An electric motor draws more current at low voltage because, as long as the load on the shaft stays the same, the motor has to supply the same power with less voltage, and the only way to do that is to raise current. With a heavy load the rise is clear; on a lightly loaded motor the magnetising current falls, so total current may not change and can even drop.
How does the power formula explain this rise?
On a three-phase supply, active power is the product of voltage, current and power factor; if shaft power is constant, a drop in voltage comes back as a rise in current. The formula is:
Pshaft = √3 × U × I × cosφ × η
The machine does not know about it. A pump, belt or crusher does not ask for less work because the supply is a few volts short; the torque requirement stays the same, and because speed drops only slightly, Pshaft stays roughly constant. When U gets smaller, the quantity that keeps the equation balanced is I (general information; confirm with the machine manufacturer).
That is not the end of it.
At low voltage the motor's ability to produce torque falls with the square of voltage. To deliver the same load torque the rotor needs more slip; as slip grows, rotor current and the stator current linked to it rise. A motor with 1460 rpm on its plate turning a few revolutions slower at low voltage is how this slip shows up on site.
Hypothetical calculation: how much does current rise at ten percent low voltage?
It rises roughly in proportion to the voltage drop, plus a small extra share from slip. Assume an 11 kW, 4-pole motor with 20.4 A at 400 V on its plate runs at full load and the terminal voltage falls to 360 V.
The active component grows. The ratio is roughly 400 / 360 ≈ 1.11. The magnetising component falls somewhat with voltage; when the two are added as vectors, stator current climbs to about 22 A. The calculation is a rough model, but the direction is right: a fully loaded motor exceeds its plate current at low voltage.
Heat rises faster. Because copper losses grow with the square of current, when current is 1.1 times higher, the heat released in the winding goes up to about 1.2 times. If the thermal relay is set to plate current, it starts tripping at summer noon, in the busiest hour of the grid, and the fault gets blamed on the motor.
If the same motor runs at half load the picture is different. Most of the current is the magnetising component; when voltage drops this component also falls and the clamp meter shows almost the same value, sometimes a little lower. That is why the observation "voltage fell, current rose" on its own also reveals how heavily the motor is loaded.
Why does low voltage make starting harder?
Starting torque is proportional to the square of voltage; with voltage ten percent low, the motor can give only about eighty-one percent of its rated starting torque (general information; confirm with the machine manufacturer). A full screw conveyor, a loaded bucket elevator or a piston compressor under pressure starts with difficulty after that loss.
This is where the vicious circle begins. As the start drags on, high starting current flows through the supply cable for extra seconds, creates additional voltage drop in the cable and the voltage reaching the motor terminals falls further. A longer hum on site, lights dimming clearly at the moment of starting and the motor being tripped by protection before it gets up to speed are the signs of this circle.
With star-delta starting the situation is more delicate, because in star the motor already starts with roughly one third of rated torque. If low voltage is added on top of that, the motor has not accelerated at the changeover and enters delta with a large current surge.
Where and how is voltage drop measured on site?
At two points, at the same time and under load. The panel may read 400 V while the motor terminals show a much lower value; the difference is the share of the cable and connections.
- Run the motor at its normal load; voltage measured at no load does not show cable drop.
- With a true-RMS multimeter, read the three phase-to-phase voltages at the contactor output in the panel.
- In the same minute, take the three phase-to-phase voltages in the terminal box and the three phase currents with a clamp meter.
- Note the difference between panel and terminals together with the current values; a clearly larger difference on one phase points to a loose connection or an oxidised terminal.
- If you suspect looseness, complete the measurement with a thermal camera; a hot terminal screw stands out in the image straight away.
Measure the start as well. A power analyser with recording shows the voltage dip at starting; a line that looks fine in continuous running can collapse unacceptably at start-up.
Cable size and fuse values are not given here; they are calculated by the engineer preparing the electrical design from cable length, installation method, starting method and permitted voltage drop, and approved according to the regulations.