Leakage on an electric motor housing is investigated after the supply has been isolated and locked: first the continuity of the earth conductor is checked, then the insulation resistance between each phase winding and the housing is measured. If voltage can be felt on the housing, the cause is usually either a broken or loose earth conductor or winding insulation weakened by moisture, dust or ageing.
What is the first step if voltage is felt on the housing?
Stop the machine, open the supply isolator, lock and tag it, then confirm absence of voltage with a suitable detector. Skipping this order makes the person investigating the next target of the same leakage.
The first sign on site is usually a slight tingle, a spark between the housing and a nearby pipe or base, or a residual current device that trips for no apparent reason. A device that trips on a washing line running on wet floors, or at the first start in the morning, suggests that moisture has reached the winding.
Pen-type non-contact detectors give only preliminary information. Concluding that the winding is faulty because the detector "beeps" on the housing is premature; capacitive coupling and an unearthed housing produce the same signal.
In what order is earth continuity checked?
First verify, with an instrument able to measure low resistance, that the protective conductor from the housing to the earth bar in the panel is not broken anywhere. Take the measurement from an unpainted point on the motor housing or from the earth screw.
The earth screw inside the terminal box may have loosened, its lug may be oxidised, or the green-yellow conductor may have pulled out of the lug. On vibrating machines, a screen or a feeder for example, this connection works itself loose over time. If there is a joint along the cable trunking, check that too.
The reading is interpreted by comparing it with other motors on runs of similar length. The acceptance limit and periodic inspection of the circuit are a matter for the site's responsible electrical person and the regulations in force; the aim here is to catch a broken or high-resistance connection.
If the earth is sound, the leakage is real and the search for its source continues. The housing and terminal box layout of HEM Motor series can be seen in the product photos on the store page.
How is winding insulation measured and how is the result interpreted?
Insulation resistance is measured with an insulation tester (megger) between each phase winding and the housing, and between phases, after the motor cable has been disconnected from the terminals. The test voltage is chosen to suit the motor's rated voltage; any electronic board, sensor or frequency inverter in the circuit is disconnected first.
- Open the terminal box, remove the supply cables, and photograph and remove the links.
- Measure each of the three phase windings in turn against the housing; read the value at the end of one minute.
- Repeat the measurement between phases; a low phase-to-phase value shows that a bridge has formed between windings.
- When finished, discharge the charge left in the winding by touching the leads to the housing for a while.
- Write the motor temperature and ambient humidity on the same form; the value changes noticeably with temperature.
If the readings are close to each other on all three phases but low, the whole winding has probably absorbed moisture. A value that is low on only one phase and normal on the others points to insulation damage at one point in that winding, most likely a crack at the slot exit or at a lead connection. The lower acceptance limit is set by the motor manufacturer's instructions and the relevant standards; comparing with earlier records of the same motor gives a more accurate picture than clinging to a single figure (general information; confirm with the instrument maker's instructions).

Is the source of the leakage the motor, the cable or the drive?
The way to isolate the source is to split the measurement into parts: first disconnect the motor cable and measure the motor alone, then measure the cable alone without the motor. Whichever part shows the low value holds the leak.
On the cable side, crushed trunking, rodent damage or a junction box full of water are common causes. Opening the trunking cover reveals chafe marks on the cable or a blackened joint.
With motors driven by a frequency inverter the situation is a little different. Fast switching at the drive output pushes a small current to earth through the cable's capacitance, and this current can trip the residual current device; the housing is thought to be "leaking" although the winding is sound. Cable length, use of screened cable and the drive filter are the first things to check in this case. Our three-phase series are suitable for speed control with a frequency inverter; for long periods at low speed with full torque an external fan may be needed; if the drive-to-motor cable is long, a dv/dt or sine filter is considered; these conditions are stated with the order.
The terminal box is not overlooked either. If its gasket has failed or the cable gland is loose, water getting in forms a conductive film on the terminal board. Seeing rust marks, white salt deposits or water droplets at the bottom of the box almost completes the diagnosis.