Mounted Shaft Up?

When an electric motor is mounted shaft up (V3, V6 and the like), the weight of the rotor and of the pulley, fan or impeller on the shaft end acts on the bearing in the axial direction. The assessment consists of finding the direction and size of this force and comparing it with the permissible axial load for that mounting and that direction. The mounting arrangement and load direction are stated together with the order.

Where does the axial load come from in shaft-up mounting?

In a horizontal motor the rotor weight acts radially on the bearings; the two bearings share this load. In the shaft-up position the same weight acts downwards along the axis, and it is carried only by the bearing that is located to take axial load.

The parts on the shaft end are added to the rotor weight. A pulley, coupling half, fan wheel or mixer hub adds downward weight. On top of these come the forces produced in operation: if an inclined-blade fan pushes air downwards, the reaction force pulls the shaft up; an impeller working the other way presses the shaft down.

The net axial load is thus the sum of three items: rotor weight, the weight of the shaft-end equipment and the thrust produced by the process. The sign of each is determined separately. Sometimes one balances another.

Why does the load direction matter so much?

In standard motors one bearing is usually arranged as the locating bearing (carrying axial load) and the other as the non-locating bearing (allowing thermal expansion). Which side is the locating one depends on the motor design, and the permissible axial load is given separately in the catalogue for each direction.

In the vertical position the rotor weight pushes the shaft towards the frame, i.e. downwards. When a force pulling the end upwards acts, the load direction reverses. That is why it is first established which of the two catalogue values, labelled "push" and "pull" or "towards the shaft end" and "towards the frame", applies.

Once the limit is exceeded, bearing noise rises quickly.

Temperature climbs and L10h life falls far below the catalogue value; the bearing on the locating side is replaced several times sooner than the one on the free side.

How is the axial load calculated?

Start with a simple table. Hypothetical example: on a vertical mixer, a motor mounted shaft up with a belt pulley on the shaft end.

ItemDirectionValue (hypothetical)Source
Rotor weightDown≈ 0.25 kNRequested from the motor manufacturer
Pulley and hubDown≈ 0.15 kNWeighing or drawing
Axial component of belt forceIgnored≈ 0Belt in the horizontal plane, axial component neglected
Thrust from the processUp or downFrom the machine manufacturerImpeller or mixer data
Net axial loadDown≈ 0.40 kN + process thrustTotal

In a belt application there is radial load as well as axial load. Belt tension pulls the shaft sideways; this force is assessed separately and compared with the permissible radial load in the catalogue according to the pulley's position on the shaft end. Having axial and radial load at the same time is harder on the bearing than either alone.

The last step is the comparison, and it is the shortest. The net axial load must stay below the permissible value given for that mounting and that direction; if it does not, a change of bearing arrangement is requested (general information; confirm with the motor manufacturer).

Which applications call for shaft-up mounting?

It is less common than horizontal mounting, but on some machines it is the only sensible solution:

  • Bottom-driven mixers built the other way round, with the motor below instead of on top of the tank.
  • Some vertical-shaft fans and cooling tower applications.
  • Turntable, rotary screen and rotary table drives.
  • Arrangements placed under a platform that drive a shaft above via a pulley.

The common risk of these applications is liquid or dust running down from the shaft end into the motor. In this position the seal faces up; water or product falling on it collects around the seal by gravity. That is why a splash ring (V-ring or flinger disc) is added to the end.

Foot-mounted electric motor, shaft and bearing side
When the mounting changes, the direction of the load on the bearings changes too; the permissible axial load for the same frame is assessed separately for each mounting (representative image).

Prices and technical data are on the product pages; choose a model and order online.

How is the mounting arrangement defined in the order?

IEC mounting codes show the shaft direction together with the foot or flange arrangement. A foot-mounted frame with the shaft facing up is V6, its large-flange version V3, its small-flange version a code like V19. The shaft-down counterparts are V5, V1 and V18.

B3, B5, B14, B34, B35 and vertical V1/V3/V5/V6/V15 are offered depending on frame; flange size is confirmed with the order. Three pieces of information should be added next to the code in the order: the weight of the shaft-end equipment, the direction and estimated size of the process thrust, and whether there is water or dust in the area. A V3 order placed without these three items does not show whether the bearing arrangement suits the application.

Turning a motor bought for horizontal use to vertical on site is possible. It is not recommended. The drain holes end up in the wrong place, terminal box entries may face up, and the bearing arrangement may not have been chosen for this load.

What shows an axial load problem on site?

Early signs can usually be heard and felt. A steady hum from the locating bearing, that end of the frame being clearly hotter than the other, and grease leakage are the first signs.

At a later stage the shaft feels rough when turned by hand and axial play increases. When the bearing is removed, the ball track appears shifted from the middle of the race towards one edge; this shows the bearing has been running under axial load in one direction all the time.

When the signs start, the first job is to rebuild the net axial load table. Most often what turns up is a heavy pulley added later, an impeller replaced during maintenance with a different blade angle, or a fan running backwards because the phase sequence was swapped and blowing air up instead of down; in that last case the direction of thrust changes as well, and the limit in the other direction now governs the load. Writing down the source of each item when building the table saves redoing the same calculation at the next failure.

Fan direction is the first thing to check.

Which motors suit this mounting?

In applications such as vertical mixers and turntables, 4-pole medium-power motors are common. The examples below are in our electric motor shop; vertical mounting arrangement and bearing arrangement are stated with the order:

  • 100L2-4: 3 kW, 1450 rpm, 19.8 Nm, 6.02 A. For small turntables and light mixers.
  • 132S-4: 5.5 kW, 1460 rpm, 36 Nm, 10.7 A. For medium belt-driven loads.
  • 160M-4: 11 kW, 1465 rpm, 71.7 Nm, 20.4 A. For heavy hubs and high-thrust applications; the bearing arrangement must be confirmed.

The frames have IP55 protection and class F insulation; the whole series is on the asynchronous motors page. For motor dimensions see the 2D technical drawings page, and for first start-up steps after installation the commissioning checklist article.

If you send the weight of the shaft-end equipment and the process thrust direction added to the quotation information list through our contact page, we will settle the bearing arrangement for the mounting in the quotation. Other frames and speeds can be seen in the HEM Motor product list.

Frequently Asked Questions

Does a horizontal motor fail straight away if run shaft up?

Not necessarily straight away. But if the bearing arrangement and drain holes are not made for this position, bearing life shortens and water can collect inside.

Where can the rotor weight be found?

It is usually not in the catalogue and is requested from the motor manufacturer. A fraction of total motor weight can serve as a rough estimate, but the calculation needs the real value.

How is the shaft seal protected on a shaft-up motor?

A V-ring or flinger disc is fitted on the shaft end, preventing product or water from collecting on the seal. If the area is very wet, the IP56 option is considered.

What is done if the axial load exceeds the catalogue value?

The load is reduced or a reinforced bearing arrangement is requested. Which solution is suitable is decided together with the motor manufacturer.

HEM Motor Models Related to This Article

The cards show example models related to the topic. A suitable motor is not chosen by power alone: compare speed, voltage, mounting, shaft and connection dimensions on the product page; if unsure, send a photo of the existing motor’s nameplate on WhatsApp.

3 kW 1500 rpm Cast Iron Frame Electric Motor 100L2-4

100L2-4

3 kW · 1500 rpm

  • Cast iron frame · IEC 100L
  • 1450 rpm · IP55
  • Mounting: B3 foot; flange (B5/B14/B35) depending on frame, confirmed with the order

US$199.92 (€182.97)

View product
5.5 kW 1500 rpm Cast Iron Frame Electric Motor 132S-4

132S-4

5.5 kW · 1500 rpm

  • Cast iron frame · IEC 132S
  • 1460 rpm · IP55
  • Mounting: B3 foot; flange (B5/B14/B35) depending on frame, confirmed with the order

US$335.43 (€306.99)

View product
11 kW 1500 rpm Cast Iron Frame Electric Motor 160M-4

160M-4

11 kW · 1500 rpm

  • Cast iron frame · IEC 160M
  • 1465 rpm · IP55
  • Mounting: B3 foot; flange (B5/B14/B35) depending on frame, confirmed with the order

US$557.82 (€510.52)

View product

Similar Articles