Different voltage readings are obtained at an electric motor drive output because a frequency converter does not produce a sine wave but a PWM voltage made of pulses switched at high frequency, and every instrument interprets that waveform in its own way. An average-responding multimeter, a true-RMS meter, a "VFD" mode with a low-pass filter and the drive's own display can show four different numbers at the same moment.
Why can a PWM output not be measured like an ordinary sine wave?
There is no real sine wave at the drive output. The voltage on the DC bus is applied to the motor terminals pulse by pulse through IGBTs switching thousands of times a second; by changing the pulse width, a wave close to a sine is formed in the motor winding, on the current side.
Because the winding inductance smooths the current, the motor "feels" these pulses as a sine. The instrument probe, however, sees the pulses themselves. The peak of each pulse is close to the DC bus voltage, and on a drive connected to a 400 V supply this is clearly higher than the peak of the sine.
What is inside the instrument therefore decides the result.
Most low-cost multimeters measure the rectified average and multiply it by a factor prepared for a sine. When the wave is not a sine, that factor is wrong.
Which instrument shows which value?
Seeing four different readings at the same terminal is not a fault symptom; each instrument measures a different face of the voltage. The table below summarises what each reading tells you (general information; confirm with the instrument manufacturer's instructions).
Measuring method
What it shows
In practice
Average-responding (non true-RMS) multimeter
Average corrected by the sine factor; meaningless on PWM
Unstable number or very different from expected, display jumps
Unfiltered true-RMS multimeter
Total RMS value of the pulses, switching components included
Reads higher than the fundamental; the gap grows at low frequency
"VFD" or "LPF" mode with low-pass filter
RMS value of the fundamental
Closest to the voltage the motor really "sees"
The drive's own display
Output voltage calculated in the drive's control algorithm
Close to the filtered measurement; a calculated, not a measured, number
Oscilloscope with differential probe
Pulse shape, peak value, rise time
The only way to see voltage overshoot on a long cable
The situation maintenance teams meet most often is the gap between the second and third rows. An unfiltered true-RMS reading can come out tens of volts higher than the filtered one, and the technician blames the drive for "giving too much voltage".
Yet the drive is working correctly.
Why does voltage read low at low frequency?
Because in standard V/f control the drive lowers the output voltage in proportion to frequency to keep the magnetic flux in the motor constant. At half the rated frequency, the fundamental voltage also drops to roughly half the rated voltage.
Hypothetical example: if a motor with a 400 V, 50 Hz plate runs at 25 Hz, the filtered measurement shows a value of around 200 V; a little higher if voltage boost at low speed is active. Seeing this value and saying "the drive is giving half voltage" is a mistake; the motor is running at exactly this voltage, with its own flux.
An unfiltered true-RMS meter can show a much higher number at the same point. Since the DC bus stays constant, the height of the pulses does not change, only their width narrows; the total RMS value therefore does not fall in the same proportion as the fundamental. On site this gap stands out most on a fan or pump turning at low speed during the night shift: compare the daytime reading at 50 Hz with the night reading at 20 Hz and the drop shown by the unfiltered meter lags far behind the drop in frequency. At light load and under vector control, the value read can also be lower than at full load at the same frequency. That is why frequency, load condition and the instrument mode used are always written on the record form next to the voltage.
Prices and technical data are on the product pages; choose a model and order online.
What order makes the measurement safe and repeatable?
First check that the instrument is suitable. Measurement at the drive output is made with a multimeter in a measurement category that withstands at least the DC bus voltage, preferably one with a VFD/LPF mode; the insulation of the test leads must be in the same class.
Note the output frequency and the voltage boost setting from the drive parameters; you will compare the reading with these values.
With the motor under load and at a steady frequency, switch the multimeter to VFD mode and read the three line-to-line voltages at the drive output terminals.
Repeat the same three measurements at the motor terminal box. A large difference between the two points indicates a cable or connection problem.
Write the values on the same form as the output voltage on the drive display.
If the cable is long or the motor winding has a history of insulation failure, also look at the pulse peak at the motor end with a differential-probe oscilloscope.
Phase-to-earth measurement is misleading here.
Reading phase-to-earth voltage between drive and motor with an ordinary multimeter gives no meaningful result. Because of common-mode voltage the display can show random values; this reading alone is no proof of an insulation fault.
Voltage at the drive output is measured with the motor under load and at a steady frequency (representative image).
What does the difference between the drive and the motor terminals tell you?
In the filtered measurement a small difference between the two ends is normal and shows the voltage drop in the cable. A clearly low value in one of the phases, however, means a loose terminal, a burnt contactor contact or a damaged cable core.
With an oscilloscope the picture changes. On a long motor cable, each pulse can reflect at the motor end and push its peak above the DC bus voltage. This overshoot is invisible on a multimeter but stresses the insulation of the first turns of the winding. Our three-phase series are suitable for speed control with a frequency converter; for long periods of full torque at low speed an external fan may be needed; if the drive-to-motor cable is long, a dv/dt or sine filter is considered; these conditions are stated with the order.
In a system with a sine filter fitted, the wave at the motor end is very close to a sine and an ordinary true-RMS measurement is enough. A dv/dt filter only softens the rise rate of the pulse; the wave is still PWM and a filtered measurement is needed.
Which reading is a real sign of a problem?
In the filtered measurement, a clear unbalance between the three phases, a large mismatch with the drive display, or a sudden drop at the motor terminals compared with the drive output should be investigated. A high reading on an unfiltered meter is not a problem on its own.
Motor current should be read as well. If voltage looks normal but current is unbalanced, the cause is sought in the winding or the connection. The same rule applies to current measurement: a true-RMS clamp is used at the drive output, and the drive input current is not taken as the motor current.
For the checks before connecting a new motor, our commissioning guide describes the order of first energising. Typical options for spare or new motors to be driven by a drive are listed in our electric motor shop:
100L2-4, aluminium frame, 3 kW, 1450 rpm, 6.02 A, 230/400 V. Connected in star on a drive with 400 V output.
132M-4, aluminium frame, 7.5 kW, 1460 rpm, 14.3 A, 400/690 V. Connected in delta on the same drive.
132S-4, cast iron, 5.5 kW, 1460 rpm, 10.7 A, 400/690 V. The frame preferred on vibrating and dusty machines.
These models have IP55 protection and class F insulation; drive cable length and running time at low speed are stated with the order. The whole family is on the 3-phase asynchronous electric motors page.
Write the drive display, the filtered measurement and the motor terminal readings into one table and send it with a photo of the motor nameplate through our contact page; together we will separate whether the difference comes from the measuring method or from the installation. Different frame options at the same power sit side by side on our sales list.
Frequently Asked Questions
Why is a true-RMS multimeter not enough at the drive output?
An unfiltered true-RMS meter also adds up the switching components and reads higher than the fundamental. To see the voltage the motor runs on, a VFD mode with a low-pass filter is needed.
Can the voltage on the drive display be trusted?
The display value is a calculated, not a measured, output voltage. It is good enough for comparison and trend tracking; when looking for a connection problem, it should be verified with a filtered measurement at the terminals.
Which instrument is used after a sine filter?
Since the wave at the filter output is close to a sine, a standard true-RMS multimeter is enough. Before the filter, VFD mode is still required.
Why does the voltage peak at the motor terminals matter?
Reflection on a long cable increases the pulse voltage on the winding insulation. This value is invisible on a multimeter; it is measured with a differential-probe oscilloscope and affects the filter decision.
HEM Motor Models Related to This Article
The cards show example models related to the topic. A suitable motor is not chosen by power alone: compare speed, voltage, mounting, shaft and connection dimensions on the product page; if unsure, send a photo of the existing motor’s nameplate on WhatsApp.
Checking that electric motor pulleys lie in the same plane means seeing whether the side faces of both pulleys meet on one straight line. In practice a taut string, a steel straigh... More Details
If an electric motor's coupling element fails often, the first thing to investigate is shaft misalignment, followed by coupling selection, starting and shock loads, environmental e... More Details
The quickest way to tell foundation looseness from unbalance in electric motor vibration is to loosen the foot bolts one at a time while measuring and watch the change, and to comp... More Details
When building a sound enclosure around an electric motor, cooling is preserved by giving the enclosure a labyrinth or silenced inlet large enough for the air the motor fan draws, p... More Details
In an electric motor running in a hot environment, winding and bearing temperatures are monitored separately because they heat up from different sources, have different limits and ... More Details
When an electric motor is started for the first time at sub-zero temperatures, three things need checking: winding insulation resistance and any moisture or ice inside, bearing gre... More Details
We use necessary and optional cookies to improve your experience, enhance content and analyse traffic. Under the GDPR, optional (analytics/marketing) cookies are only used with your explicit consent. Please choose your preference below.
Cookie Policy