An electric motor cable gland is selected so that the outer diameter of the cable stays within the gland's sealing range and the thread size matches the terminal box entry exactly. Looking only at thread fit and skipping cable diameter leaves an entry that looks tight but lets water and dust through; in practice this cancels the motor's IP55 protection at the terminal box.
Which part of the gland provides the seal?
A standard plastic or brass cable gland consists of four parts: body, threaded end entering the box, inner seal and the cap that compresses it. As the cap is turned, the fingers inside press the seal step by step around the cable and form a thin but gap-free ring on the sheath. The sealing point is the contact surface between the seal and the cable sheath. Every seal has a clamping range. With a cable thinner than the lower limit of this range, the seal cannot wrap the cable fully and moisture seeps through the gap. If it is thicker than the upper limit, the seal does not seat, the cap does not close fully or the seal tears. The gland manufacturer gives this range in the catalogue as two figures.
A separate seal is also needed on the thread side between box and body. A flat O-ring or fibre washer is usually used here. If this washer is forgotten, water can enter through the thread gap no matter how well the cable side has been tightened.
How is the cable outer diameter measured on site?
The cross-section value of the cable is not enough for gland selection. Two cables with the same cross-section can have different outer diameters depending on insulation and sheath thickness. Armoured, screened or drive output cables are clearly thicker than a standard cable of the same cross-section.
A caliper is a must.
The measurement is taken at the section of cable that will enter the gland. Where the sheath is not perfectly round, readings are taken in two perpendicular directions and the average is used. The drum label helps, but the measurement of the cut piece is what counts.
One habit from the field is useful.
The electrician first slides the gland over the cable, tightens the cap by hand and tries to pull the cable. If the cable slips when pulled by hand, the seal has not gripped it. This simple test reveals a wrong selection even without a caliper.
What determines the thread size and entry hole?
The entry holes on the terminal box are made for a particular thread type and size. Metric threads are common on IEC motors; on some older motors or motors for other markets, other thread systems may be found (general information; confirm with the motor's technical drawing). The gland thread must match the box hole exactly.
When the threads do not match, an adapter or reducer is used on site. Each of these parts is a new sealing point and each must have its own washer. With a large box hole and a thin cable, first a reducer is fitted, then a gland suited to the cable. Unused entries are a separate matter. A motor usually comes with more than one entry. An entry left empty and not closed with a suitable plug makes the terminal box behave like an open window.
Terminal box entries and glands are checked before installation (representative image).
Prices and technical data are on the product pages; choose a model and order online.
What are the signs of a wrong gland selection on site?
The most common sign is a drop of water or rust marks inside the terminal box. When the cover is opened, greenish oxide is seen on the terminal screws and a damp patch at the bottom of the box. In insulation resistance measurement, the value is noticed to fall over time. A more insidious sign is the cable being pulled. When the gland does not hold the cable, vibration or cable weight strains the conductors at the terminal screws. The ends loosen. Contact resistance rises and the terminal heats up. A thermal camera shows that one phase terminal is hotter than the others.
Then there is the torn seal. A cable forced into a gland too small for its diameter tears the seal. Nothing is seen in the first days; a few months later wash water or rain starts to seep in.
Sign
Possible cause
Check
Water, rust, oxide in the box
Cable diameter below the seal range or thread washer missing
Cable diameter with caliper, presence of washer
Cable slips when pulled by hand
Seal does not grip the cable
Comparison of gland clamping range and diameter
One phase terminal hotter than the others
End connection loosened by cable pull
Thermal camera, terminal tightness
Cap does not close fully
Cable thicker than the seal range
Next gland size up
How does gland selection change for screened and drive cables?
With a drive, the cable is screened. On these cables the gland has one more task: bonding the screen all round to the terminal box body. For this, so-called EMC glands are used, which have a spring or conical element inside that grips the screen.
When selecting an EMC gland, two diameters are checked together: the outer sheath diameter for the seal range and the diameter of the screen braid for the contact element. Connecting the screen to the gland as a long pigtail clearly reduces the effect of screening (general information; confirm with the drive manufacturer's installation manual).
These glands have a metal body and are connected to the earthing continuity of the terminal box, that is, to the whole conduction path from the box body to the motor frame and from there to the plant's protective conductor. If metal contact has not been made on a painted box surface, the gland does not connect the screen to earth; this point is checked with a meter during installation.
Which example motors suit this application?
Three cast iron models for applications in humid and wash-down environments where the cable entry is critical are listed below. IP55 protection and class F insulation are common to all three; this protection applies when the cable entries are closed with the right gland and plug. Other power steps are listed in the HEM Motor shop.
100L1-4: 2.2 kW, 1450 rpm, 4.52 A at 400 V, rated torque 14.5 Nm. A power step often seen on washing lines and small conveyor drives.
100L-2: 3 kW, 2895 rpm, 5.71 A at 400 V, rated torque 9.9 Nm. In pump and fan applications, in positions exposed to splash water.
132S-6: 3 kW, 968 rpm, 6.84 A at 400 V, rated torque 29.6 Nm. In low-speed mixers and feeders, where vibration strains the cable entry.
Terminal box entry sizes vary with the frame; they are confirmed with the order. For checks after connecting the motor, see the commissioning checklist; for the information to give when requesting a quote, see the quote request guide. All frame options are on the asynchronous electric motors page.
If you tell us the type and outer diameter of the cable you will use via our contact page, we can clarify together the gland type suited to the terminal box entry of the motor you choose. Current model information is on our sales page.
Frequently Asked Questions
Is it enough to select the gland by cable cross-section?
No. The outer diameter of cables with the same cross-section varies with insulation and sheath thickness. The gland is selected by the outer diameter measured with a caliper and the seal's clamping range.
Is a gland entry sealed with silicone acceptable?
It may be a temporary measure, but it is not a permanent solution. Silicone cracks over time and is hard to clean off when the cable changes; a gland of the right size should be used.
What is fitted to an unused entry?
A plug with a washer that matches the entry thread size. A hole left open cancels the motor's protection class at the terminal box.
How tight should the gland be?
According to the tightening value or instructions given by the gland manufacturer. Overtightening can crack a plastic body, undertightening does not hold the cable.
HEM Motor Models Related to This Article
The cards show example models related to the topic. A suitable motor is not chosen by power alone: compare speed, voltage, mounting, shaft and connection dimensions on the product page; if unsure, send a photo of the existing motor’s nameplate on WhatsApp.
Checking that electric motor pulleys lie in the same plane means seeing whether the side faces of both pulleys meet on one straight line. In practice a taut string, a steel straigh... More Details
If an electric motor's coupling element fails often, the first thing to investigate is shaft misalignment, followed by coupling selection, starting and shock loads, environmental e... More Details
The quickest way to tell foundation looseness from unbalance in electric motor vibration is to loosen the foot bolts one at a time while measuring and watch the change, and to comp... More Details
When building a sound enclosure around an electric motor, cooling is preserved by giving the enclosure a labyrinth or silenced inlet large enough for the air the motor fan draws, p... More Details
In an electric motor running in a hot environment, winding and bearing temperatures are monitored separately because they heat up from different sources, have different limits and ... More Details
When an electric motor is started for the first time at sub-zero temperatures, three things need checking: winding insulation resistance and any moisture or ice inside, bearing gre... More Details