The surge (impulse) test applies short, high-voltage, very fast-rising pulses to an electric motor winding and compares the damped oscillation wave the winding returns in order to detect turn-to-turn short circuits. Insulation resistance and winding resistance measurements often cannot see this kind of fault, because the insulation between turns looks sound at low voltage but breaks down during mains switching or inverter pulses. The surge test catches this weak point before the motor starts running and before the fault turns into a phase-to-phase or phase-to-earth short circuit.
Why is turn-to-turn insulation the first weak link?
Between neighbouring wires in a coil there is only the enamel layer and the varnish. In normal 50 Hz operation the voltage between two adjacent turns is small. But during starting, contactor switching or the fast switching of a frequency inverter, the voltage is not distributed evenly across the coil but piles up on its first turns. A small scratch in the enamel, a wire crushed during winding or varnish that has absorbed moisture breaks down under this build-up.
The breakdown point first short-circuits a few turns. By transformer action a large current circulates in the shorted turns, the area heats rapidly and burns the surrounding insulation. The result is usually a phase-to-earth or phase-to-phase fault within a few hours or days. That is why early detection is cheap and late detection costs the entire winding.
What does the impulse wave tell you about the winding?
The tester charges a capacitor to a high voltage and discharges it rapidly through the winding under test. The capacitor and the winding inductance form an LC circuit and a damped sine wave appears on the screen. The oscillation frequency is given approximately by f = 1 / (2π · √(L · C)), where L is the winding inductance and C the tester's capacitor.
If there is a short between turns, the shorted turns reduce the effective inductance of the winding and increase losses. This has two visible consequences. The wave frequency rises, so the wave shifts to the left. Damping also speeds up, and the wave amplitude shrinks faster. In a sound winding, the waves of the three phases of the same motor lie almost exactly on top of each other.
A hypothetical frequency shift example
Let the sound phase oscillate at around 10 kHz. When a few turns are shorted in one phase, the effective inductance drops by a few per cent; because of the square-root relationship the frequency rises by less than that, but clearly enough to be visible on the screen. For example, if inductance drops by about 4%, frequency rises by about 2% and the wave shifts a few hundred hertz to the left. These ratios are general knowledge; follow the test equipment manufacturer's instructions for interpretation.
How is the test voltage selected?
The impulse voltage must be high enough to represent the worst voltage stress the winding will face in service, and limited enough not to overstress sound insulation. In practice the test voltage is set according to the motor's rated voltage and whether the winding is new or used; a higher value is chosen for a new winding and a lower one for an old winding from the field. For the numerical value, follow the test equipment manufacturer's table and the workshop's written procedure.
The rise time of the pulse also matters. A very fast voltage rise concentrates the stress on the first turns of the coil and creates a situation similar to inverter pulses in the field. The voltage is increased in steps and the wave is recorded at each step. If a fault suddenly appears at a certain voltage, that voltage shows the real withstand limit of the insulation.

How is the impulse test applied step by step?
- Disconnect the motor completely from the mains and the drive, and remove the links and supply cables in the terminal box.
- First measure insulation resistance; if phase-to-earth insulation is weak, do not proceed to the impulse test.
- Measure the winding resistance of all three phases; note any marked imbalance, as it will be interpreted together with the surge result.
- Connect the tester between the first phase and the others and increase the voltage in steps, starting low.
- Record the wave of each phase at the same voltage and overlay them on the screen for comparison.
- If a difference appears, repeat the measurement; if the shift remains, write the faulty phase and the voltage value in the report.
On installed motors the rotor position can slightly affect the wave; in a doubtful case, turning the shaft a little and repeating the measurement separates a rotor-related difference from a turn fault. In measurements made through a long supply cable, cable capacitance changes the wave, so where possible the test should be done directly at the terminals.