The rated current of a three-phase motor is I = P2 / (√3 × U × η × cos φ). Even with the same power, a different efficiency, cos φ or voltage gives a different current.
| 7.5 kW IE3, 400 V | cos φ | Efficiency | Rated current |
|---|---|---|---|
| 2-pole (2,930 rpm) | 0.88 | 90.1% | 13.7 A |
| 4-pole (1,460 rpm) | 0.84 | 90.4% | 14.3 A |
| 6-pole (970 rpm) | 0.79 | 89.1% | 15.4 A |
The values come from the IE3 tables in the HEM Motor catalogue. As the pole number rises, the share of magnetising current grows, cos φ falls and the current increases.
Other reasons for the difference:
- Voltage: the same motor draws slightly more current at 380 V than at 400 V; 15.0 A versus 14.3 A in the 4-pole example.
- Load: current measured on site depends on the load at that moment; the nameplate current applies only at rated load.
- Design and efficiency class: from another manufacturer or IE class, the current for the same kW can differ by a few percent.
- Phase imbalance: voltage imbalance also unbalances the currents.
For this reason, overload protection must be set to the nameplate current of the motor actually installed, not that of another motor.