The equivalent circuit of an induction electric motor reduces the stator and rotor to a simple electrical diagram of resistances and inductances for a single phase: stator resistance R1, stator leakage reactance X1, magnetising reactance Xm, iron loss resistance Rfe, rotor leakage reactance referred to the stator X2', and the slip-dependent rotor resistance R2'/s. Once these six parameters are known, the motor's current, torque, power factor and efficiency at any load can be estimated by calculation. Below we explain the physical meaning of each element, which tests the parameters come from and how the model is used in the field.
The per-phase T circuit: what does each element represent?
A symmetrical three-phase motor is analysed through a single-phase circuit; results are multiplied by three to get the total power. In the classic T equivalent circuit, current from the supply first passes through the stator resistance and leakage reactance, then splits into two branches: one is the magnetising branch, the other the rotor branch.
- R1 – stator winding resistance: Gives the stator share of copper losses; it rises with temperature.
- X1 – stator leakage reactance: Represents flux that closes in the stator slots and end windings without crossing the air gap.
- Xm – magnetising reactance: Represents the flux that builds the rotating field in the air gap. As the air gap grows, Xm falls and no-load current rises.
- Rfe – iron loss resistance: A parallel element modelling hysteresis and eddy current losses in the stator laminations; in most practical calculations it is neglected or added as a fixed loss.
- X2' – rotor leakage reactance: Leakage flux closing around the rotor bars; a value referred to the stator.
- R2'/s – rotor resistance and mechanical load: Rotor resistance divided by slip; it also carries the power delivered to the shaft.
Why does R2'/s carry mechanical power? Slip and power split
Slip is the difference between the speed of the rotating field and the actual shaft speed, divided by the field speed: s = (ns − n) / ns. On a 50 Hz supply the field of a 4-pole machine turns at 1500 rpm; if the shaft runs at 1460 rpm, s = 40 / 1500 ≈ 0.027.
The term R2'/s can be split in two: R2'/s = R2' + R2' × (1 − s) / s. The first part represents rotor copper loss, the second a virtual load resistance standing for the mechanical power transferred to the shaft. For the power Pag crossing the air gap to the rotor, the following relations apply (general knowledge, covered in detail in electrical machine textbooks):
- Rotor copper loss = s × Pag
- Internal mechanical power = (1 − s) × Pag
- Electromagnetic torque = Pag / ωs (ωs synchronous angular speed)
This relation explains why slip is directly linked to efficiency: the larger the slip, the bigger the share of air-gap power turned into heat in the rotor.
Which tests give the parameters?
The equivalent circuit parameters are derived from three measurements. The tests are usually the job of the motor manufacturer or a well-equipped workshop; in the field, knowing the principle helps interpret measurement results.
| Test | How is it done? | What does it give? |
|---|---|---|
| DC resistance measurement | Resistance is measured with direct current between winding terminals and the winding temperature is recorded | R1 (converted to a phase value according to the connection) |
| No-load test | The motor runs unloaded at rated voltage; voltage, current and power are measured | Xm, iron and friction losses |
| Locked-rotor test | The rotor is locked and a low voltage is applied until rated current flows; voltage, current and power are measured | Sum X1 + X2' and R1 + R2' |
In the no-load test slip is almost zero, so the rotor branch behaves like an open circuit and current flows mostly through the magnetising branch. In the locked-rotor test s = 1; since R2'/s stays small, the magnetising branch can be neglected and the measured impedance is mostly the series branches. The split between X1 and X2' is usually made with ratios from standard tables or by assuming them equal (the IEC 60034 family describes the general framework of these tests; for the detailed procedure refer to the relevant standard and the test equipment instructions).

Hypothetical example: current, torque and efficiency from the circuit
To show the logic of the calculation, take a 400 V, star-connected, 4-pole motor; the phase voltage is 400 / √3 ≈ 231 V. Hypothetical parameters: R1 = 0.5 Ω, X1 = 1.2 Ω, R2' = 0.45 Ω, X2' = 1.5 Ω, Xm = 40 Ω, Rfe neglected. Let the motor run at 1460 rpm, i.e. s ≈ 0.027.
- Rotor branch: R2'/s ≈ 0.45 / 0.027 ≈ 16.7 Ω; rotor impedance ≈ 16.7 + j1.5 Ω.
- This branch is in parallel with Xm; the parallel combination comes to about 13.4 + j6.8 Ω.
- Adding the series branch gives a total impedance ≈ 13.9 + j8.0 Ω, magnitude ≈ 16.0 Ω.
- Phase current ≈ 231 / 16.0 ≈ 14.4 A; power factor ≈ 13.9 / 16.0 ≈ 0.87.
- Air-gap power ≈ 3 × I² × 13.4 ≈ 3 × 14.4² × 13.4 ≈ 8.3 kW; internal mechanical power ≈ (1 − 0.027) × 8.3 ≈ 8.1 kW.
- Electromagnetic torque ≈ Pag / ωs ≈ 8300 / 157 ≈ 53 Nm (ωs = 2π × 1500 / 60 ≈ 157 rad/s).
Once friction, windage and iron losses are deducted, the shaft power drops a little further. These figures are hypothetical; the point is to show how the equivalent circuit leads from a slip value to current, torque and power. Efficiency comes from the same circuit: shaft power divided by the input power calculated as 3 × Uphase × I × cos φ.