Three-phase motors between 30 and 90 kW draw roughly 52 A to 161 A at 400 V. Cables and breakers are sized starting from this nameplate current, taking the starting method and the cable route into account.

Power (kW)3,000 rpm (A)1,500 rpm (A)1,000 rpm (A)
3052.153.856.2
3764.066.168.1
4576.880.281.6
5593.597.698.1
75127129136
90152155161

Values are the nameplate ratings of the models in the HEM Motor catalogue; they may differ for other brands or series.

How are breakers and contactors sized?

With direct-on-line starting, the motor protection breaker, contactor and thermal relay are chosen for the motor's line current, i.e. the value in the table. With star-delta starting, the main and delta contactors carry the winding current: Iwinding = Iline / √3 ≈ 0.58 × Iline. The star contactor sees roughly Iline / 3.

Example: the 45 kW 1,500 rpm 225M-4 motor has a nameplate current of 80.2 A. Assumption: 400 V supply, star-delta starting, thermal relay at the output of the main contactor. The main and delta contactors must carry at least 80.2 / √3 ≈ 46.3 A in category AC-3 and the star contactor at least 80.2 / 3 ≈ 26.7 A; the thermal relay is set to 46.3 A. The supply breaker and supply cable are chosen for the full line current of 80.2 A.

Cable cross-section

The cross-section cannot be read from the current alone: installation method (cable tray, conduit, underground), ambient temperature, the number of cables running side by side and the voltage drop due to length are assessed together. With star-delta, two separate three-core cables run to the motor and each carries the winding current. The calculation should be done by an electrical engineer; for the method see the question on motor cable cross-section.

Models in these ratings are in the cast iron frame electric motors category. For panel preparation, the article on panel checks when ordering a 30 kW motor is also useful. Send a photo of the existing motor's nameplate on WhatsApp and we will confirm the equivalent model and its nameplate current together.