Insulation resistance is the resistance of the insulation between the stator winding and the motor frame, read at a set DC test voltage, usually at the 1st minute; the polarisation index is the ratio of the 10th-minute reading to the 1st-minute reading in the same test. The first shows the insulation level at that moment, the second shows how the reading rises over time and is more reliable for telling moisture from contamination.
Why does the megger reading rise over time?
The moment DC voltage is applied, three separate currents flow through the insulation and two of them die away over time. The capacitive charging current ends within a few seconds. The absorption current comes from molecules in the insulation material aligning with the electric field and decreases slowly over several minutes. The remaining third component is leakage current. It flows through surface moisture, dust, oil film and cracks in the insulation and does not decrease over time.
The resistance shown on the instrument display is the applied voltage divided by the sum of these three currents. In a dry, clean winding the absorption current dominates, so resistance climbs noticeably in the first minutes. In a wet or dirty winding leakage dominates; the reading settles on one value within seconds and stays there.
How is insulation resistance measured and how is it read?
With the motor de-energised and locked off, the supply cables are disconnected from the terminals, the three phase terminals are shorted together and the megger is connected between this common point and the frame. The reading is usually taken at the end of the 1st minute and recorded together with winding temperature.
The test voltage is chosen according to the motor's rated voltage. For low-voltage motors in the 400 V and 690 V class, 500 V or 1000 V DC is common (general information; confirm with the instrument maker's instructions and the relevant standard). An electronic device such as a frequency converter, PTC relay or capacitor left connected on the motor side can be damaged during the test. These are disconnected beforehand.
The reading is very sensitive to temperature. As a general approach, insulation resistance roughly halves for every 10 °C rise. So 2000 MΩ taken on a cold motor in the morning and 500 MΩ taken on a warm motor in the afternoon may show the same insulation condition; for comparison, readings are corrected to a common reference temperature.

After the test the winding must be discharged to earth for a while.
This time is kept at least as long as the test, preferably longer. A technician who removes the megger and touches the terminals straight away can get a shock from the still-charged winding.
How is the polarisation index calculated?
PI = R10 min / R1 min. At the same test voltage, without interrupting the test, the two resistance values read at the 1st and 10th minutes are divided.
A hypothetical example: if 850 MΩ is read at the 1st minute and 2300 MΩ at the 10th, PI ≈ 2.7. On another motor, if 900 MΩ is read at the 1st minute and 1050 MΩ at the 10th, PI ≈ 1.2. The 1st-minute values of the two motors are almost the same, but in the second the resistance has hardly risen over time; this points to dominant leakage current, that is, moisture or conductive dirt on the surface.
Being a ratio, PI is hardly affected by temperature, which is a big help on site.
Since the two readings are taken a few minutes apart at the same temperature, the correction factor cancels out; even if the temperature record is missing on site, PI can still be interpreted. For those who prefer a short test, the dielectric absorption ratio (DAR) is also used: the 60-second reading divided by the 30-second reading. It is useful on small motors and for quick checks, but it is not as discriminating as PI.
When does insulation resistance tell more, and when does PI?
For a quick "can it be started" decision insulation resistance tells more; to understand the real condition and trend of the insulation, PI gives more information. Each is incomplete on its own; read together they make sense.
| 1st-minute resistance | PI | Likely interpretation | Step on site |
|---|---|---|---|
| High | High | Dry and clean insulation | Record the values and commission |
| Low | Low, close to 1 | Moisture or conductive dirt on the surface | Drying, cleaning and re-measurement |
| Low | High | Insulation sound, measured on a hot winding or with the cable included | Disconnect the cable and repeat once cooled |
| Very high | Close to 1 | Small motor or very dry insulation, PI may have lost its meaning | Compare with the previous record |
| Falling fast compared with the previous record | Both values falling | Insulation ageing or repeated moisture ingress | Check the environment and drain holes, consult a rewind shop |
The table is a rough matching used on site. As a common rule for acceptance limits, a PI below about 2 on motors with class F insulation is treated as a warning; however, which figure applies depends on the standard used and the motor's construction (general information; confirm with the current text of the relevant standard and with the rewinder).