When an overcurrent alarm comes up on an electric motor drive, the check starts by establishing at which moment the alarm tripped; then the drive parameters, the output cable, the motor winding and finally the mechanical load are examined in that order. This sequence rules out the easiest and most frequent cause first and leaves the jobs that need dismantling to the end.
When does the alarm come: at start, at constant speed or when stopping?
The timing of the alarm tells you half of the cause.
Most drives record the alarm in their fault history with separate codes for acceleration, constant speed and deceleration; the first job is to read that record and see whether the last few alarms cluster in the same phase.
An alarm during acceleration usually comes from an acceleration time that is short for the load inertia or from starting torque boost set too high. A sudden alarm at constant speed points to a mechanical jam, a short circuit on the output side or an earth leak. Overcurrent during deceleration is rarer; it mostly appears when the deceleration time is very short or when a motor that is still coasting is restarted.
If the alarm comes the moment power is applied, before the motor even turns, the problem is most likely in the output cable or the winding.
How should the check sequence be set up?
Records first, then parameters, screwdriver last. The sequence that works on site is:
- Read the fault history: alarm code, output frequency at the moment of the alarm, current and DC bus voltage.
- Compare the motor plate with the drive's motor parameters: rated voltage, rated current, rated frequency, rated speed.
- Check the acceleration and deceleration times, the starting torque boost and the V/f curve selection.
- Isolate, wait for the capacitor discharge time and disconnect the motor cable from the drive output.
- Measure cable and motor together, then separately, against earth with an insulation tester.
- Read the winding resistance between motor terminals with a micro-ohmmeter and compare the three values.
- Remove the coupling and turn the shaft by hand; then run the motor unloaded and see whether the alarm returns.
The drive cover is not opened before the fourth step. Even with the isolator off, the capacitors stay charged for a while; the waiting time is written on the drive label and is verified with a multimeter on the DC bus.
Which drive parameter mistake is seen most often?
The most common mistake is that the motor plate data are not entered at all, or are entered for the wrong connection. A motor with a 230/400 V plate is connected in star to a 400 V drive, and the star current is written into the drive; if the higher delta current is entered, protection acts late, and conversely if a low value is entered, the drive alarms right at start.
Acceleration time comes second. When a fan with a heavy impeller or a mixer full of dough is to reach full speed in a few seconds, the drive hits its current limit. Lengthening the time and seeing the alarm disappear is both the diagnosis and the cure.
Check the boost setting too.
If starting torque boost is set too high, the motor is over-magnetised at low frequency. High current is then read even at no load and the motor shudders at start. On some drives, selecting vector control without running automatic motor identification (autotuning) gives the same symptom; identification is done with the motor cable connected and, if possible, unloaded.
Overcurrent also appears if a stopped fan is being turned backwards by the wind and the drive tries to start it from zero. In such applications the catch-a-spinning-motor function (flying start) is enabled.
How are the output cable and motor winding measured?
First the cable is removed from the drive. Applying an insulation tester with the output connected can destroy the IGBT stage, and this mistake is made on site more often than people think.
The measurement is first taken with cable and motor together, with U, V, W bridged and measured against earth. If the value is low, the cable is disconnected in the terminal box on the motor side and the two parts are measured separately. On cables running outside the cabinet, through ducts and exposed to water, weak insulation turns up more often than in the winding.
Winding resistance needs a micro-ohmmeter or four-wire measurement; an ordinary multimeter may do on small motors but cannot catch the difference on large ones. The values between the three phases are expected to be close. One clearly lower value points to an inter-turn short, one higher value to a loose connection.
Cable length has to be taken into account as well. A long screened motor cable creates capacitive leakage current at the drive output; even with a healthy motor, the drive may see this as overcurrent or earth leakage. Our three-phase series are suitable for speed control with a frequency converter; for long periods at low speed with full torque an external fan may be needed; if the drive-to-motor cable is long, a dv/dt or sine filter is considered; these conditions are stated with the order.