Most screw compressors start unloaded with an unloader valve: loading begins after the motor reaches full speed and starting is complete. The torque to overcome at start is then low. On a piston compressor, if the cylinder or line remains pressurised, the motor may have to start against load.

CaseLoad seen by the motorSelection focus
Unloaded startLow torque at start, then continuous full loadHeating under continuous load, S1 duty, efficiency
Loaded startHigh torque from standstillStarting torque (Ts/Tn), starting time, suitability for the starting method

The starting method also affects starting torque: with star-delta starting, motor torque drops to about one third, so on a compressor that starts loaded the motor may fail to accelerate in star. In the catalogue's 4-pole IE3 motors, starting torque is 2.0 to 2.4 times rated torque depending on power.

When ordering, state the compressor type, whether it starts loaded or unloaded, the number of starts per hour and the starting method. Range: compressor motors; starting options are covered in motor connection and starting questions.