Check Sequence for an Overcurrent Alarm on an Electric Motor Drive

Check Sequence for an Overcurrent Alarm on an Electric Motor Drive

When an overcurrent alarm comes up on an electric motor drive, the check starts by establishing at which moment the alarm tripped; then the drive parameters, the output cable, the motor winding and finally the mechanical load are examined in that order. This sequence rules out the easiest and most frequent cause first and leaves the jobs that need dismantling to the end.

When does the alarm come: at start, at constant speed or when stopping?

The timing of the alarm tells you half of the cause.

Most drives record the alarm in their fault history with separate codes for acceleration, constant speed and deceleration; the first job is to read that record and see whether the last few alarms cluster in the same phase.

An alarm during acceleration usually comes from an acceleration time that is short for the load inertia or from starting torque boost set too high. A sudden alarm at constant speed points to a mechanical jam, a short circuit on the output side or an earth leak. Overcurrent during deceleration is rarer; it mostly appears when the deceleration time is very short or when a motor that is still coasting is restarted.

If the alarm comes the moment power is applied, before the motor even turns, the problem is most likely in the output cable or the winding.

How should the check sequence be set up?

Records first, then parameters, screwdriver last. The sequence that works on site is:

  1. Read the fault history: alarm code, output frequency at the moment of the alarm, current and DC bus voltage.
  2. Compare the motor plate with the drive's motor parameters: rated voltage, rated current, rated frequency, rated speed.
  3. Check the acceleration and deceleration times, the starting torque boost and the V/f curve selection.
  4. Isolate, wait for the capacitor discharge time and disconnect the motor cable from the drive output.
  5. Measure cable and motor together, then separately, against earth with an insulation tester.
  6. Read the winding resistance between motor terminals with a micro-ohmmeter and compare the three values.
  7. Remove the coupling and turn the shaft by hand; then run the motor unloaded and see whether the alarm returns.

The drive cover is not opened before the fourth step. Even with the isolator off, the capacitors stay charged for a while; the waiting time is written on the drive label and is verified with a multimeter on the DC bus.

Which drive parameter mistake is seen most often?

The most common mistake is that the motor plate data are not entered at all, or are entered for the wrong connection. A motor with a 230/400 V plate is connected in star to a 400 V drive, and the star current is written into the drive; if the higher delta current is entered, protection acts late, and conversely if a low value is entered, the drive alarms right at start.

Acceleration time comes second. When a fan with a heavy impeller or a mixer full of dough is to reach full speed in a few seconds, the drive hits its current limit. Lengthening the time and seeing the alarm disappear is both the diagnosis and the cure.

Check the boost setting too.

If starting torque boost is set too high, the motor is over-magnetised at low frequency. High current is then read even at no load and the motor shudders at start. On some drives, selecting vector control without running automatic motor identification (autotuning) gives the same symptom; identification is done with the motor cable connected and, if possible, unloaded.

Overcurrent also appears if a stopped fan is being turned backwards by the wind and the drive tries to start it from zero. In such applications the catch-a-spinning-motor function (flying start) is enabled.

How are the output cable and motor winding measured?

First the cable is removed from the drive. Applying an insulation tester with the output connected can destroy the IGBT stage, and this mistake is made on site more often than people think.

The measurement is first taken with cable and motor together, with U, V, W bridged and measured against earth. If the value is low, the cable is disconnected in the terminal box on the motor side and the two parts are measured separately. On cables running outside the cabinet, through ducts and exposed to water, weak insulation turns up more often than in the winding.

Winding resistance needs a micro-ohmmeter or four-wire measurement; an ordinary multimeter may do on small motors but cannot catch the difference on large ones. The values between the three phases are expected to be close. One clearly lower value points to an inter-turn short, one higher value to a loose connection.

Cable length has to be taken into account as well. A long screened motor cable creates capacitive leakage current at the drive output; even with a healthy motor, the drive may see this as overcurrent or earth leakage. Our three-phase series are suitable for speed control with a frequency converter; for long periods at low speed with full torque an external fan may be needed; if the drive-to-motor cable is long, a dv/dt or sine filter is considered; these conditions are stated with the order.

Three-phase electric motor on a test bench
Trying the motor without cable and without load is the shortest way to separate the source of the alarm between drive, cable and load (representative image).

Prices and technical data are on the product pages; choose a model and order online.

How does the mechanical load trigger the alarm?

The mechanical side is examined only after the electrical side is clean, because checking it requires dismantling and a production stop. With the coupling removed, the shaft is turned by hand. Rough, uneven rotation or rotation that catches at one point reveals the bearing, a rubbing fan cover or a jammed rotor.

If the motor runs unloaded and the alarm disappears, the problem is in the driven machine. Lack of oil in the gearbox, a seized roller on the conveyor, a clogged impeller in the pump or material built up in the screw fall into this class. On site the machine is turned by hand while current is watched on the drive display, and the catching point is found. Sudden alarms sometimes come from a shock on the load side. A large stone dropping into the crusher mouth or a blade meeting a hard piece pushes current above the limit within milliseconds; here the solution is not a parameter but sizing the drive and motor for that shock. If you need to look at the next power step, the options are sorted by frame on the electric motor sales page.

Where to look first according to the symptom

The table below suggests the first check according to when the alarm occurs and the symptom that comes with it. It is based on site experience and does not replace a drive manufacturer's fault code table.

SymptomPossible causeFirst check
Alarm as soon as power is applied, motor not turningShort circuit in cable or winding, earth leakInsulation measurement with cable disconnected from the drive
Alarm only during accelerationAcceleration time short, boost too highLengthen time and retry, boost setting
Occasional alarm at constant speedMechanical jam, shock loadCompare current log with events at the machine
Alarm during decelerationDeceleration time short, load turning backwardsDeceleration time, flying start function
Alarm only on the motor with a long cableCapacitive leakage currentCable length, output filter evaluation
Alarm starting after the motor was replacedParameters left for the old motorRe-enter plate data and run motor identification

When is the motor replaced, and when is the manufacturer asked?

If the insulation value stays permanently low or there is a clear difference between winding resistances, the motor goes for repair or replacement. On the drive side, if the alarm continues even in unloaded running with motor and cable healthy, the drive itself must be examined; at that stage the drive manufacturer's service is contacted.

After the replacement decision, the values on the new plate are set side by side with the drive's limits. Which information to give when requesting a quote is listed in the guide to preparing a quote request. Four-pole cast iron frame steps that are often paired with drives:

  • 100L1-4: 2.2 kW, 1450 rpm, 230/400 V (Δ/Y), 4.52 A at 400 V.
  • 100L2-4: 3 kW, 1450 rpm, 230/400 V (Δ/Y), 6.02 A at 400 V. On a 400 V drive it is connected in star and this current is entered in the drive.
  • 112M-4: 4 kW, 1450 rpm, 400/690 V (Δ/Y), 7.95 A at 400 V. On a 400 V drive it is connected in delta.

These steps and the other ratings are listed in the electric motor store, and the family features are on the asynchronous electric motors page. The series is offered in IE3, IE4 and IE5 efficiency classes; which class is available for a given model is confirmed with the order.

Send the alarm code, the frequency and current log at the moment of the alarm, your insulation and winding resistance readings and a photo of the motor plate through the contact page; if a replacement is needed we will choose a step compatible with the drive together. Prices can be seen in the HEM Motor product list.

Frequently Asked Questions

Is resetting the first thing to do after an overcurrent alarm?

Before a reset, the fault history should be read and the frequency and current at the moment of the alarm noted. Resetting repeatedly without knowing the cause can also damage the drive if there is a short circuit.

Can the insulation test be done with the drive connected?

No. The tester voltage can damage the IGBTs; the cable is first removed from the output terminals.

If the alarm disappears when the motor runs unloaded, where is the problem?

Most probably in the driven machine: a jam, lack of oil or built-up material. The machine is turned by hand while current is watched and the catching point is searched for.

What should be done if the alarm started after the motor was replaced?

The motor parameters in the drive are re-entered according to the new plate and motor identification is repeated. The suitability of the connection for the drive voltage is also checked.

HEM Motor Models Related to This Article

The cards show example models related to the topic. A suitable motor is not chosen by power alone: compare speed, voltage, mounting, shaft and connection dimensions on the product page; if unsure, send a photo of the existing motor’s nameplate on WhatsApp.

2.2 kW 1500 rpm Cast Iron Frame Electric Motor 100L1-4

100L1-4

2.2 kW · 1500 rpm

  • Cast iron frame · IEC 100L
  • 1450 rpm · IP55
  • Mounting: B3 foot; flange (B5/B14/B35) depending on frame, confirmed with the order

US$184.70 (€169.04)

View product
3 kW 1500 rpm Cast Iron Frame Electric Motor 100L2-4

100L2-4

3 kW · 1500 rpm

  • Cast iron frame · IEC 100L
  • 1450 rpm · IP55
  • Mounting: B3 foot; flange (B5/B14/B35) depending on frame, confirmed with the order

US$199.92 (€182.97)

View product
4 kW 1500 rpm Cast Iron Frame Electric Motor 112M-4

112M-4

4 kW · 1500 rpm

  • Cast iron frame · IEC 112M
  • 1450 rpm · IP55
  • Mounting: B3 foot; flange (B5/B14/B35) depending on frame, confirmed with the order

US$249.49 (€228.34)

View product

Similar Articles