How to Tell an Open Circuit from Overtemperature on an Electric Motor PTC Sensor

How to Tell an Open Circuit from Overtemperature on an Electric Motor PTC Sensor

The quickest way to tell an open circuit from overtemperature in an electric motor's PTC circuit is to measure the resistance of the PTC leads while the motor is cold: if the cold winding reads somewhere around a few hundred ohms, the sensor is healthy and the earlier trip came from real heating; if the multimeter shows infinity (OL), the circuit is broken. The distinction is confirmed by watching how resistance behaves as the motor cools.

How does a PTC sensor report temperature?

A PTC thermistor shows a low, almost constant resistance up to a certain threshold temperature; near the threshold its resistance rises steeply within a few degrees. Three sensors embedded in the winding are connected in series and their two ends come out to a separate terminal in the terminal box.

The motor itself does not interpret this resistance. The leads go to the thermistor relay in the panel; the relay sends a small measuring current, opens its contact when resistance passes the threshold and drops out the main contactor. For the relay both situations are the same: whether the winding overheats or the cable breaks, what it sees is high resistance. That is why the technician has to make the distinction.

The sensor's threshold temperature is chosen according to the insulation class and is written in the motor's winding data. At HEM Motor, PTC and PT100 winding sensors are an order option; which threshold temperature is applied is confirmed with the order.

What does a resistance measurement on a cold motor show?

When the motor has stood for at least a few hours and cooled to ambient temperature, the total resistance of the three series PTCs should be low; typically each sensor reads between tens and a few hundred ohms (general information; confirm with the sensor and relay manufacturer's data sheet). If this value is seen, the sensor chain is intact.

The measuring order should be as follows:

  1. Isolate and lock off the supply, and also disconnect the thermistor relay's supply voltage.
  2. Remove the PTC leads at the relay end; measure first in the panel, including the cable.
  3. Set the multimeter to a low ohms range and read between the two ends.
  4. If the value is infinite, open the motor terminal box and repeat the same measurement directly on the PTC terminals.

A panel reading of infinity together with low resistance at the motor puts the break in the cable.

When the motor also reads infinity, the sensor chain has opened inside the winding.

Never connect an insulation tester (megger) to the PTC leads. The high test voltage destroys the thermistor within a second, makes a healthy sensor read open at the next measurement and also hides the original fault. The measuring instrument's test voltage must be low; many manufacturers limit it to a few volts.

How are an open circuit and real heating told apart on site?

With an open circuit the relay stays open even when the motor is cold and will not reset; with real heating, resistance falls as the motor cools and the relay can reset automatically or by hand. Time is the most reliable witness for this distinction.

ObservationOpen circuitOvertemperature
When did the relay open?At start-up or at a moment of vibration, motor coldAfter running under load for a while
Frame temperatureClose to ambientSo hot a hand cannot stay on it even for a few seconds
Cold resistance readingInfinite or unstableLow, normal value
As the motor coolsNo change, relay does not resetResistance falls, relay resets
When the cable is moved slightlyValue jumps (loose end)Value does not change

An unstable reading is especially important. If the value on the multimeter display jumps between infinity and low when the cable or terminal screw is touched, the problem is a loose connection or a broken conductor. Vibration from the fan end exposes this kind of break during running, the contact closes again when the motor stops, and the fault looks as if it "cleared itself".

If overtemperature is confirmed, where is the cause looked for?

When the PTC really reported heating, the sensor has worked correctly and the problem lies in the motor's cooling or load balance. The checks fall under four headings: current, voltage, cooling air and duty pattern.

The clamp meter is placed on the three phases in turn and the readings are compared with the plate value; line-to-line voltage is measured at the same time, because low voltage and phase imbalance raise current. Then the fan cover is inspected from outside without removing it. If dust, fibre or oily dirt has built up on the cover grille and the gaps between the frame fins are packed, the motor cannot draw its own air.

In textile and flour mills, a grille that clogs within a few weeks is the most frequent cause of PTC trips.

The same result is seen on motors driven at low frequency by a converter for many hours, because the shaft-mounted fan slows down and airflow drops. Our three-phase ranges are suitable for speed control with a frequency converter; for long periods at low speed with full torque an external fan may be needed; if the drive-to-motor cable is long, a dv/dt or sine filter is considered; these conditions are stated with the order.

Frequent stop-start is another overlooked cause. Every start heats the winding with a current several times rated current; if the permitted number of starts per hour is exceeded, the winding heats up even when average current looks normal. A conveyor on a packaging line that stops for every product, or a pump that switches on and off according to temperature, can make hundreds of starts a day, and at the end of the shift its frame is noticeably hotter than a motor of the same power running continuously; in that case blaming the sensor without comparing the number of starts with the machine manufacturer's data is a mistake. Models for similar duties are listed by power and frame in the store.

Three-phase electric motor on a workshop bench
PTC measurement is made with the motor cold, first in the panel and then in the terminal box (representative image).

Prices and technical data are on the product pages; choose a model and order online.

Can a PTC that has broken inside the winding be replaced?

Because the sensors are embedded in the winding they cannot be removed and fitted on their own; replacement is only done during a rewind. That is why you first have to be sure the break really is inside the winding.

In the terminal box the PTC leads are thin wires that can be crushed under a screw, and in oily environments their insulation can crack. Looking with a magnifier at the point inside the box where the two thin wires from the winding enter the terminal disproves many "broken sensor" diagnoses in a few minutes.

With a chain that has opened inside the winding, two options remain. If the motor is going for a rewind, the sensors are renewed then; if the winding is sound and the motor is not critical, another form of protection (thermal relay setting, surface temperature sensor) is brought in temporarily with the responsible engineer's approval and the situation is written in the maintenance record. Bridging the thermistor protection and running with nothing in its place is not acceptable.

Which faults on the relay side look like a PTC failure?

When the thermistor relay's supply voltage is lost or the relay itself fails, the contact also opens and the picture resembles a broken PTC. Connecting a test resistor of suitable value to the relay terminals in the panel with the motor disconnected shows at once whether the relay is healthy.

Some relays also treat a short circuit as a fault. Should the PTC leads touch each other in the terminal box or the cable be crushed into a short, the relay still opens; this time the multimeter reads close to zero. The difference between zero and infinity on the display is enough to tell a crushed cable from a broken one.

A cable between relay and motor that runs a long distance in the same tray as the power cable can pick up induced voltage and cause false trips. A screened cable on a separate route removes this problem; the decision is made by the site's electrical supervisor.

What is specified when ordering an electric motor with PTC?

The order states the sensor type (PTC or PT100), the quantity and the required threshold temperature; it also states whether the leads should come out to a separate terminal in the terminal box. Adding application details (converter drive, frequent starting, dusty environment) makes the right choice easier.

Examples from mid-power steps where PTC is often requested:

  • 132M-4, cast iron, 7.5 kW, 1460 rpm, 400/690 V, 14.3 A at 400 V.
  • 180M-4, cast iron, 18.5 kW, 1470 rpm, 400/690 V, 33.5 A at 400 V.
  • 200L-4, cast iron, 30 kW, 1475 rpm, 400/690 V, 53.8 A at 400 V.

The models are IP55 with class F insulation and carry CE marking.

The PTC/PT100 sensor and IE class are confirmed per model with the order. The whole asynchronous family is on the asynchronous electric motors page, and the information to prepare when requesting a quote is in the quote preparation guide.

Send the failed motor's plate, a photo of the PTC leads in the terminal box and the resistance you measured cold through the nameplate submission page; we will work out an equivalent with sensors together and choose it from the HEM Motor sales list.

Frequently Asked Questions

Can PTC resistance be measured while the motor is running?

No measurement is made with the leads still on the relay and the motor energised; for safety and because the relay current distorts the reading, the measurement is made on a stopped and locked-off motor.

What is the difference between PT100 and PTC?

A PTC works like a switch that raises its resistance suddenly at the threshold; a PT100 gives a resistance that changes continuously in proportion to temperature, so the temperature itself can be monitored. A PT100 needs a separate measuring device.

What should be done if the motor trips again right after the relay is reset?

The winding has not yet fallen below the threshold or the cause of heating has not been removed. Restarting without letting the motor cool fully and checking current, voltage and cooling air wears the winding insulation.

HEM Motor Models Related to This Article

The cards show example models related to the topic. A suitable motor is not chosen by power alone: compare speed, voltage, mounting, shaft and connection dimensions on the product page; if unsure, send a photo of the existing motor’s nameplate on WhatsApp.

7.5 kW 1500 rpm Cast Iron Frame Electric Motor 132M-4

132M-4

7.5 kW · 1500 rpm

  • Cast iron frame · IEC 132M
  • 1460 rpm · IP55
  • Mounting: B3 foot; flange (B5/B14/B35) depending on frame, confirmed with the order

US$387.29 (€354.46)

View product
18.5 kW 1500 rpm Cast Iron Frame Electric Motor 180M-4

180M-4

18.5 kW · 1500 rpm

  • Cast iron frame · IEC 180M
  • 1470 rpm · IP55
  • Mounting: B3 foot; flange (B5/B14/B35) depending on frame, confirmed with the order

US$856.68 (€784.05)

View product
30 kW 1500 rpm Cast Iron Frame Electric Motor 200L-4

200L-4

30 kW · 1500 rpm

  • Cast iron frame · IEC 200L
  • 1475 rpm · IP55
  • Mounting: B3 foot; flange (B5/B14/B35) depending on frame, confirmed with the order

US$1,211.23 (€1,108.54)

View product

Similar Articles