When buying a three-phase AC asynchronous motor, most businesses select the power and speed correctly; but when the motor is installed on site and started for the first time, unexpected problems appear: the breaker trips, the lights of other devices on the main panel dim, the belt flies off the pulley, or there is a knocking sound in the reducer gears. Most of these stem not from the motor, but from the wrong choice of starting method. The right starting method is a purchasing decision that directly affects the motor's lifespan, the cost of the panel and the plant's energy infrastructure. This article explains, from the eyes of the person making the purchasing decision, which of the direct-on-line (DOL), star-delta, soft starter and frequency inverter (VFD) options your business should prefer. As HEM Motor, manufacturing electric motors since 1979, we supply motors together with the right starting recommendation, in the 0.55–355 kW range from our stock in Türkiye.

AC asynchronous motor terminal box and star-delta connection bridges

Starting Current: The Heart of the Starting Decision

When an asynchronous motor starts from standstill, it draws roughly 3 to 7 times its rated current from the grid; in standard industrial motors this ratio is typically around 6 times. A 22 kW three-phase motor with a rated current of about 42 A can exceed 250 A at the moment of starting in direct-on-line starting. This brief inrush current directly determines the selection of breakers and fuses, the cable cross-section, the contactor size and the transformer/generator capacity. Choosing a starting method is, in effect, deciding how much you want to soften this starting inrush.

Alongside the starting current there is also the starting torque. While loads such as pumps and fans start lightly with little load, loads such as crushers, mills, conveyors and compressors start heavily. Because the starting method affects both the current and the starting torque, the character of the load directly determines the method selection. A wrong match means either the motor failing to start (constantly tripping the overload relay) or extra cost from an unnecessarily large panel.

Direct-On-Line (DOL): The Simplest and the Harshest

Direct On Line is connecting the motor directly to the rated voltage. A single contactor and an overload relay are enough; it is the cheapest and most robust solution. At small powers — in practice, for motors below about 5.5–7.5 kW — DOL is almost always used, because the starting inrush does not create a problem for the grid. Its disadvantage is that it applies the full starting current and full starting torque to the field; in large motors this both strains the grid and jolts the mechanical transmission elements such as belt-pulley, coupling and reducer with a harsh torque.

Star-Delta: Economical and a Classic at Medium Power

Star-delta starting first starts the motor in star connection (the voltage across the winding is reduced), then a few seconds later switches it to delta connection. In the star position, the starting current and starting torque drop to about one-third. Built with three contactors and a time relay, this system is the most economical current-limiting method for medium-power motors. It is very common especially in pump, fan and exhaust fan applications that can start unloaded or lightly loaded.

The limit of star-delta is this: if the motor starts heavily together with its load, it may fail to start at all with the low torque of the star position, or a current/torque surge occurs at the moment of switching to delta. That is why star-delta is often unsuitable for loads requiring high starting torque, such as jaw crushers and pellet presses.

Soft Starter: Smooth Starting and Frequent Switching

A soft starter raises the voltage gradually with thyristors, bringing the motor up without inrush. The starting current is kept at an adjustable limit; the starting ramp is programmed second by second. Its advantages: inrush-free, adjustable starting for the mechanical transmission, soft stop in most models, and stable operation in frequently switched applications. Conveyors, compressors, large fans and water pumps are typical addresses for soft starters; they are especially valuable in pump lines where water hammer is to be prevented.

A soft starter does not change the motor's speed; it only manages starting and stopping. If continuous speed adjustment is needed, the right device is not a soft starter but a frequency inverter.

Frequency Inverter (VFD): When Speed Control Is Needed

A VFD (variable frequency drive) provides both a smooth start and continuous adjustment of the motor's speed by changing the frequency supplied to the motor. By throttling the flow in pumps and fans it provides significant energy savings, which makes the VFD not just a starter but an efficiency tool. Its cost is higher than a soft starter and it requires application engineering; but wherever the process speed needs to change (adjusting flow, speed, cycle time), this is the only correct solution. As in our IE3 vs IE4 investment decision article, in VFD applications too the efficiency class determines the total energy cost. When selecting a motor to be driven by a VFD, one point needs attention: in motors that will run for long periods at low speed with the drive, cooling weakens, so a force-cooled (separately ventilated) motor or one frame size larger may be preferred. Stating at the order stage whether the motor will run with a VFD or directly from the grid ensures the right motor arrives.

A Quick Comparison of the Four Methods

If we gather the four methods into a single frame: DOL lowest initial investment, highest starting inrush; star-delta low investment, medium-level current limiting, but low starting torque; soft starter medium investment, very low mechanical inrush, adjustable starting; VFD highest investment, smooth starting plus speed control plus energy savings. When deciding, you need to look not only at the device price but at the total cost of the panel, the lifespan of the motor and transmission elements, and the energy bill together. For most businesses, the most expensive scenario is the motor failing early and production stopping because of the wrong starting method.

Star and Delta Connection in the Terminal Box

In the terminal box of three-phase motors there are six terminals (U1-V1-W1 and U2-V2-W2). These terminals are connected with bridges in star (Y) or delta (Δ). The motor nameplate usually states two voltages (for example 400/690 V). Here the low voltage corresponds to delta and the high voltage to star connection. On a 400 V grid this motor is operated connected in delta; if it is to be used with a star-delta starter, the running position is still delta, and star is only the starting position.

This distinction is critically important at the order stage: the motor's nameplate voltage must match your grid and your chosen starting method. If you are going to use star-delta, the motor must have a winding that can run in delta at 400 V. A motor that arrives with the wrong winding voltage provides neither star-delta nor correct operation. Our exact matching from nameplate information guide helps you prevent such mistakes before ordering. We addressed the relationship of starting current with generator capacity from a separate angle in our motor selection on a generator-powered site article; on generator-fed sites the starting method is even more decisive.

Connecting the terminal bridges incorrectly is one of the most common mistakes seen in the field. If a motor that should run in delta on a 400 V grid is mistakenly connected in star, it delivers only one-third of its power; it cannot lift a heavy load, is constantly strained and heats up. In the opposite case — a winding designed for 690 V connected in delta at 400 V — the motor draws excessive current and its winding can burn out. For this reason, when commissioning a motor, the nameplate voltage, grid voltage and terminal bridge position must be checked together. The rotation direction of a three-phase motor can be reversed by swapping any two phases; in direction-critical applications such as pumps and fans, the rotation direction must be verified at the first start. All these checks are completed within minutes when you start with a motor of the correct winding voltage and correct nameplate.

Star-delta contactor panel and soft starter comparison

Which Method Should I Choose? A Practical Decision

To simplify the purchasing decision, a practical framework: (1) If the motor is below about 5.5 kW and the load is light, DOL is sufficient. (2) At medium power (roughly 7.5–45 kW), if the load starts unloaded/lightly and your priority is budget, star-delta is the economical solution. (3) If you want to prevent mechanical inrush, switch frequently or achieve a soft stop, a soft starter is the right choice. (4) If you want to change the process speed or save energy in a pump/fan, a VFD is selected.

Let us make it concrete with application examples. A 15 kW non-submersible centrifugal pump feeding a water tank runs economically with star-delta because it starts unloaded; however, if there is a water hammer problem in the line, a soft starter is more suitable. A 7.5 kW motor driving a grain conveyor starts loaded, so it starts smoothly with a soft starter while preserving belt tension. On a 30 kW motor driving a screw compressor, the need for frequent switching and a smooth start makes the soft starter stand out. The 45 kW motor of a jaw crusher in a crushing plant, on the other hand, requires high starting torque and is therefore generally driven with direct-on-line or a properly sized soft starter; the low torque of star-delta falls short here. As you can see, the method is determined more by the character of the load than by the power of the motor.

One more caution in terms of investment planning: when choosing the starting device, also consider the possibility of a future speed/power change in the motor. In a plant that runs at fixed speed today but will tomorrow need speed adjustment for process optimization, moving to a VFD from the start is advantageous in terms of both infrastructure and energy. Our article on the information to provide when requesting a quote will also clarify your decision regarding fast delivery from stock and correct winding selection.

The motor-side counterpart of this decision is also important: for heavy-starting applications, high-starting-torque, cast iron frame motors are preferred. As HEM Motor, we recommend our 3-phase electric motors and compressor motors according to the application's starting need. Across our entire high-efficiency motor and IE4 motor range, star-delta and soft-starter compatible winding options are available. If you want to expand the subject from the application side, you can also take a look at our geared motor versus separate motor + reducer article; in geared systems, a smooth start extends gear life. For a deeper technical comparison, you can review the articles in our Asynchronous / AC Motors blog category.

How Does the Starting Method Affect Motor Selection?

The starting method affects not only the panel but also the specifications of the motor to be purchased. The first issue is the winding voltage: a motor to be used with star-delta must have a dual-voltage winding that can run in delta at 400 V and in star at 690 V. The second issue is starting torque: for heavy-starting loads, motor designs that produce high starting torque should be preferred; otherwise no starting method can lift the load. The third issue is duty type: in frequently switched applications, the motor must be durable against the number of starts and have sufficient thermal reserve.

These three headings show why selecting the right motor from the very beginning cannot be considered independently of the starting method. As HEM Motor, in our production we offer all motors with the very common 400/690 V winding option, with Class F insulation and IP55 protection; this directly meets the great majority of star-delta, soft-starter and VFD applications. For crusher, mill and mining applications requiring heavy duty and high starting torque, we recommend cast iron frame, reinforced-bearing motors. Our stone crushing-screening plant motors are designed for these demanding starting conditions. The right motor + right starter match optimizes both the initial investment and the long-term energy and maintenance cost.

A practical summary on the cost side: the difference you pay for your panel is in most cases recovered within a few years by the extra lifespan gained by the motor and the transmission elements. The downtime cost of replacing a coupling worn by a harsh start or a burned-out winding is far above the investment made in the right starter from the outset. That is why the starting decision should be treated not as an "extra expense" but as an integral part of the motor investment.

Frequently Asked Questions

Is star-delta starting used on every motor?

No. Star-delta is meaningful only on motors wound to run in delta on a 400 V grid (for example, labeled 400/690 V) and able to start in the star position together with their load. If a heavy-starting load cannot start with the low torque of the star position, a soft starter or VFD should be preferred over star-delta. If you share your application with us before ordering, we will recommend the motor with the correct winding voltage.

Soft starter or VFD — which is better?

It depends on the need. If you only want to soften starting and stopping, a soft starter is more economical and sufficient. If you want to continuously change the motor's speed or save energy in a pump/fan, a VFD is needed. A soft starter does not change the speed; therefore, where process speed adjustment is required, a VFD is the only correct solution.

Does the wrong starting method damage the motor?

Yes. Lifting a heavy load with direct-on-line starting increases the starting current and mechanical inrush, leading to winding heating and wear of bearings and couplings. A motor that cannot start with insufficient torque (for example, an unsuitable star-delta) constantly trips the overload relay and its winding burns out over time. The right method extends the lifespan of both the motor and the transmission elements.

Get a Quote

Share with us the character of the load in your plant and your existing panel infrastructure; let us recommend an AC asynchronous motor that is both of the right power and the right winding voltage, suitable for the starting method. As HEM Motor, we deliver motors quickly from our stock in Türkiye and provide technical support on starting. To get a quote right away, call us: +90 (532) 345 49 86 or reach us via our contact us page.